Electrodes, pits for target Ω, strips, IEEE 80 grid with step and mesh voltage.
IS 3043 · IEEE 80
| Field | Type / default | Meaning |
|---|---|---|
| Site & fault | ||
| Soil resistivity | number (Ω·m) default 100 | measured (Wenner 4-pin) or IS 3043 Table 1: clay 10–50, loam 50–100, sand 100–500, rock 1000+ |
| Target earth resistance | number (Ω) default 1.0 | practice: ≤ 1 Ω substations, ≤ 5 Ω LT installations; NBCS 2026 gives no general value (LPS earth < 10 Ω, cl. 11.6.3) |
| Earth-fault current | number (kA) default 25 | |
| Fault clearing time | number (s) default 1.0 | |
| Earth conductor material | choice default gi | GI strip / flat, Copper, Aluminium |
| Corrosion allowance | number (%) default 30 | IS 3043 cl. 12: allow for corrosion in buried steel (typically 30 % for GI) |
| Largest phase conductor (for PE sizing) | number (mm²) default 240 | |
| Earthing three-phase equipment / installation (two distinct earths, NBCS 8.2.9) | yes / no default True | |
| Electrode | ||
| Electrode type | choice default pipe | Pipe / rod (vertical), Plate (vertical, buried), Strip / conductor (horizontal) |
| Electrode material (NBCS Table 2 check) | choice default gi | Hot-dip galvanised steel, Copper, Copper-sheathed steel, Steel with electro-deposited copper (copper-bonded), Stainless steel |
| Pipe or solid rod | choice default pipe | Pipe, Solid round rod |
| Length | number (m) default 3.0 | |
| Diameter (pipe / rod) | number (mm) default 40 | |
| Plate size (square) | number (mm) default 600 | |
| Plate thickness | number (mm) default 3 | |
| Strip width | number (mm) default 25 | |
| Strip thickness | number (mm) default 6 | |
| Burial depth (top) | number (m) default 0.6 | |
| Spacing between electrodes | number (m) default 6.0 | |
| Backfill / treatment | choice default none | Native soil, Bentonite / conductive backfill (× 0.6), Chemical / maintenance-free electrode (× 0.5) |
| Substation earth mat (IEEE 80) | ||
| Design an earth grid | yes / no default False | |
| Grid length | number (m) default 30 | |
| Grid width | number (m) default 20 | |
| Conductor spacing | number (m) default 5 | |
| Grid depth | number (m) default 0.6 | |
| Number of rods | number default 20 | |
| Rod length | number (m) default 3 | |
| Grid conductor diameter | number (mm) default 10 | |
| Surface layer resistivity (gravel) | number (Ω·m) default 3000 | |
| Surface layer thickness | number (m) default 0.1 | |
| Grid current I_G (blank = 0.6 × fault × 1.05 decrement) | number (kA) | |
| Shock duration | number (s) default 0.5 | |
| Output | Content |
|---|---|
| Results, checks, worked steps, schedules; report, Excel and DXF exports. | |