SAMPLEPower factor correction (APFC) — this is what your report looks like, generated from demo inputs.Generate yours →2 free designs every day for every signed-in account · 1 design free on sign-in · ₹99 + GST per design (report + Excel + DXF) · free for DesignLink companies
Report ready — use Print → Save as PDF (A4).
calc.designlink.in
Power factor correction — design calculation
APFC panel — Sample project — Tower A · project: Sample project — Tower A
Generated 28 Nov 2026 16:09 NBCS 2026 (SP 7:2026) Part D Sec 2 · IS 13340 / IEC 60831 · IEC 61921 · IEEE 519-2022
1. Inputs
Input
Value
Compensation scheme
Capacitor bank (APFC) only
Load P
400.0 kW
Existing pf (cos φ₁)
0.78
Target pf (cos φ₂)
0.99
Transformer rating
630 kVA
System voltage
415 V, 3φ, 50 Hz
Harmonic distortion THD-I (network)
8 %
Detuned reactor
auto by THD
Step pattern
1:1:2:2
Transformer no-load compensation
yes (5 % of kVA)
2. Calculation
Quantity
Result
Basis
tan φ₁ − tan φ₂
0.660
Q = P·(tan φ₁ − tan φ₂)
Reactive power required Q
263.9 kVAR
Transformer no-load compensation
31.5 kVAR
5 % × S_rT
Total
295.4 kVAR
Selected bank (standard)
300 kVAR
7 steps: 25, 25, 50, 50, 50, 50, 50
Detuned reactor
7 % (f_res = 189 Hz)
by THD-I
Capacitor rated voltage / kVAR
480 V / 432 kVAR
Q_c = Q/(1−p)·(U_r/U_n)²
Bank current I_n
417.4 A
Q/(√3·U)
APFC incomer breaker
630 A 4P ACB
≥ 1.5 × I_n
Feeder cable
2R x 4C x 150 sqmm Cu / 2R x 4C x 240 sqmm Al
≥ 1.43 × I_n
kVA before / after
512.8 / 404.0 kVA
released 108.8 kVA
Line current before / after
713.4 / 562.1 A
I²R loss reduction ≈ 37.9 %
Transformer loading before / after
81.4 % / 64.1 %
3. APFC steps and switching
Step
kVAR
I (A)
MCB / MCCB
Contactor
Cable (Cu sqmm)
1
25
34.8
63 A
capacitor-duty ≥ 63A
10
2
25
34.8
63 A
capacitor-duty ≥ 63A
10
3
50
69.6
125 A
capacitor-duty ≥ 125A
25
4
50
69.6
125 A
capacitor-duty ≥ 125A
25
5
50
69.6
125 A
capacitor-duty ≥ 125A
25
6
50
69.6
125 A
capacitor-duty ≥ 125A
25
7
50
69.6
125 A
capacitor-duty ≥ 125A
25
4. Graphs
Triangle drawn to scale from P, cos φ₁ and cos φ₂; the ladder shows each capacitor step and the bank built up in the APFC relay's switching order.
5. Code basis — NBCS 2026 (SP 7:2026) Part D Sec 2
Clause (NBCS 2026 Part D Sec 2)
Requirement
This design
Result
3.8.1 power factor improvement
supply pf ≥ 0.95 lag (lower limit of the supply conditions)
target cos φ₂ = 0.99 (existing 0.78)
PASS
5.3.6.6 harmonics
non-linear loads: plan detuned banks / active filters; filter + capacitor panel in a controlled environment
7 % detuned reactor, fr 189 Hz
note
8.2.9.1 note — neutral
full-size neutral where harmonics are present
feeder cables 4-core (NBCS 5.3.7.1); an AHF on 3P4W compensates the neutral (triplen) — size its neutral as the phase
note
6. Worked example — from this project
Worked from this calculation’s own inputs — each value matches the tables above.
400 kW load, cos φ 0.78 → 0.99
the inputs of this calculation
Given: System 415 V 3φ 50 Hz · THD-I 8 % · Transformer 630 kVA
1. tan φ₁ − tan φ₂: tan(arccos cos φ1) − tan(arccos cos φ2) = 0.802 − 0.142 = 0.66
2. Reactive power required: Q = P · (tan φ1 − tan φ2) = 400 · (0.802 − 0.142) = 263.9 kVAr
Capacitor feeder: breaker ≥ 1.5 × In (IS 13340), cable ≥ 1.43 × In, capacitor-duty contactors with damping resistors per step, discharge resistors to ≤ 50 V in 1 min.
NBCS 2026 (SP 7:2026) Part D Sec 2 cl. 3.8.1: supply pf lower limit generally 0.95 lag — target 0.99 meets it.
NBCS 2026 (SP 7:2026) Part D Sec 2 cl. 5.3.6.6: non-linear loads (LED / VFD / UPS / IT) inject 3rd, 5th, 7th and 9th harmonics and can put almost phase-level current in the neutral; plan detuned capacitor banks and / or active filters at the design stage and locate the filter with the capacitor panel in a controlled (ventilated / air-conditioned) room.
NBCS 2026 (SP 7:2026) Part D Sec 2 cl. 8.2.9.1 note: with harmonic loads the neutral is sized equal to the phase conductor (half neutral no longer acceptable).
IEEE 519-2022 Table 2 (current distortion limits at PCC: TDD 5 % for I_sc/I_L < 20 … 20 % for > 1000) and Table 1 (voltage THD 8 % ≤ 1 kV); IEC 61000-3-6
AHF rating = rms harmonic current injected; CT class 1, ratio ≥ 1.2 × I_load
Standards and code references
Standard
Title
Used for
IS 13340:1993 / IEC 60831-1
Shunt capacitors of the self-healing type for a.c. systems up to 1000 V
Capacitor rating, 1.3 × In continuous overcurrent, feeder ≥ 1.5 × In
IS 13341:1992 / IEC 60831-2
Shunt capacitors — Ageing test, self-healing test and destruction test
Capacitor duty
NBCS 2026 (SP 7:2026) Part D Sec 2
National Building Construction Standards — Electrical and allied installations
pf ≥ 0.95 (cl. 3.8.1), harmonics (5.3.6.6), full neutral (8.2.9.1)
IEC 61921:2017
Power capacitors — Low-voltage power factor correction banks
APFC bank design, step switching, detuned reactors, discharge ≤ 50 V in 1 min
IEEE 519-2022
Harmonic control in electric power systems
THD limits at PCC (voltage 5–8 %, current 5–20 % by Isc/IL); active filter target THD-I
IEC 61000-3-6:2008
EMC — Assessment of emission limits for distorting loads (MV/HV)
Harmonic emission assessment
IEC 60364-5-52:2009
Low-voltage electrical installations — Selection and erection of wiring systems
Current-carrying capacity, derating (temperature, grouping, installation method), voltage drop ≤ 3–5 %
Prepared by
Checked by
Approved by
Results are design aids computed by designlink calc (calc.designlink.in). Verify with capacitor / reactor / AHF manufacturer data and the utility's pf tariff before issue.