Novec 1230 / FM-200 / inert / CO₂ agent quantity, cylinders, nozzles, venting.
NFPA 2001 · NFPA 12
| Field | Type / default | Meaning |
|---|---|---|
| Hazard | ||
| Agent | choice default fk | FK-5-1-12 (Novec 1230), HFC-227ea (FM-200), HFC-125 (ECARO-25), IG-541 (Inergen: N₂ 52 % · Ar 40 % · CO₂ 8 %), IG-55 (Argonite: N₂ 50 % · Ar 50 %), IG-100 (Nitrogen), Carbon dioxide (NFPA 12, total flooding) |
| Hazard class | choice default C | Class A — surface fire (offices, archives), Class C — energised electrical (server / data / control rooms), Class B — flammable liquids (heptane basis) |
| CO₂ deep-seated hazard | choice default elec | Electrical hazards / switchgear (50 %), Record / archive storage (65 %), Dust collectors / fur (75 %), Cable galleries (50 %), Surface fire only (34 %) |
| Minimum design concentration (blank = NFPA 2001 minimum for the class) | number (%) | Enter the listed / IS 15493 – ISO 14520 value when the system listing asks for more (e.g. IG-541 class A 39.9 %) |
| Extra design factor on agent quantity | number default 1.0 | 1.0 = NFPA 2001 minimum (the design concentration already carries the 1.2 / 1.3 / 1.35 safety factor); > 1 for unclosable openings, tee-count or owner margin |
| Normally occupied | yes / no default True | |
| Minimum anticipated room temperature | number (°C) default 20.0 | |
| Maximum anticipated room temperature | number (°C) default 35.0 | |
| Site altitude | number (m) default 220 | |
| Enclosure | ||
| Room length | number (m) default 12 | |
| Room width | number (m) default 8 | |
| Room height (floor to ceiling) | number (m) default 3.0 | |
| Raised-floor void (0 = none) | number (m) default 0.6 | |
| Ceiling void (0 = none or not protected) | number (m) default 0 | |
| Impermeable fixed volume to deduct (columns, ducts) | number (m³) default 0 | |
| Enclosure strength (pressure-relief design) | number (Pa) default 250 | |
| Installed pressure-relief vent free area (0 = none yet) | number (m²) default 0 | |
| Hold time | number (min) default 10 | |
| System | ||
| Cylinder size (blank = auto) | number (L) | |
| Inert-gas cylinder pressure | choice default 300 | 200 bar, 300 bar |
| Halocarbon design fill density (blank = auto, fewest containers ≤ max fill) | number (kg/L) | |
| Nozzle coverage (side of square) | number (m) default 9.8 | Listed 360° nozzles typically ≤ 9.8 m square (32 ft); 180° nozzles half that |
| Max height per nozzle tier | number (m) default 4.9 | |
| Pipe run cylinders → farthest nozzle | number (m) default 25 | |
| Discharge design target (blank = 8.5 s halocarbon / 50 s inert) | number (s) | Keep a margin below the 10 s / 60 s limit so valve and fabrication tolerances stay compliant |
| 100 % connected reserve bank | yes / no default False | |
| Output | Content |
|---|---|
| Results, checks, worked steps, schedules; report, Excel and DXF exports. | |