USER GUIDE

IDMT relay setting & grading

Plug and TMS for OC / EF relays, operating times, grading margins down the chain and across transformers, time-current curves.

IEC 60255-151 · IEEE 242

How to use it

  1. Enter the inputs on the left — defaults are a typical case; every field has a note.
  2. Results, checks (PASS / CHECK) and worked steps appear on the right as you type; Drawing and 3D tabs where the calculation has a layout.
  3. Save the project, then export the Report, Excel with formulas.

Inputs

FieldType / defaultMeaning
Relays (downstream first)
One relay per line: name, kV, CT primary A, plug setting ×In, TMS (0 = auto), curve SI/VI/EI/LTI, max fault current at the relay Atext default Outgoing feeder, 0.415, 400, 1.0, 0.1, SI, 18000 LT incomer, 0.415, 1600, 1.0, 0, SI, 25000 HT transformer feeder, 11, 100, 1.0, 0, SI, 4000
Grading marginnumber (s) default 0.3numerical relays 0.25–0.3 s, electromechanical 0.4 s (typical, IEEE 242 practice)
Lowest TMS of the relaynumber default 0.05
TMS stepnumber default 0.01
Plug setting check (first relay)
Full-load current through the first relaynumber (A) default 320
Pick-up above full loadnumber default 1.25pick-up ≥ 1.1–1.3 × full load (typical)
Plug setting stepnumber (× In) default 0.05

What you get

OutputContent
Results, checks, worked steps, schedules; report, Excel and DXF exports.

Standards applied

Good to know