IR corrected to 40 °C, minimum IR, polarisation index and DAR for machines; IEC 60364-6 minimum for installations.
IEEE 43 · IEC 60364-6
| Field | Type / default | Meaning |
|---|---|---|
| Equipment | ||
| What is tested | choice default machine | Motor / generator winding (IEEE 43), LV installation / cable circuit (IEC 60364-6) |
| Rated voltage | number (kV) default 0.415 | |
| Winding | choice default random | Before ~1970 / unknown construction (kV + 1 MΩ), Form-wound, after ~1970 (100 MΩ), Random-wound and form-wound below 1 kV (5 MΩ) |
| Insulation class | choice default F | Class A, Class B, Class F, Class H |
| Circuit | choice default lv | SELV / PELV, Up to 500 V (incl. FELV), Above 500 V |
| Readings | ||
| IR at 30 s (0 = not read) | number (MΩ) default 0 | |
| IR at 1 min | number (MΩ) default 450 | |
| IR at 10 min (0 = not read) | number (MΩ) default 1200 | |
| Winding temperature during the test | number (°C) default 30 | |
| Output | Content |
|---|---|
| Results, checks, worked steps, schedules; report, Excel and DXF exports. | |