Demand, storage, heater or heat pump kW, recirculation pipe and pump.
NBCS 2026 Part E · IS 2065
| Field | Type / default | Meaning |
|---|---|---|
| Demand | ||
| Occupancy | choice default hotel | Residential (per person), Hotel (per guest), Hostel (per person), Hospital (per bed), Office (per person), Restaurant (per meal), Gym / club (per shower), School (per student) |
| Number of persons / beds / meals / showers | number default 200 | |
| Litres per unit per day at 60 °C (0 = design-practice table) | number (L) default 0 | NBCS 2026 has no per-occupancy hot-water table; the defaults are ASHRAE / ASPE design-practice values |
| Peak-hour fraction of daily (0 = table) | number default 0 | |
| Storage temperature | number (°C) default 60 | NBCS E1 4.14.2.2: 60 °C, up to 65 °C with soft water and limited storage |
| Cold water inlet | number (°C) default 20 | |
| Use temperature (info) | number (°C) default 43 | |
| Plant | ||
| Usable storage as fraction of peak-hour demand | number default 0.8 | ASHRAE: storage 0.6–1.0 × peak hour with recovery over 2–4 h |
| Recovery period | number (h) default 3 | |
| Heat source | choice default hp | Electric immersion / instantaneous, Air-source heat pump, Gas / diesel boiler + calorifier, Solar (with electric back-up) |
| Heat pump COP | number default 3.5 | |
| Boiler efficiency | number default 0.88 | |
| Solar fraction | number default 0.6 | |
| Heaters in parallel | number default 2 | |
| Recirculation | ||
| Recirculation loop length (flow + return) | number (m) default 300 | |
| Insulated pipe heat loss | number (W/m) default 15 | |
| Allowed temperature drop in loop | number (K) default 5 | NBCS E1 4.2.3: keep ≥ 50 °C at all points |
| Hot-water pipe material | choice default cu | Copper (NBCS 4.8.6: ≤ 1.5 m/s), CPVC / PPR / PEX, Stainless steel |
| NBCS 2026 checks | ||
| Longest draw-off pipe (dead leg) — largest internal Ø | number (mm) default 20 | |
| Its length from the tap to the tank / circulation pipe | number (m) default 10 | NBCS E1 Table 5: ≤ 12 m (Ø ≤ 20), 7.5 m (20–25), 3 m (> 25) |
| Bath tubs per dwelling | number default 0 | |
| Storage per bath tub at 60 °C (50–75 L) | number (L) default 60 | |
| Showers / bucket taps per dwelling (25 L each) | number default 2 | |
| Output | Content |
|---|---|
| Results, checks, worked steps, schedules; report, Excel and DXF exports. | |