USER GUIDE

Insulation & condensate

Dew point, thickness for pipes and surfaces, condensate and drain size.

IS 14164 · ASHRAE

How to use it

  1. Enter the inputs on the left — defaults are a typical case; every field has a note.
  2. Results, checks (PASS / CHECK) and worked steps appear on the right as you type; Drawing and 3D tabs where the calculation has a layout.
  3. Save the project, then export the Report, Excel with formulas.

Inputs

FieldType / defaultMeaning
Code basis
Design regimechoice default india
India — NBCS 2026 (Part F 3.5.7.3.5 duct insulation non-combustible, D3 10.6), International — IS 14164 / ASHRAE physics only
Ambient
Ambient dry bulbnumber (°C) default 35
Ambient RHnumber (%) default 70
Outer surface coefficientnumber (W/m²K) default 9.0still air 8–10; AHU room with air movement 12–15
Surface temperature margin above dew pointnumber (K) default 1.0
Surface
Geometrychoice default pipe
Pipe (round), Duct / flat surface
Fluid / inside temperaturenumber (°C) default 7
Pipe outside diameternumber (mm) default 114.3
Insulationchoice default nitrileDucts (India): NBCS Part F 3.5.7.3.5 non-combustible — glass / mineral wool; PUF not to be used (D3 10.6.4)
Nitrile rubber / elastomeric (k 0.036), XLPE closed-cell (k 0.034), PUF / PIR (k 0.023), Glass wool 48 kg/m³ (k 0.038), Rockwool 100 kg/m³ (k 0.040), EPS (k 0.038)
Cladding emissivity (info)number default 0.9
Length (for heat gain)number (m) default 100
Condensate drain
Cooling capacity of the unitnumber (TR) default 30
Sensible heat rationumber default 0.75
Drain slopenumber (%) default 1.0

What you get

OutputContent
Results, checks, worked steps, schedules; report, Excel and DXF exports.

Standards applied

Good to know