USER GUIDE

Hot water system

Demand, storage, heater or heat pump kW, recirculation pipe and pump.

NBCS 2026 Part E · IS 2065

How to use it

  1. Enter the inputs on the left — defaults are a typical case; every field has a note.
  2. Results, checks (PASS / CHECK) and worked steps appear on the right as you type; Drawing and 3D tabs where the calculation has a layout.
  3. Save the project, then export the Report, Excel with formulas.

Inputs

FieldType / defaultMeaning
Demand
Occupancychoice default hotel
Residential (per person), Hotel (per guest), Hostel (per person), Hospital (per bed), Office (per person), Restaurant (per meal), Gym / club (per shower), School (per student)
Number of persons / beds / meals / showersnumber default 200
Litres per unit per day at 60 °C (0 = design-practice table)number (L) default 0NBCS 2026 has no per-occupancy hot-water table; the defaults are ASHRAE / ASPE design-practice values
Peak-hour fraction of daily (0 = table)number default 0
Storage temperaturenumber (°C) default 60NBCS E1 4.14.2.2: 60 °C, up to 65 °C with soft water and limited storage
Cold water inletnumber (°C) default 20
Use temperature (info)number (°C) default 43
Plant
Usable storage as fraction of peak-hour demandnumber default 0.8ASHRAE: storage 0.6–1.0 × peak hour with recovery over 2–4 h
Recovery periodnumber (h) default 3
Heat sourcechoice default hp
Electric immersion / instantaneous, Air-source heat pump, Gas / diesel boiler + calorifier, Solar (with electric back-up)
Heat pump COPnumber default 3.5
Boiler efficiencynumber default 0.88
Solar fractionnumber default 0.6
Heaters in parallelnumber default 2
Recirculation
Recirculation loop length (flow + return)number (m) default 300
Insulated pipe heat lossnumber (W/m) default 15
Allowed temperature drop in loopnumber (K) default 5NBCS E1 4.2.3: keep ≥ 50 °C at all points
Hot-water pipe materialchoice default cu
Copper (NBCS 4.8.6: ≤ 1.5 m/s), CPVC / PPR / PEX, Stainless steel
NBCS 2026 checks
Longest draw-off pipe (dead leg) — largest internal Ønumber (mm) default 20
Its length from the tap to the tank / circulation pipenumber (m) default 10NBCS E1 Table 5: ≤ 12 m (Ø ≤ 20), 7.5 m (20–25), 3 m (> 25)
Bath tubs per dwellingnumber default 0
Storage per bath tub at 60 °C (50–75 L)number (L) default 60
Showers / bucket taps per dwelling (25 L each)number default 2

What you get

OutputContent
Results, checks, worked steps, schedules; report, Excel and DXF exports.

Standards applied

Good to know