USER GUIDE

Bus bar / bus duct sizing

Bars per phase, short-circuit minimum section, forces and supports.

IEC 61439-1 · IEC 60865

How to use it

  1. Enter the inputs on the left — defaults are a typical case; every field has a note.
  2. Results, checks (PASS / CHECK) and worked steps appear on the right as you type; Drawing and 3D tabs where the calculation has a layout.
  3. Save the project, then export the Report, Excel with formulas.

Inputs

FieldType / defaultMeaning
Duty
Conductor materialchoice default cu
Copper, Aluminium
Rated current per phasenumber (A) default 1600
Short-circuit current (rms)number (kA) default 50
Peak short-circuit current (blank = 2.2 × Ik)number (kA)
Fault durationnumber (s) default 1.0
Arrangementchoice default open
Open air (bars on edge, free convection), Enclosed, ventilated panel (× 0.85), Enclosed, non-ventilated busduct (× 0.75), Sandwich busduct (manufacturer data; × 0.9)
Thermal
Ambient temperaturenumber (°C) default 40
Permissible temperature risenumber (K) default 35IS 8623 practice 35 K (bare Cu); IEC 61439-1 allows higher where connections and insulation permit
Surface finishchoice default bright
Bright / bare (ε ≈ 0.3), Painted / oxidised (ε ≈ 0.9)
Bars per phase (0 = auto)number default 0
Preferred bar width (0 = auto)number (mm) default 0
Mechanical
Phase centre spacingnumber (mm) default 150
Support spacing (0 = compute maximum)number (mm) default 0
Longest straight run (busduct / rising main, 0 = n/a)number (m) default 0NBCS 2026 D2 5.3.8.1: seismic supports for > 24 m horizontal / > 12 m vertical straight lengths
Run directionchoice default h
Horizontal, Vertical (rising main)
Support factor βchoice default 0.73
1.0 simply supported (single span), 0.73 continuous beam, 3+ supports, 0.5 fixed ends

What you get

OutputContent
Results, checks, worked steps, schedules; report, Excel and DXF exports.

Standards applied

Good to know