USER GUIDE

Occupant load & means of egress

NBCS 2026 Part F Tables 2–4 (NBC 2016 or IBC 2021 option): occupants from area, stair / door exit widths, number of exits, travel distance and dead-end checks, minimum widths.

NBCS 2026 Part F · IBC 2021

How to use it

  1. Enter the inputs on the left — defaults are a typical case; every field has a note.
  2. Results, checks (PASS / CHECK) and worked steps appear on the right as you type; Drawing and 3D tabs where the calculation has a layout.
  3. Save the project, then export the Report, Excel with formulas.

Inputs

FieldType / defaultMeaning
Floor
Codechoice default nbc
Indian — NBCS 2026 / NBC 2016, IBC 2021 / NFPA 101 — International
Indian code editionchoice default nbcs2026
NBCS 2026 (SP 7:2026) Part F, NBC 2016 Part 4
Occupancychoice default bus
Residential — apartments, lodging, dormitory (A-I/II/III), Residential — one / two-family dwelling, Residential — hotel (A-IV/A-V), Educational (B), Institutional — hospital inpatient / wards (C), Institutional — hospital outpatient (C), Institutional — nursing home (C), Institutional — day-care clinic (C) …
Floor area (net or gross as the occupancy factor states)number (m²) default 1500
Fixed seatsnumber default 0
Declared occupants (0 = from area; NBC uses the larger)number default 0
Stair sizingchoice default floor
Floor by floor — largest floor served (NBCS 4.4.2.3 e), Cumulative — all floors served (conservative)
Identical floors above served by the same stairsnumber default 0
Occupants of other floors served (comma-separated, optional)text
Building heightnumber (m) default 30High-rise ≥ 24 m (NBCS 2.39) / ≥ 15 m (NBC 2016); special-building limits of cl. 1.2
This floor is a basementyes / no default False
Fully sprinkleredyes / no default True
Construction typechoice default t12
Types 1 and 2, Types 3 and 4
High-ceiling area (NBCS Table 4 Notes 5 / 6)choice default none
No, Ceiling ≥ 10 m at ground floor, sprinklered (Note 5), Ceiling ≥ 17 m, sprinkler-exempt (Note 6)
Provided
Exit staircases providednumber default 2
Stair clear width eachnumber (mm) default 2000
Exit doors providednumber default 2
Door clear width eachnumber (mm) default 1000
Longest travel distance to an exitnumber (m) default 28
Longest dead-end corridornumber (m) default 4
Common path of travel (0 = not checked)number (m) default 0
Corridor clear widthnumber (mm) default 1800

What you get

OutputContent
Results, checks, worked steps, schedules; report, Excel and DXF exports.