Bars per phase, short-circuit minimum section, forces and supports.
IEC 61439-1 · IEC 60865
| Field | Type / default | Meaning |
|---|---|---|
| Duty | ||
| Conductor material | choice default cu | Copper, Aluminium |
| Rated current per phase | number (A) default 1600 | |
| Short-circuit current (rms) | number (kA) default 50 | |
| Peak short-circuit current (blank = 2.2 × Ik) | number (kA) | |
| Fault duration | number (s) default 1.0 | |
| Arrangement | choice default open | Open air (bars on edge, free convection), Enclosed, ventilated panel (× 0.85), Enclosed, non-ventilated busduct (× 0.75), Sandwich busduct (manufacturer data; × 0.9) |
| Thermal | ||
| Ambient temperature | number (°C) default 40 | |
| Permissible temperature rise | number (K) default 35 | IS 8623 practice 35 K (bare Cu); IEC 61439-1 allows higher where connections and insulation permit |
| Surface finish | choice default bright | Bright / bare (ε ≈ 0.3), Painted / oxidised (ε ≈ 0.9) |
| Bars per phase (0 = auto) | number default 0 | |
| Preferred bar width (0 = auto) | number (mm) default 0 | |
| Mechanical | ||
| Phase centre spacing | number (mm) default 150 | |
| Support spacing (0 = compute maximum) | number (mm) default 0 | |
| Longest straight run (busduct / rising main, 0 = n/a) | number (m) default 0 | NBCS 2026 D2 5.3.8.1: seismic supports for > 24 m horizontal / > 12 m vertical straight lengths |
| Run direction | choice default h | Horizontal, Vertical (rising main) |
| Support factor β | choice default 0.73 | 1.0 simply supported (single span), 0.73 continuous beam, 3+ supports, 0.5 fixed ends |
| Output | Content |
|---|---|
| Results, checks, worked steps, schedules; report, Excel and DXF exports. | |