DESIGNLINK CALC · calc.designlink.in
UGT / WTP & pump room
Step-by-step user guide — from the population and the fire-tank capacity to the sized tanks, the fire and plumbing pumps, the treatment train, a layout that fits the plot (even an irregular one), the DXF drawing with sections and schedules, and a 3D model.
Written for anyone in the office. You need a browser, your DesignLink login, the building's population (or daily demand), the fire-tank capacity agreed with the fire authority, and the shape of the space available.
Version 1.0 · September 2026
What this tool does
It reproduces the standard UGT + pump-room package: raw-water and treated (domestic) tanks, an optional flushing tank, the fire static tank split into compartments, and a pump room between them holding the filter-feed pumps, the multi-grade and activated-carbon filters, ozonator and chlorine dosing, the hydro-pneumatic (or transfer) pumps with pressure vessels, and the fire pump sets — electric main, diesel standby and jockey for hydrant and sprinkler, plus the water-curtain set when needed. The flow never changes; the sizes, the number of compartments, the depth, the location and the arrangement of the tanks change with your inputs and with the space you have.
Everything you type is a default you can override. Results update as you type; when you are happy, save and download the report, the Excel (live formulas), the DXF and look at the 3D model.
Contents
- Open the tool and name the project
- Tank & site
- Domestic demand and storage
- Fire water — confirm the capacity
- Tank construction
- Space available — rectangle or polygon
- Treatment and plumbing pumps
- Reading the results
- Plan, 3D and schedules
- Outputs: report, Excel, DXF
- Frequently asked questions
1. Open the tool and name the project
a. calc.designlink.in → UGT / WTP & pump room (or open /ugt/). Sign in when asked.
b. Type the project / reference name at the top (e.g. "Tower A — UGT & pump room"). The six tiles beside it are the key figures and go green / red with the checks.
c. The left card holds the inputs in seven groups; the right card has four tabs — Results, Plan, 3D, Schedules.
2. Tank & site
| Input | What to enter |
| Tank type | Underground (the usual: top slab below ground, pump room sunk to the tank floor so the pumps have positive suction), Over-ground (tank on the surface, pump room beside it) or Overhead (on a staging — enter the staging height). |
| Earth / landscape cover | Depth of filling above the top slab. 0 when the slab is at ground; 1.5–2 m when a garden runs over the tank (the sample drawing has about 1.8 m). |
3. Domestic demand and storage
a. Give the demand as population × lpcd (135 lpcd residential, 200 hotels / hospitals, 45 offices — NBC 2016 Pt 9 Table 1) or directly as kL/day.
b. Storage days: 1 day for a municipal supply (NBC Pt 9 cl. 4.4); 2 days where tankers are the source.
c. Share in the UGT: 1.0 when the building is fed by hydro-pneumatic pumps and has no roof tank (as the sample); ⅔ when a roof tank holds the remaining ⅓.
d. Keep the treatment train ticked to get a raw-water tank ahead of the filters and a treated (domestic) tank after them; set the raw share (half and half is usual). Untick it for a single domestic tank fed directly.
e. A flushing tank (kL) adds a third domestic-side tank and a flushing pump set when the building has dual plumbing fed by the STP.
The sample drawing: 2 560 persons × 135 lpcd = 345.6 kL/day, all in the sump → raw 173 kL + domestic 173 kL.
4. Fire water — confirm the capacity
a. Enter the building height: the tool shows the NBC 2016 Part 4 Table 7 band (≤ 15, 15–24, 24–35, 35–45, 45–60, > 60 m) with its underground tank, terrace tank and pump duty.
b. Fire tank capacity: enter the value agreed with the fire authority (the tool checks it against the NBC minimum and flags a shortfall), or switch to "From NBC Table 7" and add any extra storage the authority or the sprinkler duration demands.
c. Maximum compartment size decides how many compartments the fire tank is split into (never fewer than two, so one can be emptied for cleaning). 200 kL gives the sample's 3 × 200 kL.
d. Tick Sprinkler for a second pump set and Water curtain for the drencher set; enter the pump head (from the Fire tool: static + friction + 3.5 bar at the top landing valve) and, if you do not want the NBC band value, the main pump duty.
Result: per system an electric main pump, a 100 % diesel standby and a jockey pump (IS 12469), an air vessel per system and a diesel day tank per diesel pump.
5. Tank construction
Water depth sets the plan area (volume ÷ depth) — 3.5 m is usual; deeper tanks save plot but need a heavier structure. Maximum depth is how far the tool may deepen the tanks on its own when the space is short. Free board, wall and slab thicknesses, the drain sump, the manhole size and the access cut-out are drawing and quantity inputs — the structural engineer designs the tank to IS 3370.
6. Space available — rectangle or polygon
a. Rectangle L × B when the plot is regular.
b. Polygon vertices for an irregular plot: type the corners as x,y pairs (metres, any order round the shape) or sketch them on the small grid — click each corner, drag to pan, wheel to zoom, "Clear sketch" to start again. The tool finds the largest rectangle that fits inside the polygon, trying each edge direction, and lays the tanks along it. The plan shows the plot in green and the structure inside it.
c. No constraint: give the preferred width and the tool reports the length needed.
d. Arrangement: pump room between the domestic and fire tanks (sample) or at one end; rows of domestic tanks across the width (2 = domestic above raw); rows of fire compartments (0 = one row per compartment, like the sample's three strips).
e. Deepen if short: when the strip does not fit, the tool deepens the tanks in 0.25 m steps up to the maximum, then tries the other axis; if it still does not fit the check turns red and tells you how many metres — and square metres — are missing. Stretch the pump room uses the whole plot length; otherwise the structure takes only what it needs (pump room up to 30 % longer than the equipment requires).
7. Treatment and plumbing pumps
Filter feed pumps = daily demand ÷ filtration run hours (8 h → the sample's 470–720 LPM), 1 working + 1 standby. MGF / ACF diameter from the filtration rate (10–20 m/h, CPHEEO). Hydro-pneumatic pumps = daily demand ÷ pumping hours × peak factor at the head you enter from the Water tool; "transfer to OHT" sizes the pumps to fill the roof tank in two hours instead. Ozonator (2 g/m³), chlorine dose (mg/L → kg/day), pressure-vessel diameter, diesel day tank and the drainage-sump submersible pumps complete the room.
8. Reading the results
| Block | What it tells you |
| Checks | Fire tank ≥ NBC minimum · ≥ 2 compartments · depth within the maximum · raw tank holds ≥ 4 h of filter flow · tanks + pump room fit the space (with the depth used, or the shortfall). |
| Storage | Daily demand, total and UG storage, raw / domestic / flushing / fire volumes, compartments. |
| Tanks (as laid out) | Each tank's length × width × depth and volume after placement — the last tank in a row is stretched to keep the wall straight, so volumes are ≥ the requirement. |
| Levels | Top slab, soffit, water level, floor, base, pump-room F.F.L. and drainage-sump invert, all relative to GL = 0 — the same numbers appear on the DXF sections and in the puddle-flange schedule. |
| Layout | Largest rectangle found, bank lengths, pump-room size, length required vs available. |
| Quantities | Footprint, RCC (walls, base, top) and excavation with 0.6 m working space — indicative, for early costing. |
| Worked steps | Every number with its arithmetic and clause, in order. |
9. Plan, 3D and schedules
Plan — the layout to scale: green dashed plot, tanks coloured (brown raw, blue domestic, purple flushing, red fire), pump room with equipment, pipes (red fire, blue domestic, brown raw; dashed = high level), puddle flanges as numbered circles, section lines X-X and Y-Y. Hover anything for its name.
3D — drag to orbit, right-drag / shift-drag to pan, wheel to zoom, click an object for its name. Tick / untick the groups (top slab, ground, structure, water, equipment, pipes) to look inside; the top slab is off by default.
Schedules — plumbing pumps, fire pumps, treatment & vessels, the puddle-flange sleeve schedule with bottom-of-pipe levels, ancillaries (drain sumps, manholes, cut-outs, ladders, drainage sump, drain channel, flow meter, pressure switches, stair).
10. Outputs: report, Excel, DXF
Save keeps the inputs under the project name; the address gets a code you can bookmark or send.
Report — printable (Print → Save as PDF, A4 landscape): inputs, storage and tanks, levels, NBC table, layout with the plan, pumps and equipment, puddle-flange schedule, ancillaries, quantities, checks, worked steps, notes, standards.
Excel — Sizing sheet with the inputs in yellow and every result as a live formula (change the population and the tanks, filters and pumps recalculate), plus Tanks (area and volume formulas), Pumps, Equipment, Puddle flanges, Levels, Quantities, Checks.
DXF (millimetres, AutoCAD 2018) — plan with walls, tanks, equipment, piping with sizes, puddle flanges, manholes, sumps, ladders; section X-X along the tanks and pump room and section Y-Y across the fire compartments with levels, water depth and free board; schedules of tanks, plumbing pumps, fire pumps and puddle flanges; valve legend and notes. Layers follow the sample: RSC-PL-UGT, RSC-PL-PUMP, RSC-FF-PUMP, RSC-FF-FIRE PIPE, RSC-PL-DWS, RSC-PL-RAWS, RSC-PL-SLEEVE, RSC-PL-TEXT, RSC-PL-DETAILS.
11. Frequently asked questions
The fire authority asked for a different capacity. Enter it under "Fire tank capacity"; the tool keeps the NBC value beside it for comparison and re-splits the compartments.
The tanks do not fit my plot. Read the fit check: it tells you the metres missing. Options: allow a deeper maximum depth, add rows (e.g. 3 domestic rows), move the pump room to the end, or give the tool a larger polygon. Deepening beyond 4.5–5 m should be agreed with the structural engineer.
My plot is a trapezium / L-shape. Use the polygon input; the largest inscribed rectangle is found automatically in the direction of the edges, so a skewed plot gives a skewed layout.
Can I move a pump or a tank myself? Not in the tool yet — edit the DXF; the piping is schematic so it will follow your changes easily. Tank order and rows are inputs.
Where do the pump heads come from? Enter them: the Water tool gives the domestic head, the Fire tool the fire pump head. A later release will read them across automatically.
Overhead tank and terrace fire tank? Reported for reference (⅓ of a day and the NBC terrace value); they belong to the roof, not this structure.