Design Linkcalc.designlink.in

Short-circuit & discrimination study

Sample project — Tower A — short-circuit study · from voltage-drop project “Sample project — Tower A”
Generated 28 Nov 2026 16:09
Method: IEC 60909 impedance method · IEC 60364-4-43 cable withstand · IEC 60947-2 trip curves
Project code SAMPLE
Max fault level
5.2 kA
Feeders checked
4
Cable I²t failures
0
Breakers beyond kA steps
0
Discrimination
0 full · 2 partial · 1 none

1. Basis and method

ZT = %Z/100 · U²/S (R, X split by X/R)  ·  ZQ = c·U²/S"kQ (utility, in series)  ·  ZG = Xd"/100 · U²/S (DG)
Zcable = (R·f20°C + jX)·L/1000/runs  ·  Ik" = c·Un/(√3·|Zk|), c = 1.05 (max) / 0.95 (min)  ·  κ = 1.02 + 0.98·e−3R/X, ip = κ·√2·Ik"
Breaker: Icu ≥ Ik" at its bus → next standard step  ·  Cable: Smin = Ik"·√t / k (k: Cu XLPE 143, Cu PVC 115, Al XLPE 94, Al PVC 76; t: MCB 0.01 s, MCCB 0.03 s, ACB 0.4 s)  ·  MCB ≤ 63 A: Smin = √(I²t let-through of a class-3 MCB, IEC 60898-1 Annex ZC) / k (marked I²t); adiabatic for MCCB / ACB
Discrimination: downstream slowest trip < upstream fastest trip for all currents up to Ik" at the bus (bands ±10 % I, ±20 % t). Long-time t = tr·35/((I/Ir)²−1); short-time definite tsd above Isd; instantaneous ti above Ii.

2. Sources

NameBusTypekVA%Z / Xd"X/RUpstream MVAOn
TR-1 (TR-1 (1000 KVA))TR-1 (1000 KVA)transformer1604.53.5—Yes

3. Fault level at each panel bus

BusZ (mΩ)X/RIk" 3φ (kA)ip peak (kA)Breaker Icu ≥ (kA)Ik" DG-only (kA)
LP-1215.460.271.171.76.0
MLP58.721.614.287.16.0
TR-1 (1000 KVA) (source)48.443.505.1910.66.0

Fault level per bus — Ik″ and peak ip with the breaker Icu

Ik″ 3φ (kA)ip peak (kA)Ik″ DG-only (kA)breaker Icu step (≥ Ik″)024681012LP-11.21.7Icu 6MLP4.37.1Icu 6TR-1 (1000 KVA)5.210.6Icu 6Fault level at the bus, kA (IEC 60909)

4. Feeders — fault current, breaker breaking capacity, cable withstand

#From busToCable / bus ductL mR+jX seg (mΩ)Z cum (mΩ)X/RIk" From (kA)Ik" To (kA)ip (kA)BreakerIcu (kA)S min / have (sqmm)I²tIk" DG (kA)
1TR-1 (1000 kVA)MLP4C X 70 Sq.mm, AL × 14017.72 + j3.2858.721.615.194.287.1160A MCCB6.09.6 / 70OK
2MLPLP-14C X 6 Sq.mm, Cu × 160176.90 + j6.60215.460.274.281.171.725A MCB6.01.2 / 6 I²tOK
3MLPPP-1 (Pumps)4C X 50 Sq.mm, AL × 18051.29 + j6.7299.890.694.282.523.7125A MCCB6.07.9 / 50OK
4LP-1Lift-14C X 10 Sq.mm, Cu × 170123.40 + j7.00337.350.191.170.751.125A MCB6.00.8 / 10 I²tOK

5. Breaker trip settings

#FeederTypeIn (A)Ir (A)tr @6Ir (s)Isd (A)tsd (s)Ii (A)ti (s)Ik" at bus (kA)
1TR-1 (1000 kVA) → MLPMCCB16016010.0012800.1019200.0205.19
2MLP → LP-1MCB25253.00OFF0.002500.0104.28
3MLP → PP-1 (Pumps)MCCB12512510.0010000.1015000.0204.28
4LP-1 → Lift-1MCB25253.00OFF0.002500.0101.17

Defaults by type

TypeIr ×Intr sIsd ×Irtsd sIi ×Inti s
MCB1.0300100.01
MCCB1.01080.1120.02
ACB1.01060.300.02

6. Discrimination (selectivity) results

BusUpstreamDownstreamIk" (kA)StatusLimit (kA)Remark
MLP160A MCCB
TR-1 (1000 kVA) → MLP
25A MCB
MLP → LP-1
4.28PARTIAL1.68limited by upstream instantaneous — raise Ii, switch it OFF (ACB) or use manufacturer selectivity table / zone selectivity
MLP160A MCCB
TR-1 (1000 kVA) → MLP
125A MCCB
MLP → PP-1 (Pumps)
4.28PARTIAL1.12limited by upstream short-time pick-up — raise Isd or add time delay tsd
LP-125A MCB
MLP → LP-1
25A MCB
LP-1 → Lift-1
1.17NONE—upstream can trip first even at low fault currents

7. Time-current curves

MLP: 160A MCCB (upstream) vs 25A MCB (downstream) — PARTIAL · selectivity limit 1.68 kA

100 A1 kA0.01 s0.1 s1 s10 s1 min16 minIk" 4.28 kAlimit 1.68 kATR-1 (1000 kVA) → MLP 160A MCCB — upstreamMLP → LP-1 25A MCB — downstreamCurrent (log)

limited by upstream instantaneous — raise Ii, switch it OFF (ACB) or use manufacturer selectivity table / zone selectivity

MLP: 160A MCCB (upstream) vs 125A MCCB (downstream) — PARTIAL · selectivity limit 1.12 kA

100 A1 kA0.01 s0.1 s1 s10 s1 min16 minIk" 4.28 kAlimit 1.12 kATR-1 (1000 kVA) → MLP 160A MCCB — upstreamMLP → PP-1 (Pumps) 125A MCCB — downstreamCurrent (log)

limited by upstream short-time pick-up — raise Isd or add time delay tsd

LP-1: 25A MCB (upstream) vs 25A MCB (downstream) — NONE

100 A1 kA0.01 s0.1 s1 s10 s1 min16 minIk" 1.17 kAMLP → LP-1 25A MCB — upstreamLP-1 → Lift-1 25A MCB — downstreamCurrent (log)

upstream can trip first even at low fault currents

8. Worked examples — from this project

Worked from this project’s own inputs and results — each value can be traced to the schedules above.

Fault level at TR-1 (1000 KVA) — scenario ‘study’
The main LV bus with the highest fault level; every downstream level is cascaded from it.
Given: Un 415 V · cmax 1.05 (IEC 60909-0 Table 1, LV)
1. TR-1 (TR-1 (1000 KVA)) transformer: ZT = uk/100 · U²/SrT = 4.5/100 · 415² / 160 000 = 48.438 mΩ (X/R 3.5: RT = Z/√(1+(X/R)²), XT = R·X/R)
2. TR-1 (TR-1 (1000 KVA)) R + jX: RT + jXT = 13.307 + j46.575 mΩ (infinite upstream network (no S″kQ entered))
3. Initial symmetrical short-circuit current: Ik″ = c·Un / (√3·|Zk|) = 1.05 · 415 / (1.732 · 0.04844 Ω) = 5.19 kA (study value 5.19 kA)
4. Peak current: κ = 1.02 + 0.98·e−3R/X; ip = κ·√2·Ik″ = X/R = 3.5 → κ = 1.436; 1.436 · 1.414 · 5.19 = 10.55 kA (study 10.55 kA)
5. Breaker breaking capacity at this bus: Icu ≥ Ik″ → next standard step → 5.19 kA → 6 kA PASS
Feeder MLP → LP-1 — fault current and cable withstand
The feeder with the smallest short-circuit withstand margin (S_min / S installed) in the study.
Given: Cable 4C X 6 Sq.mm, Cu × 1, L = 60 m · Protective device 25 A MCB
1. Fault level at MLP (cable start): Ik,from = from the bus table (|Z| = 58.722 mΩ) = 4.28 kA
2. Cable impedance: Zc = (R·f20°C + jX)·L / (1000·n) = (3.78·0.78 + j0.11) · 60 / (1000 · 1) = 176.904 + j6.6 mΩ (R at 20 °C for the maximum fault current (IEC 60909-0 §5.3))
3. Fault level at LP-1 (cable end): Ik,to = c·Un / (√3·|Zbus + Zc|) = 1.05 · 415 / (1.732 · 215.46 mΩ) = 1.17 kA (X/R 0.27, ip 1.68 kA)
4. Let-through energy of the MCB: I²t (class 3, IEC 60898-1 Annex ZC) = at 4.28 kA = 30 702 A²s
5. Minimum section: Smin = √(I²t) / k = √30 702 / 143.0 = 1.2 mm²
6. Cable withstand: S × n ≥ Smin → 6 ≥ 1.2 mm² PASS
7. Breaker at MLP: Icu ≥ Ik,from → 6 ≥ 4.28 kA PASS
Discrimination 25A MCB (MLP → LP-1) over 25A MCB (LP-1 → Lift-1)
The least selective pair in the study.
Given: Upstream MCB 25 A: Ir 25 A, tr 3 s, Ii 250 A · Downstream MCB 25 A, Ii 250 A
1. Rule: tmax,downstream(I) < tmin,upstream(I) for every I ≤ Ik″ at the bus = tolerance bands ±10 % current, ±20 % time
2. Prospective fault at LP-1: Ik″ = 1.17 kA
3. Selectivity limit: Is ≥ Ik″ for total selectivity → selective up to — kA vs 1.17 kA → none CHECK (upstream can trip first even at low fault currents)

9. Settings

SettingValue
voltage415
c_max1.05
c_min0.95
r_temp_factor0.78
bd_temp_factor1.0
k_cu_pvc115
k_cu_xlpe143
k_al_pvc76
k_al_xlpe94
t_mcb0.01
t_mccb0.03
t_acb0.4
util_xr10
dg_xd_pct16
dg_xr6.7
mcb_ruleclass3
tr_table[{'kva_max': 630, 'z_pct': 4.5, 'xr': 5}, {'kva_max': 1250, 'z_pct': 5.0, 'xr': 7}, {'kva_max': 2500, 'z_pct': 6.25, 'xr': 9}, {'kva_max': 5000, 'z_pct': 7.15, 'xr': 10}]
ka_steps6, 10, 16, 25, 36, 50, 65, 80, 100, 120, 150

10. Formulae applied (with code clauses)

QuantityFormulaReference / clauseNotes
Transformer impedance (referred to LV)Z_T = (u_kr / 100) · U_n² / S_rT ; R_T, X_T from X/RIEC 60909-0:2016 cl. 6.3.2 eq. (7)-(9); u_kr per IS 1180 Pt 1:2014 Table / IS 2026 Pt 1Typical u_kr: 4.5 % ≤ 630 kVA, 5 % ≤ 1250 kVA, 6.25 % ≤ 2500 kVA (editable)
Network feeder (utility) impedanceZ_Q = c · U_nQ² / S"_kQ (referred to LV by 1/t_r²)IEC 60909-0:2016 cl. 6.2.1 eq. (4)-(5); X_Q/R_Q ≈ 10 (cl. 6.2.1 note)Blank MVA = infinite bus
Generator (DG) impedanceZ_G = (x"_d / 100) · U_rG² / S_rGIEC 60909-0:2016 cl. 6.6.1 eq. (18); x"_d from generator data (default 16 %)DG-only case uses c_min for the minimum fault level (cl. 5.3.1)
Cable impedanceZ_L = (R_20 + jX) · L / (1000 · n) ; R_20 = R_θ / (1 + α(θ − 20))IEC 60909-0:2016 cl. 6.7 (line impedances at 20 °C for maximum current); α per IS 8130:2013Catalogue R at 90 °C × 0.78 ≈ R at 20 °C
Initial symmetrical short-circuit currentI"_k = c · U_n / (√3 · |Z_k|)IEC 60909-0:2016 cl. 7.1.1 eq. (29); voltage factor c Table 1 (c_max 1.05 / 1.10, c_min 0.95 for LV)
Peak short-circuit currenti_p = κ · √2 · I"_k ; κ = 1.02 + 0.98 · e^(−3R/X)IEC 60909-0:2016 cl. 8.1.1 eq. (55)-(56)Used for busbar dynamic withstand (IEC 61439-1 cl. 10.11.5)
Breaker breaking capacityI_cu ≥ I"_k at the bus where the breaker is installed → next standard kA stepIEC 60947-2:2016 cl. 4.3.5.2 (I_cu), 4.3.5.3 (I_cs), 4.3.5.4 (I_cw); IS/IEC 61439-1 cl. 10.11 (I_cw of assembly)Steps 6/10/16/25/36/50/65/80/100 kA (editable)
Cable short-circuit withstand (adiabatic)I² · t ≤ k² · S² → S_min = I"_k · √t / kIEC 60364-4-43:2008 cl. 434.5.2, Table 43A (k: Cu PVC 115, Cu XLPE 143, Al PVC 76, Al XLPE 94)t = clearing time of the upstream breaker (MCB 0.01 s, MCCB 0.03 s, ACB with STD 0.4 s, editable)
Long-time (thermal) tript = t_r · 35 / ((I/I_r)² − 1) (I²t inverse, asymptotic at I_r)IEC 60947-2:2016 Annex F / cl. 7.2.1.2.4 (L-release, ±10 % current tolerance); IEC 60898-1:2015 Table 6 (1.13 I_n no trip 1 h, 1.45 I_n trip < 1 h)t_r = trip time at 6 × I_r
Short-time tript = t_sd for I ≥ I_sd (definite time)IEC 60947-2:2016 cl. 7.2.1.2.4 (S-release), tolerance ±10 % current / ±20 % time
Instantaneous tript = t_i for I ≥ I_i ; MCB C-curve 5–10 × I_nIEC 60898-1:2015 Table 7 (B 3–5, C 5–10, D 10–20 × I_n); IEC 60947-2 cl. 7.2.1.2.4 (I-release)
Discrimination (selectivity) criteriont_max,downstream(I) < t_min,upstream(I) for all I ≤ I"_k at the downstream bus ; limit = highest I satisfying itIEC 60947-2:2016 Annex A (selectivity, A.4 total / partial); IEC 60364-5-53:2019 cl. 535 (coordination); IS 10118 Pt 3Energy-based selectivity in the instantaneous zone requires manufacturer tables (IEC 60947-2 Annex A.5)
Device numbers50/51 OC, 50N/51N EF, 64 REF, 86 lockout, 95 trip-circuit supervision, 25 sync-check, 27/59 U/V–O/V, 32 reverse powerIEEE C37.2-2008 Table 1

11. Standards and code references

StandardTitleUsed for
IEC 60909-0:2016Short-circuit currents in three-phase a.c. systems — Calculation of currentsImpedance method, voltage factor c (1.05 / 1.10 max, 0.95 min), peak factor κ = 1.02 + 0.98·e^(−3R/X), Ik" = c·Un/(√3·Zk)
IS 13234 (Part 1):2022 / IEC 60909-0Short-circuit currents in three-phase a.c. systemsIndian adoption of IEC 60909
IS 8130:2013Conductors for insulated electric cables and flexible cordsConductor resistance at 20 °C; temperature coefficient for fault-level resistance correction
IEC 60364-4-43:2008Protection against overcurrentIb ≤ In ≤ Iz, adiabatic cable withstand I²t ≤ k²S² with k = 143 (Cu XLPE), 115 (Cu PVC), 94 (Al XLPE), 76 (Al PVC)
IEC 60947-2:2016 / IS/IEC 60947-2Low-voltage switchgear — Circuit-breakersACB/MCCB ratings Icu, Ics, Icw; release characteristics (L-S-I-G); selectivity definitions
IEC 61439-1/2:2020 / IS/IEC 61439Low-voltage switchgear and controlgear assembliesPanel construction (TTA/PTTA), busbar short-time withstand (Icw 1 s), temperature rise, IP rating
IS 1180 (Part 1):2014Outdoor type oil-immersed distribution transformers up to 2500 kVA, 33 kVTypical impedance (%Z) by rating
IS 2026 (Part 1):2011 / IEC 60076-1Power transformersImpedance voltage, ratings, Dyn11 vector group
IEC 60076-5:2006Power transformers — Ability to withstand short circuitTransformer short-circuit impedance and withstand
IEC 60898-1:2015 / IS/IEC 60898-1Circuit-breakers for overcurrent protection for household and similar installations (MCB)B/C/D tripping bands (C: 5–10 × In), thermal tripping 1.13/1.45 × In
IEC 60255-151:2009Measuring relays — Overcurrent protection functional requirementsIDMT / definite-time characteristics used in discrimination curves
IS 10118 (Part 1–4):1982Code of practice for selection, installation and maintenance of switchgear and controlgearDiscrimination / coordination practice
IEEE C37.2-2008Standard electrical power system device function numbers (ANSI)Relay codes 50, 51, 50N, 51N, 64, 86, 95, 27, 59, 25, 32
Prepared by
Checked by
Approved by

Results are design aids computed by designlink calc (calc.designlink.in). Verify against transformer test certificates (%Z), breaker let-through / selectivity tables and cable manufacturer data before issue.