USER GUIDE

Transformer, DG & UPS sizing

Every feed of the load estimate classified essential / non-essential / UPS / fire → transformers (N or N+1 at the loading you set), DG sets derated for site altitude and ambient with the loading sequence — fire pump first, motors by starting kVA, transient dip per step — and the UPS with its battery bank; report and Excel.

IS 10002 · ISO 8528 · IS 1180 · IEEE 485

How to use it

  1. Pull the feeds from a load-estimation project (or type the loads); set each load's class — essential, non-essential, UPS, fire — and its starting method and motor kW.
  2. Set the basis: growth, diversity per class, transformer units and redundancy, DG sets with site altitude / ambient, allowed transient dip and single-step limit, UPS redundancy and backup time.
  3. Read the selected transformers, DG sets and UPS, the DG loading sequence with the dip at every step, and the checks.
  4. Export the report and the Excel.

Inputs

FieldType / defaultMeaning
Loadstag, panel, kind, class, demand kW, starting method, motor kW
Basisgrowth, diversity, N / N+1, loading limits, derating, dip, UPS battery

What you get

OutputContent
Transformerscount × kVA, loading, LV current, fault level
DGcount × kVA, derating, loading sequence with transient dip, fuel
UPSmodules × kVA, battery strings / blocks / Ah, input kVA, heat

Standards applied