USER GUIDE

Earthing & earth mat

Electrodes, pits for target Ω, strips, IEEE 80 grid with step and mesh voltage.

IS 3043 · IEEE 80

How to use it

  1. Enter the inputs on the left — defaults are a typical case; every field has a note.
  2. Results, checks (PASS / CHECK) and worked steps appear on the right as you type; Drawing and 3D tabs where the calculation has a layout.
  3. Save the project, then export the Report, Excel with formulas.

Inputs

FieldType / defaultMeaning
Site & fault
Soil resistivitynumber (Ω·m) default 100measured (Wenner 4-pin) or IS 3043 Table 1: clay 10–50, loam 50–100, sand 100–500, rock 1000+
Target earth resistancenumber (Ω) default 1.0practice: ≤ 1 Ω substations, ≤ 5 Ω LT installations; NBCS 2026 gives no general value (LPS earth < 10 Ω, cl. 11.6.3)
Earth-fault currentnumber (kA) default 25
Fault clearing timenumber (s) default 1.0
Earth conductor materialchoice default gi
GI strip / flat, Copper, Aluminium
Corrosion allowancenumber (%) default 30IS 3043 cl. 12: allow for corrosion in buried steel (typically 30 % for GI)
Largest phase conductor (for PE sizing)number (mm²) default 240
Earthing three-phase equipment / installation (two distinct earths, NBCS 8.2.9)yes / no default True
Electrode
Electrode typechoice default pipe
Pipe / rod (vertical), Plate (vertical, buried), Strip / conductor (horizontal)
Electrode material (NBCS Table 2 check)choice default gi
Hot-dip galvanised steel, Copper, Copper-sheathed steel, Steel with electro-deposited copper (copper-bonded), Stainless steel
Pipe or solid rodchoice default pipe
Pipe, Solid round rod
Lengthnumber (m) default 3.0
Diameter (pipe / rod)number (mm) default 40
Plate size (square)number (mm) default 600
Plate thicknessnumber (mm) default 3
Strip widthnumber (mm) default 25
Strip thicknessnumber (mm) default 6
Burial depth (top)number (m) default 0.6
Spacing between electrodesnumber (m) default 6.0
Backfill / treatmentchoice default none
Native soil, Bentonite / conductive backfill (× 0.6), Chemical / maintenance-free electrode (× 0.5)
Substation earth mat (IEEE 80)
Design an earth gridyes / no default False
Grid lengthnumber (m) default 30
Grid widthnumber (m) default 20
Conductor spacingnumber (m) default 5
Grid depthnumber (m) default 0.6
Number of rodsnumber default 20
Rod lengthnumber (m) default 3
Grid conductor diameternumber (mm) default 10
Surface layer resistivity (gravel)number (Ω·m) default 3000
Surface layer thicknessnumber (m) default 0.1
Grid current I_G (blank = 0.6 × fault × 1.05 decrement)number (kA)
Shock durationnumber (s) default 0.5

What you get

OutputContent
Results, checks, worked steps, schedules; report, Excel and DXF exports.