| Source | Description | Rating | Impedance data | Connection |
|---|---|---|---|---|
| Utility | 11 kV point of supply | 250 MVA declared | — | grid |
| TR-1 | 11KV/0.433KV oil transformer, ONAN | 1600 kVA | %Z 6.25 · X/R 7 (library) | section 1 · bbt |
| TR-2 | 11KV/0.433KV oil transformer, ONAN | 1600 kVA | %Z 6.25 · X/R 7 (library) | section 2 · bbt |
| DG-1 | diesel genset via DG synchronising panel | 1000 kVA | xd″ 16 % · X/R 14 (library) | section 1 |
| DG-2 | diesel genset via DG synchronising panel | 1000 kVA | xd″ 16 % · X/R 14 (library) | section 2 |
| Solar PV | 500 kWp, 5 × 100 kW inverters | current source | k = 1.2 × I rated (IEC 60909-0:2016 6.5.4) | section 1 |
| Main LT panel | 2 incomer section(s), coupler normally open (sectionalised) |
Scenarios evaluated: grid, dg, grid+inv, dg+inv. The worst case at each bus governs the breaker rating and the cable withstand. Design loop converged in 1 iteration(s).
| Bus | kV | MVA | Ik″ kA | Basis |
|---|---|---|---|---|
| 11 kV point of supply | 11 | 250.0 | 13.12 | utility declared fault level |
| 11 kV HT panel bus | 11 | 250.0 | 13.12 | HT cable impedance neglected (conservative) |
| Feeder | kV | kVA | Ib A | Length m | Derating | Cable × runs | Iz A | S min (3-ph, t s) | Screen min / have | VD % | Governs | Check |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 11 kV incomer → HT panel | 11 | 3200 | 168.0 | 60.0 | 1.0 (soil 30 °C k1 1.0 · ρ 1.2 k2 1.0 · group 1 k3 1.0 · depth 0.9 m k4 1.0) | 3C X 150 Sq.mm, Al 11kV XLPE × 1 | 260 | 139.6 (1.0 s, 13.12 kA) | 7.0 / 25 | 0.044 | short-circuit | PASS |
| HT panel → TR-1 | 11 | 1600 | 84.0 | 60.0 | 1.0 (soil 30 °C k1 1.0 · ρ 1.2 k2 1.0 · group 1 k3 1.0 · depth 0.9 m k4 1.0) | 3C X 150 Sq.mm, Al 11kV XLPE × 1 | 260 | 139.6 (1.0 s, 13.12 kA) | 7.0 / 25 | 0.022 | short-circuit | PASS |
| HT panel → TR-2 | 11 | 1600 | 84.0 | 60.0 | 1.0 (soil 30 °C k1 1.0 · ρ 1.2 k2 1.0 · group 1 k3 1.0 · depth 0.9 m k4 1.0) | 3C X 150 Sq.mm, Al 11kV XLPE × 1 | 260 | 139.6 (1.0 s, 13.12 kA) | 7.0 / 25 | 0.022 | short-circuit | PASS |
HT cable checks: Iz (derated) ≥ Ib; S ≥ Ik″·√t / k with the HV protection clearing time (IEC 60364-4-43 / IEC 60949); screen ≥ Ief·√t / k; voltage drop ≤ limit. Typical IS 7098-2 / IEC 60502-2 data — confirm with the manufacturer's catalogue.
| Bus | Ik″ kA — grid | Ik″ kA — dg | Ik″ kA — grid+inv | Ik″ kA — dg+inv | Worst kA | Breaker Icu ≥ kA |
|---|---|---|---|---|---|---|
| AHU-1 | 1.20 | 1.08 | 1.20 | 1.08 | 1.20 | 6 |
| CHILLER-1 | 10.83 | 8.28 | 10.83 | 8.28 | 10.83 | 16 |
| HVAC PANEL | 15.07 | 11.12 | 15.90 | 11.95 | 15.90 | 16 |
| LIGHTING DB | 7.95 | 6.72 | 8.78 | 7.55 | 8.78 | 10 |
| MAIN LT PANEL source | 35.14 | 17.89 | 35.97 | 18.72 | 35.97 | 36 |
| PUMP-1 | 3.45 | 3.06 | 3.45 | 3.06 | 3.45 | 6 |
| SMDB-1 | 11.94 | 9.27 | 12.77 | 10.10 | 12.77 | 16 |
Each supply scenario is solved separately with the IEC 60909 impedance method (cmax = 1.05 for the maximum current): grid = transformers (with the upstream network) feeding the main LV panel sections as connected; dg = gensets only (cmin = 0.95 for the minimum-current check); +inv = with the PV / battery inverters contributing about 1.2 × their rated current (IEC 60909-0:2016 §6.5.4). Fault levels are cascaded bus to bus through the cable impedances at 20 °C. The breaker at every bus is chosen for the worst scenario, and the cable withstand of every feeder uses the fault level at its upstream bus. The design loop re-sizes cables with the new levels until no level changes by more than 2 %.
Scenario: grid — the worst case for the LV buses; every scenario's levels are in the LT fault-level table.
| Name | Bus | Type | kVA | %Z / Xd" | X/R | Upstream MVA | On |
|---|---|---|---|---|---|---|---|
| TR-1 | MAIN LT PANEL | transformer | 1600.0 | 6.25 | 7.0 | 250.0 | Yes |
| Bus | Z (mΩ) | X/R | Ik" 3φ (kA) | ip peak (kA) | Breaker Icu ≥ (kA) | Ik" DG-only (kA) |
|---|---|---|---|---|---|---|
| HVAC PANEL | 18.01 | 0.89 | 13.97 | 20.8 | 16.0 | |
| MAIN LT PANEL (source) | 7.45 | 7.21 | 33.77 | 79.6 | 36.0 | |
| SMDB-1 | 21.56 | 0.57 | 11.67 | 16.9 | 16.0 |
| # | From bus | To | Cable / bus duct | L m | R+jX seg (mΩ) | Z cum (mΩ) | X/R | Ik" From (kA) | Ik" To (kA) | ip (kA) | Breaker | Icu (kA) | S min / have (sqmm) | I²t | Ik" DG (kA) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | MAIN LT PANEL | SMDB-1 | 4C X 70 Sq.mm, AL × 1 | 40 | 17.72 + j3.28 | 21.56 | 0.57 | 33.77 | 11.67 | 16.9 | 100A MCCB | 36.0 | 62.2 / 70 | OK | |
| 2 | SMDB-1 | AHU-1 | 4C X 4 Sq.mm, Cu × 1 | 43 | 190.84 + j4.95 | 210.17 | 0.07 | 11.67 | 1.20 | 1.7 | 25A MCB | 16.0 | 2.8 / 4 I²t | OK | |
| 3 | SMDB-1 | PUMP-1 | 4C X 10 Sq.mm, Cu × 1 | 30 | 52.88 + j3.00 | 72.92 | 0.19 | 11.67 | 3.45 | 5.0 | 63A MCB | 16.0 | 3.5 / 10 I²t | OK | |
| 4 | MAIN LT PANEL | LIGHTING DB | 4C X 6 Sq.mm, Cu × 1 | 10 | 29.48 + j1.10 | 31.66 | 0.28 | 33.77 | 7.95 | 11.5 | 25A MCB | 36.0 | 4.8 / 6 I²t | OK | |
| 5 | MAIN LT PANEL | HVAC PANEL | 4C X 150 Sq.mm, AL × 1 | 60 | 12.40 + j4.62 | 18.01 | 0.89 | 33.77 | 13.97 | 20.8 | 250A MCCB | 36.0 | 62.2 / 150 | OK | |
| 6 | HVAC PANEL | CHILLER-1 | 4C X 150 Sq.mm, AL × 1 | 25 | 5.17 + j1.93 | 23.23 | 0.75 | 13.97 | 10.83 | 15.9 | 250A MCCB | 16.0 | 25.7 / 150 | OK |
| # | Feeder | Type | In (A) | Ir (A) | tr @6Ir (s) | Isd (A) | tsd (s) | Ii (A) | ti (s) | Ik" at bus (kA) |
|---|---|---|---|---|---|---|---|---|---|---|
| 1 | MAIN LT PANEL → SMDB-1 | MCCB | 100 | 100 | 10.00 | 800 | 0.10 | 1200 | 0.020 | 33.77 |
| 2 | SMDB-1 → AHU-1 | MCB | 25 | 25 | 3.00 | OFF | 0.00 | 250 | 0.010 | 11.67 |
| 3 | SMDB-1 → PUMP-1 | MCB | 63 | 63 | 3.00 | OFF | 0.00 | 630 | 0.010 | 11.67 |
| 4 | MAIN LT PANEL → LIGHTING DB | MCB | 25 | 25 | 3.00 | OFF | 0.00 | 250 | 0.010 | 33.77 |
| 5 | MAIN LT PANEL → HVAC PANEL | MCCB | 250 | 250 | 10.00 | 2000 | 0.10 | 3000 | 0.020 | 33.77 |
| 6 | HVAC PANEL → CHILLER-1 | MCCB | 250 | 250 | 10.00 | 2000 | 0.10 | 3000 | 0.020 | 13.97 |
| Type | Ir ×In | tr s | Isd ×Ir | tsd s | Ii ×In | ti s |
|---|---|---|---|---|---|---|
| MCB | 1.0 | 3 | 0 | 0 | 10 | 0.01 |
| MCCB | 1.0 | 10 | 8 | 0.1 | 12 | 0.02 |
| ACB | 1.0 | 10 | 6 | 0.3 | 0 | 0.02 |
| Bus | Upstream | Downstream | Ik" (kA) | Status | Limit (kA) | Remark |
|---|---|---|---|---|---|---|
| SMDB-1 | 100A MCCB MAIN LT PANEL → SMDB-1 | 25A MCB SMDB-1 → AHU-1 | 11.67 | PARTIAL | 1.07 | limited by upstream instantaneous — raise Ii, switch it OFF (ACB) or use manufacturer selectivity table / zone selectivity |
| SMDB-1 | 100A MCCB MAIN LT PANEL → SMDB-1 | 63A MCB SMDB-1 → PUMP-1 | 11.67 | PARTIAL | 1.04 | limited by upstream instantaneous — raise Ii, switch it OFF (ACB) or use manufacturer selectivity table / zone selectivity |
| HVAC PANEL | 250A MCCB MAIN LT PANEL → HVAC PANEL | 250A MCCB HVAC PANEL → CHILLER-1 | 13.97 | NONE | — | upstream can trip first even at low fault currents |
limited by upstream instantaneous — raise Ii, switch it OFF (ACB) or use manufacturer selectivity table / zone selectivity
limited by upstream instantaneous — raise Ii, switch it OFF (ACB) or use manufacturer selectivity table / zone selectivity
upstream can trip first even at low fault currents
Design regime: Indian — code edition NBCS 2026 (SP 7:2026) Part D Sec 2 (replaces NBC 2016 Part 8 Sec 2): VD basis — Split — ≤ 6 % transformer → final DB plus ≤ 3 % final DB → last point (9 % at the last point) (NBCS 2026 (SP 7:2026) Part D Sec 2 cl. 6.2 / 5.6 Note a): voltage drop ≤ 6 % transformer → final DB and ≤ 3 % DB → last point (cl. 6.2, 5.6 Note a), four-core cables only and Cu up to 25 sq mm (cl. 5.3.7.1), full-size neutral (cl. 8.2.9.1), F&LS supplies (cl. 4.2.1 jj); IS 732:2019 (harmonised with IEC 60364), IS 1554 / IS 7098 cables, CPWD General Specifications cascade limits (stricter than NBCS), with the IEC standards they adopt.
| Panel | Connected kW | DF | Demand kW | Ib A | Incomer breaker | Incoming cable |
|---|---|---|---|---|---|---|
| SMDB-1 | 49.0 | 1.00 | 49.0 | 71.8 | 100A MCCB | 4C X 70 Sq.mm, AL × 1 |
| HVAC PANEL | 150.0 | 1.00 | 150.0 | 219.7 | 250A MCCB | 4C X 150 Sq.mm, AL × 1 |
| # | From | To | Ph | Load kW | L m | Laying | Cable / bus duct | Runs | Ib A | Breaker | k (derating) | Iz2 A | VD % | Cum. % | Limit % | Status |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | MAIN LT PANEL | SMDB-1 (panel) | 3φ | 49.0 Σ49.0×1.00 | 40 | In air – perforated tray / ladder / clipped direct | 4C X 70 Sq.mm, AL | 1 | 71.8 | 100A MCCB 4P | 1.00 θ 1.00 · ρ 1.00 · d 1.00 · grp 1.00 (1) · lay 1.00 | 175 | 0.68 | 0.68 | 4.0 | PASS |
| 2 | SMDB-1 | AHU-1 | 3φ | 12.0 | 43 | In air – perforated tray / ladder / clipped direct | 4C X 4 Sq.mm, Cu | 1 | 17.6 | 25A MCB FP | 1.00 θ 1.00 · ρ 1.00 · d 1.00 · grp 1.00 (1) · lay 1.00 | 45 | 1.72 | 2.39 | 5.0 | PASS |
| 3 | SMDB-1 | PUMP-1 | 3φ | 37.0 | 30 | In air – perforated tray / ladder / clipped direct | 4C X 10 Sq.mm, Cu | 1 | 54.2 | 63A MCB FP | 1.00 θ 1.00 · ρ 1.00 · d 1.00 · grp 1.00 (1) · lay 1.00 | 74 | 1.48 | 2.15 | 5.0 | PASS |
| 4 | MAIN LT PANEL | LIGHTING DB | 3φ | 2.0 | 10 | In air – perforated tray / ladder / clipped direct | 4C X 6 Sq.mm, Cu | 1 | 2.9 | 25A MCB FP | 1.00 θ 1.00 · ρ 1.00 · d 1.00 · grp 1.00 (1) · lay 1.00 | 56 | 0.04 | 0.04 | 4.0 | PASS |
| 5 | MAIN LT PANEL | HVAC PANEL (panel) | 3φ | 150.0 Σ150.0×1.00 | 60 | In air – perforated tray / ladder / clipped direct | 4C X 150 Sq.mm, AL | 1 | 219.7 | 250A MCCB 4P | 1.00 θ 1.00 · ρ 1.00 · d 1.00 · grp 1.00 (1) · lay 1.00 | 284 | 1.52 | 1.52 | 4.0 | PASS |
| 6 | HVAC PANEL | CHILLER-1 | 3φ | 150.0 | 25 | In air – perforated tray / ladder / clipped direct | 4C X 150 Sq.mm, AL | 1 | 219.7 | 250A MCCB 4P | 1.00 θ 1.00 · ρ 1.00 · d 1.00 · grp 1.00 (1) · lay 1.00 | 284 | 0.63 | 2.15 | 5.0 | PASS |
| Node | Fed from | Cable × runs | L m | Segment VD % | Cumulative VD % | Limit % | Check |
|---|---|---|---|---|---|---|---|
| MAIN LT PANEL source · connected 201.0 kW · demand 201.0 kW (DF 1.00) | 0.00 | 4.0 | |||||
| └ SMDB-1 (panel) | MAIN LT PANEL | 4C X 70 Sq.mm, AL × 1 | 40 | 0.68 | 0.68 | 4.0 | PASS |
| └ AHU-1 | SMDB-1 | 4C X 4 Sq.mm, Cu × 1 | 43 | 1.72 | 2.39 | 5.0 | PASS |
| └ PUMP-1 | SMDB-1 | 4C X 10 Sq.mm, Cu × 1 | 30 | 1.48 | 2.15 | 5.0 | PASS |
| └ LIGHTING DB | MAIN LT PANEL | 4C X 6 Sq.mm, Cu × 1 | 10 | 0.04 | 0.04 | 4.0 | PASS |
| └ HVAC PANEL (panel) | MAIN LT PANEL | 4C X 150 Sq.mm, AL × 1 | 60 | 1.52 | 1.52 | 4.0 | PASS |
| └ CHILLER-1 | HVAC PANEL | 4C X 150 Sq.mm, AL × 1 | 25 | 0.63 | 2.15 | 5.0 | PASS |
Single-phase loads are placed on their tagged phase or on the least-loaded phase of their panel; three-phase loads are split equally unless a split is entered. Design current Ib = worst-phase current (IEC 60364-5-52 cl. 523.6.3); neutral current IN = |IR + a·IY + a²·IB| adds to the worst-phase voltage drop. Unbalance = (Imax − Iavg)/Iavg; limit 10 % (design practice / IEEE 141 / CEA).
| Panel | kW R | kW Y | kW B | I R A | I Y A | I B A | I N A | Unbalance % | Limit % | Check |
|---|---|---|---|---|---|---|---|---|---|---|
| MAIN LT PANEL (source) | 67.0 | 67.0 | 67.0 | 294.4 | 294.4 | 294.4 | 0.0 | 0 | 10 | PASS |
| SMDB-1 | 16.3 | 16.3 | 16.3 | 71.8 | 71.8 | 71.8 | 0.0 | 0 | 10 | PASS |
| HVAC PANEL | 50.0 | 50.0 | 50.0 | 219.7 | 219.7 | 219.7 | 0.0 | 0 | 10 | PASS |
3rd-harmonic content of the line current ≤ 15 %: no reduction; 15–33 %: factor 0.86 on the line current; 33–45 %: factor 0.86 applied to the neutral current IN = 3·h3·IL; > 45 %: cable sized for the neutral current. Project default h3 = 0 %.
No feeder with 3rd-harmonic content above 0 % — no harmonic derating applied.
Istart = m · Ib (DOL 6 ×, star-delta 2.5 ×, soft starter 3 ×, VFD 1.5 ×) at pf 0.3; dip at the motor terminals = upstream running VD + starting VD of the motor feeder ≤ 15 % (IEEE 141 / IS 732 guidance; upstream feeders assumed at running load).
| From | To | Starter | Ib A | Multiple | I start A | pf start | Cable | Start VD % | Upstream VD % | Dip at terminals % | Limit % | Check |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| SMDB-1 | PUMP-1 | DOL | 54.2 | 6.0 × | 325 | 0.30 | 4C X 10 Sq.mm, Cu × 1 | 3.15 | 0.68 | 3.83 | 15 | PASS |
| HVAC PANEL | CHILLER-1 | Star-delta | 219.7 | 2.5 × | 549 | 0.30 | 4C X 150 Sq.mm, AL × 1 | 0.88 | 1.52 | 2.39 | 15 | PASS |
Ib ≤ In ≤ Iz and I2 ≤ 1.45·Iz, where I2 = 1.45·In for MCB (IS/IEC 60898-1), 1.30·In for MCCB / ACB (IEC 60947-2) and 1.60·In for gG fuses (IS 13703 / IEC 60269). With the rule on, the cable is sized so that Iz2 ≥ In (the second condition is then automatically satisfied for breakers).
| From | To | Ib A | In A · type | Iz2 A | I2 A | 1.45·Iz A | Ib ≤ In ≤ Iz | I2 ≤ 1.45 Iz |
|---|---|---|---|---|---|---|---|---|
| MAIN LT PANEL | SMDB-1 | 71.8 | 100 MCCB | 175.0 | 1.30 × In = 130.0 | 253.8 | PASS | PASS |
| SMDB-1 | AHU-1 | 17.6 | 25 MCB | 45.0 | 1.45 × In = 36.2 | 65.2 | PASS | PASS |
| SMDB-1 | PUMP-1 | 54.2 | 63 MCB | 74.0 | 1.45 × In = 91.3 | 107.3 | PASS | PASS |
| MAIN LT PANEL | LIGHTING DB | 2.9 | 25 MCB | 56.0 | 1.45 × In = 36.2 | 81.2 | PASS | PASS |
| MAIN LT PANEL | HVAC PANEL | 219.7 | 250 MCCB | 284.0 | 1.30 × In = 325.0 | 411.8 | PASS | PASS |
| HVAC PANEL | CHILLER-1 | 219.7 | 250 MCCB | 284.0 | 1.30 × In = 325.0 | 411.8 | PASS | PASS |
S ≥ Ik·√t / k with k = 143 (Cu XLPE), 115 (Cu PVC), 94 (Al XLPE), 76 (Al PVC) — Table 43A; Ik = three-phase fault level at the upstream bus, cascaded from the source (36 kA at each source panel unless set per panel) through cable impedances Ik = Uph/|Z| (screening, c = 1; see the Short-circuit tool for the IEC 60909 study); t = clearing time of the feeder's own breaker (MCB 0.01 s, MCCB 0.03 s, ACB 0.4 s). Parallel runs share the fault current (S = size × runs).
Fault levels at 7 bus(es) are taken from the linked Short-circuit study (IEC 60909 Ik″): AHU-1, CHILLER-1, HVAC PANEL, LIGHTING DB, MAIN LT PANEL, PUMP-1, SMDB-1. Other buses are cascaded from these.
| From (bus) | To | Ik at bus kA | Ik at To kA | Breaker | t s / let-through I²t | k | S min sqmm | Cable × runs | S sqmm | Check | Ik source |
|---|---|---|---|---|---|---|---|---|---|---|---|
| MAIN LT PANEL | SMDB-1 | 35.97 | 9.66 | 100 MCCB | 0.030 s | 94 | 66.3 | 4C X 70 Sq.mm, AL × 1 | 70 | PASS | SC study |
| SMDB-1 | AHU-1 | 12.77 | 0.97 | 25 MCB | I²t 178,780 A²s | 143 | 3.0 | 4C X 4 Sq.mm, Cu × 1 | 4 | PASS | SC study |
| SMDB-1 | PUMP-1 | 12.77 | 3.36 | 63 MCB | I²t 280,940 A²s | 143 | 3.7 | 4C X 10 Sq.mm, Cu × 1 | 10 | PASS | SC study |
| MAIN LT PANEL | LIGHTING DB | 35.97 | 6.21 | 25 MCB | I²t 503,580 A²s | 143 | 5.0 | 4C X 6 Sq.mm, Cu × 1 | 6 | PASS | SC study |
| MAIN LT PANEL | HVAC PANEL | 35.97 | 12.29 | 250 MCCB | 0.030 s | 94 | 66.3 | 4C X 150 Sq.mm, AL × 1 | 150 | PASS | SC study |
| HVAC PANEL | CHILLER-1 | 15.90 | 13.14 | 250 MCCB | 0.030 s | 94 | 29.3 | 4C X 150 Sq.mm, AL × 1 | 150 | PASS | SC study |
MCB-protected feeders (In ≤ 63 A): k²S² ≥ let-through I²t of an energy-limiting class 3 MCB at the prospective current (IEC 60898-1 Annex ZC, type C values; IEC 60364-4-43 cl. 434.5.2). Other feeders: adiabatic S ≥ Ik·√t / k with the device clearing time.
Four-core cables (cl. 5.3.7.1): only four-core cables are used for internal installations (four-core in place of 3½-core below 50 sq mm) and all sizes up to 25 sq mm are copper — auto-sizing picks 4C Cu up to 35 sq mm, then 4C Al. No 3½-core cable in this schedule.
Neutral (cl. 8.2.9.1 Note): neutral of the same size as the phase conductor (half-size neutral no longer acceptable with non-linear loads); the neutral-current term in the voltage drop uses zN = z for 4C cables.
Voltage drop (cl. 6.2, 5.6 Note a): ≤ 6 % from the transformer to the final distribution board and ≤ 3 % from the distribution board to the last point — read either as split (6 % + 3 %) or as total (6 % to the last point incl. ≤ 3 % final circuit); the project chooses (Settings ▸ VD basis).
Voltage-drop basis: Split — ≤ 6 % transformer → final DB plus ≤ 3 % final DB → last point (9 % at the last point) — NBCS 2026 (SP 7:2026) Part D Sec 2 cl. 6.2 / 5.6 Note a. This project: first hop ≤ 4.0 %, total ≤ 5.0 %, final circuits ≤ 3.0 % on the segment; final-circuit rows add their segment limit on top of the DB's own cumulative drop. (stricter than NBCS — CPWD practice)
No row is marked as a final circuit (Load details ▸ Final circuit) — the 3 % DB → last-point check applies to final-circuit rows.
Fire & life-safety supplies (cl. 4.2.1 jj): fire pumps, pressurisation / smoke venting, fireman's and all lifts, exit and emergency lighting, fire alarm, PA, door hold-open devices and fire-control-room lighting are fed from the normal and the standby-generator supply with changeover; the generator takes the starting current of all F&LS loads; the F&LS panel / DB is in a fire-safe zone; cables are fire-survival (circuit integrity) as far as possible. F&LS rows are auto-sized in the fire-survival (FS) cable family.
No feeder is marked F&LS (Load details ▸ F&LS feeder).
Worked from this schedule’s own inputs and results — the values can be traced to the cable schedule (section 3) and the cascade (section 4).
| From | To | Load kW | Ib A | Breaker | Icu kA | Cable × runs | Iz A | VD % | Cum VD % | Ik″ at bus kA | S min / S | Governs | Checks |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| MAIN LT PANEL | SMDB-1 | 49.0 | 71.76 | 100 MCCB | 36 | 4C X 70 Sq.mm, AL × 1 | 175.0 | 0.677 | 0.677 | 35.97 | 66.3 / 70.0 | short circuit | PASS |
| SMDB-1 | AHU-1 | 12.0 | 17.57 | 25 MCB | 16 | 4C X 4 Sq.mm, Cu × 1 | 45.0 | 1.716 | 2.393 | 12.77 | 3.0 / 4.0 | minimum size | PASS |
| SMDB-1 | PUMP-1 | 37.0 | 54.18 | 63 MCB | 16 | 4C X 10 Sq.mm, Cu × 1 | 74.0 | 1.478 | 2.155 | 12.77 | 3.7 / 10.0 | ampacity | PASS |
| MAIN LT PANEL | LIGHTING DB | 2.0 | 2.93 | 25 MCB | 36 | 4C X 6 Sq.mm, Cu × 1 | 56.0 | 0.044 | 0.044 | 35.97 | 5.0 / 6.0 | short circuit | PASS |
| MAIN LT PANEL | HVAC PANEL | 150.0 | 219.66 | 250 MCCB | 36 | 4C X 150 Sq.mm, AL × 1 | 284.0 | 1.517 | 1.517 | 35.97 | 66.3 / 150.0 | ampacity | PASS |
| HVAC PANEL | CHILLER-1 | 150.0 | 219.66 | 250 MCCB | 16 | 4C X 150 Sq.mm, AL × 1 | 284.0 | 0.632 | 2.149 | 15.9 | 29.3 / 150.0 | ampacity | PASS |
Governing constraint = the check that fails on the next smaller cable of the same family. Short-circuit rule: MCB feeders by the let-through I²t of a class-3 MCB (IEC 60898-1), other devices adiabatic Ik″·√t / k; mode: autofix. Conductor policy: Cu up to 35 sq mm, Cu for fire / life-safety feeders; four-core cables only and Cu up to 25 sq mm (NBCS 2026 Part D Sec 2 cl. 5.3.7.1), full-size neutral (cl. 8.2.9.1); F&LS feeders on fire-survival cable from normal + standby DG supply with changeover (cl. 4.2.1 jj).
| Cable | Length m | Runs | Feeders | Terminations |
|---|---|---|---|---|
| 4C X 150 Sq.mm, AL | 85 | 2 | 2 | 4 |
| 4C X 4 Sq.mm, Cu | 43 | 1 | 1 | 2 |
| 4C X 70 Sq.mm, AL | 40 | 1 | 1 | 2 |
| 4C X 10 Sq.mm, Cu | 30 | 1 | 1 | 2 |
| 4C X 6 Sq.mm, Cu | 10 | 1 | 1 | 2 |
Worked from this project’s own inputs and results — each value can be traced to the schedules above.
| Setting | Value |
|---|---|
| voltage | 415 |
| pf | 0.95 |
| k1_temp | 0.95 |
| k2_group | 0.86 |
| k3_tray | 0.92 |
| max_size | 300 |
| max_runs | 8 |
| cu_upto_size | 35 |
| default_cores_small | 4 |
| default_cores_large | 4 |
| limit_first_hop | 4.0 |
| limit_total | 5.0 |
| bbt_vd | 2.0 |
| seg_limit_align | True |
| min_breaker | 25 |
| termination_per_run | 2 |
| size_for_breaker | False |
| parent_share | 0.6 |
| default_material | auto |
| default_df | 1.0 |
| mcb_max | 63 |
| mccb_max | 630 |
| derating_mode | tables |
| overload_rule | True |
| unbalance_limit | 10 |
| thd3 | 0 |
| motor_start_pf | 0.3 |
| motor_start_limit | 15 |
| sc_check | True |
| sc_source_ka | 36 |
| regime | indian |
| limit_final | 3.0 |
| code_edition | nbcs2026 |
| vd_basis | split |
| cu_lifesafety | True |
| derating.insulation | XLPE |
| derating.air_temp | 40 |
| derating.ground_temp | 30 |
| derating.soil_rho | 1.5 |
| derating.depth | 0.9 |
| derating.n_circuits | 1 |
| derating.spacing | touching |
| derating.trays | 1 |
| Setting | Value |
|---|---|
| voltage | 415.0 |
| c_max | 1.05 |
| c_min | 0.95 |
| r_temp_factor | 0.78 |
| bd_temp_factor | 1.0 |
| k_cu_pvc | 115 |
| k_cu_xlpe | 143 |
| k_al_pvc | 76 |
| k_al_xlpe | 94 |
| t_mcb | 0.01 |
| t_mccb | 0.03 |
| t_acb | 0.4 |
| util_xr | 10 |
| dg_xd_pct | 16 |
| dg_xr | 6.7 |
| mcb_rule | class3 |
| ka_steps | 6, 10, 16, 25, 36, 50, 65, 80, 100, 120, 150 |
| Quantity | Formula | Reference / clause | Notes |
|---|---|---|---|
| Design current (3φ) | Ib = P / (√3 · U · cosφ) | IEC 60364-5-52:2009 cl. 523 / IS 732:2019 Sec. 5.2 | P in kW × 1000, U = 415 V line voltage; 1φ: Ib = P / (U_ph · cosφ) |
| Current-carrying capacity (derated) | Iz2 = n · Ir · k_θ · k_ρ · k_d · k_grp · k_lay (manual mode: n · Ir · k1 · k2 · k3 · k_lay) | IEC 60364-5-52:2009 cl. 523.1; Table A.52.3 (reference methods B, C, E, F, D1, D2); B.52.14 (air temperature), B.52.15 (ground temperature), B.52.16 (soil thermal resistivity), B.52.17 / B.52.20 / B.52.21 (grouping in air), B.52.18 (direct buried), B.52.19 (in ducts); IS 3961 Pt 2 (rating factors, depth); IEC 60287-2-1 (k_θ = √((θmax−θamb)/(θmax−θref)), depth); IS 1554 Pt 1 / IS 7098 Pt 1 base ratings | Base ratings at 40 °C air / 30 °C ground / 1.5 K·m/W / 0.9 m / single circuit; parallel runs counted as circuits in k_grp; grouping rows for n above the table use the next larger row (conservative); Ib ≤ In ≤ Iz (IEC 60364-4-43 cl. 433.1) |
| Voltage drop (3φ, impedance method) | ΔU = √3 · Ib · L · (R·cosφ + X·sinφ) / (1000 · n) | IEC 60364-5-52:2009 Annex G (G.1); IS 732:2019 Annex on voltage drop; conductor R, X per IS 1554 / IS 7098 / IS 8130 | R, X in Ω/km at operating temperature; 1φ: ΔU = 2 · Ib · L · (R·cosφ + X·sinφ)/1000 |
| Voltage drop, percent | ΔU% = ΔU / Un × 100 | NBCS 2026 (SP 7:2026) Part D Sec 2 cl. 6.2 / 5.6 Note a — Split — ≤ 6 % transformer → final DB plus ≤ 3 % final DB → last point (9 % at the last point); IEC 60364-5-52:2009 Annex G Table G.52.1 (≤ 3 % lighting, ≤ 5 % other, from origin); CPWD General Specifications Pt I (2013) cl. on voltage drop | Cascade: first hop from source panel ≤ limit_first_hop, cumulative to last point ≤ limit_total |
| Bus-duct voltage drop | ΔU = √3 · Ib · L · (R·cosφ + X·sinφ) / 1000 | IEC 61439-6:2012 (busbar trunking systems) Annex — voltage drop from manufacturer R, X per metre | Checked against the bus-duct VD allowance (default 2 %) |
| Panel demand (diversity) | DL(N) = Σ connected × DF ; DL(F) = Σ fire/essential loads × 1.0 | NBCS 2026 Part D Sec 2 cl. 4.2.2.2 (diversity) and 4.2.1 (jj) (fire & life-safety supplies); CPWD GS Pt I | DF per panel, default 1.0; cable sized for the diversified demand |
| Breaker rating | In = next standard switchgear rating ≥ max(Ib, I_min) ; standard steps 25, 32, 40, 63, 100, 125, 160, 200, 250, 315, 400, 630, 800, 1000, 1250, 1600, 2000, 2500, 3200, 4000, 5000, 6300 A ; I_min = 25 A default (user-settable) ; MCB ≤ 63 A, MCCB ≤ 630 A, ACB above (configurable) | IEC 60364-4-43:2008 cl. 433.1 (Ib ≤ In ≤ Iz, I2 ≤ 1.45 Iz); IEC 60898-1 (MCB); IEC 60947-2 (MCCB/ACB) | |
| Design current with unbalance | I_b = max(I_R, I_Y, I_B) ; I_N = |I_R + a·I_Y + a²·I_B| ; unbalance = (I_max − I_avg)/I_avg | IEC 60364-5-52:2009 cl. 523.6.3 (neutral carrying current); IEEE 141 / CEA practice ≤ 10 % | 1φ loads on tagged or least-loaded phase; worst-phase VD = L·(I_max·z + I_N·z_N)/(1000·n)/U_ph, z_N = 2z for reduced neutral (3.5-core) |
| Harmonic reduction factor | h3 ≤ 15 %: 1.0 on I_L ; 15–33 %: 0.86 on I_L ; 33–45 %: 0.86 on I_N = 3·h3·I_L ; > 45 %: 1.0 on I_N | IEC 60364-5-52:2009 Annex E, Table E.52.1 | Applied to 4-core / 3.5-core three-phase circuits with neutral |
| Motor starting voltage dip | I_start = m·I_b (DOL 6, Y-Δ 2.5, soft 3, VFD 1.5) ; ΔU_start % = upstream running VD + segment VD at I_start, pf_start 0.3 ≤ 15 % | IEEE 141-1993 cl. 3.11 (starting voltage ≥ 80–85 %); IS 732:2019 cl. 525 note; IEC 60364-5-52 Annex G | Upstream circuits taken at running load (screening) |
| Overload protection rule | I_b ≤ I_n ≤ I_z ; I_2 ≤ 1.45·I_z (I_2 = 1.45 I_n MCB, 1.30 I_n MCCB/ACB, 1.60 I_n gG fuse) | IS 732:2019 cl. 433.1 = IEC 60364-4-43:2008 cl. 433.1; IS/IEC 60898-1 cl. 8.6.2; IEC 60947-2 cl. 7.2.1.2.4; IS 13703 / IEC 60269-1 | Rule on → cable sized for I_n |
| Cable short-circuit withstand (in VD) | S_min = I_k·√t / k ; I_k(bus) = U_ph / |Z_source + Σ(R + jX)·L/(1000·n)| | IS 732:2019 / IEC 60364-4-43:2008 cl. 434.5.2, Table 43A (k); IEC 60909-0 (c = 1 screening) | t = clearing time of the feeder breaker (MCB 0.01 s, MCCB 0.03 s, ACB 0.4 s); parallel runs share the fault current |
| Quantity | Formula | Reference / clause | Notes |
|---|---|---|---|
| Transformer impedance (referred to LV) | Z_T = (u_kr / 100) · U_n² / S_rT ; R_T, X_T from X/R | IEC 60909-0:2016 cl. 6.3.2 eq. (7)-(9); u_kr per IS 1180 Pt 1:2014 Table / IS 2026 Pt 1 | Typical u_kr: 4.5 % ≤ 630 kVA, 5 % ≤ 1250 kVA, 6.25 % ≤ 2500 kVA (editable) |
| Network feeder (utility) impedance | Z_Q = c · U_nQ² / S"_kQ (referred to LV by 1/t_r²) | IEC 60909-0:2016 cl. 6.2.1 eq. (4)-(5); X_Q/R_Q ≈ 10 (cl. 6.2.1 note) | Blank MVA = infinite bus |
| Generator (DG) impedance | Z_G = (x"_d / 100) · U_rG² / S_rG | IEC 60909-0:2016 cl. 6.6.1 eq. (18); x"_d from generator data (default 16 %) | DG-only case uses c_min for the minimum fault level (cl. 5.3.1) |
| Cable impedance | Z_L = (R_20 + jX) · L / (1000 · n) ; R_20 = R_θ / (1 + α(θ − 20)) | IEC 60909-0:2016 cl. 6.7 (line impedances at 20 °C for maximum current); α per IS 8130:2013 | Catalogue R at 90 °C × 0.78 ≈ R at 20 °C |
| Initial symmetrical short-circuit current | I"_k = c · U_n / (√3 · |Z_k|) | IEC 60909-0:2016 cl. 7.1.1 eq. (29); voltage factor c Table 1 (c_max 1.05 / 1.10, c_min 0.95 for LV) | |
| Peak short-circuit current | i_p = κ · √2 · I"_k ; κ = 1.02 + 0.98 · e^(−3R/X) | IEC 60909-0:2016 cl. 8.1.1 eq. (55)-(56) | Used for busbar dynamic withstand (IEC 61439-1 cl. 10.11.5) |
| Breaker breaking capacity | I_cu ≥ I"_k at the bus where the breaker is installed → next standard kA step | IEC 60947-2:2016 cl. 4.3.5.2 (I_cu), 4.3.5.3 (I_cs), 4.3.5.4 (I_cw); IS/IEC 61439-1 cl. 10.11 (I_cw of assembly) | Steps 6/10/16/25/36/50/65/80/100 kA (editable) |
| Cable short-circuit withstand (adiabatic) | I² · t ≤ k² · S² → S_min = I"_k · √t / k | IEC 60364-4-43:2008 cl. 434.5.2, Table 43A (k: Cu PVC 115, Cu XLPE 143, Al PVC 76, Al XLPE 94) | t = clearing time of the upstream breaker (MCB 0.01 s, MCCB 0.03 s, ACB with STD 0.4 s, editable) |
| Long-time (thermal) trip | t = t_r · 35 / ((I/I_r)² − 1) (I²t inverse, asymptotic at I_r) | IEC 60947-2:2016 Annex F / cl. 7.2.1.2.4 (L-release, ±10 % current tolerance); IEC 60898-1:2015 Table 6 (1.13 I_n no trip 1 h, 1.45 I_n trip < 1 h) | t_r = trip time at 6 × I_r |
| Short-time trip | t = t_sd for I ≥ I_sd (definite time) | IEC 60947-2:2016 cl. 7.2.1.2.4 (S-release), tolerance ±10 % current / ±20 % time | |
| Instantaneous trip | t = t_i for I ≥ I_i ; MCB C-curve 5–10 × I_n | IEC 60898-1:2015 Table 7 (B 3–5, C 5–10, D 10–20 × I_n); IEC 60947-2 cl. 7.2.1.2.4 (I-release) | |
| Discrimination (selectivity) criterion | t_max,downstream(I) < t_min,upstream(I) for all I ≤ I"_k at the downstream bus ; limit = highest I satisfying it | IEC 60947-2:2016 Annex A (selectivity, A.4 total / partial); IEC 60364-5-53:2019 cl. 535 (coordination); IS 10118 Pt 3 | Energy-based selectivity in the instantaneous zone requires manufacturer tables (IEC 60947-2 Annex A.5) |
| Device numbers | 50/51 OC, 50N/51N EF, 64 REF, 86 lockout, 95 trip-circuit supervision, 25 sync-check, 27/59 U/V–O/V, 32 reverse power | IEEE C37.2-2008 Table 1 |
Results are design aids computed by designlink calc (calc.designlink.in) and must be reviewed by a qualified engineer before issue. Ground levels marked "assumed" have no survey level within reach — verify.