USER GUIDE

Gas suppression

Novec 1230 / FM-200 / inert / CO₂ agent quantity, cylinders, nozzles, venting.

NFPA 2001 · NFPA 12

How to use it

  1. Enter the inputs on the left — defaults are a typical case; every field has a note.
  2. Results, checks (PASS / CHECK) and worked steps appear on the right as you type; Drawing and 3D tabs where the calculation has a layout.
  3. Save the project, then export the Report, Excel with formulas and DXF.

Inputs

FieldType / defaultMeaning
Hazard
Agentchoice default fk
FK-5-1-12 (Novec 1230), HFC-227ea (FM-200), HFC-125 (ECARO-25), IG-541 (Inergen: N₂ 52 % · Ar 40 % · CO₂ 8 %), IG-55 (Argonite: N₂ 50 % · Ar 50 %), IG-100 (Nitrogen), Carbon dioxide (NFPA 12, total flooding)
Hazard classchoice default C
Class A — surface fire (offices, archives), Class C — energised electrical (server / data / control rooms), Class B — flammable liquids (heptane basis)
CO₂ deep-seated hazardchoice default elec
Electrical hazards / switchgear (50 %), Record / archive storage (65 %), Dust collectors / fur (75 %), Cable galleries (50 %), Surface fire only (34 %)
Minimum design concentration (blank = NFPA 2001 minimum for the class)number (%)Enter the listed / IS 15493 – ISO 14520 value when the system listing asks for more (e.g. IG-541 class A 39.9 %)
Extra design factor on agent quantitynumber default 1.01.0 = NFPA 2001 minimum (the design concentration already carries the 1.2 / 1.3 / 1.35 safety factor); > 1 for unclosable openings, tee-count or owner margin
Normally occupiedyes / no default True
Minimum anticipated room temperaturenumber (°C) default 20.0
Maximum anticipated room temperaturenumber (°C) default 35.0
Site altitudenumber (m) default 220
Enclosure
Room lengthnumber (m) default 12
Room widthnumber (m) default 8
Room height (floor to ceiling)number (m) default 3.0
Raised-floor void (0 = none)number (m) default 0.6
Ceiling void (0 = none or not protected)number (m) default 0
Impermeable fixed volume to deduct (columns, ducts)number (m³) default 0
Enclosure strength (pressure-relief design)number (Pa) default 250
Installed pressure-relief vent free area (0 = none yet)number (m²) default 0
Hold timenumber (min) default 10
System
Cylinder size (blank = auto)number (L)
Inert-gas cylinder pressurechoice default 300
200 bar, 300 bar
Halocarbon design fill density (blank = auto, fewest containers ≤ max fill)number (kg/L)
Nozzle coverage (side of square)number (m) default 9.8Listed 360° nozzles typically ≤ 9.8 m square (32 ft); 180° nozzles half that
Max height per nozzle tiernumber (m) default 4.9
Pipe run cylinders → farthest nozzlenumber (m) default 25
Discharge design target (blank = 8.5 s halocarbon / 50 s inert)number (s)Keep a margin below the 10 s / 60 s limit so valve and fabrication tolerances stay compliant
100 % connected reserve bankyes / no default False

What you get

OutputContent
Results, checks, worked steps, schedules; report, Excel and DXF exports.

Standards applied

Good to know