Plug and TMS for OC / EF relays, operating times, grading margins down the chain and across transformers, time-current curves.
IEC 60255-151 · IEEE 242
| Field | Type / default | Meaning |
|---|---|---|
| Relays (downstream first) | ||
| One relay per line: name, kV, CT primary A, plug setting ×In, TMS (0 = auto), curve SI/VI/EI/LTI, max fault current at the relay A | text default Outgoing feeder, 0.415, 400, 1.0, 0.1, SI, 18000 LT incomer, 0.415, 1600, 1.0, 0, SI, 25000 HT transformer feeder, 11, 100, 1.0, 0, SI, 4000 | |
| Grading margin | number (s) default 0.3 | numerical relays 0.25–0.3 s, electromechanical 0.4 s (typical, IEEE 242 practice) |
| Lowest TMS of the relay | number default 0.05 | |
| TMS step | number default 0.01 | |
| Plug setting check (first relay) | ||
| Full-load current through the first relay | number (A) default 320 | |
| Pick-up above full load | number default 1.25 | pick-up ≥ 1.1–1.3 × full load (typical) |
| Plug setting step | number (× In) default 0.05 | |
| Output | Content |
|---|---|
| Results, checks, worked steps, schedules; report, Excel and DXF exports. | |