USER GUIDE

Exhaust fan by air changes

Room volume × air changes → airflow, number and sweep of exhaust fans, make-up air opening.

ASHRAE 62.1 · practice

How to use it

  1. Enter the inputs on the left — defaults are a typical case; every field has a note.
  2. Results, checks (PASS / CHECK) and worked steps appear on the right as you type; Drawing and 3D tabs where the calculation has a layout.
  3. Save the project, then export the Report, Excel with formulas.

Inputs

FieldType / defaultMeaning
Room
Lengthnumber (m) default 4
Widthnumber (m) default 3
Heightnumber (m) default 3
Use (air changes, typical)choice default toilet
Toilet / bathroom — 10 ACH, Domestic kitchen — 15 ACH, Commercial kitchen (without hood calculation) — 30 ACH, Store — 6 ACH, Plant / pump room — 10 ACH, Laundry — 15 ACH, Garage / small parking — 6 ACH, Office (no AC) — 6 ACH …
Air changes per hour (custom)number default 10
Fans
Number of fans (0 = choose)number default 0
Derating for louvre / short ductnumber (%) default 20
Velocity through the make-up openingnumber (m/s) default 2.0

What you get

OutputContent
Results, checks, worked steps, schedules; report, Excel and DXF exports.

Standards applied

Good to know