USER GUIDE

Insulation resistance & PI

IR corrected to 40 °C, minimum IR, polarisation index and DAR for machines; IEC 60364-6 minimum for installations.

IEEE 43 · IEC 60364-6

How to use it

  1. Enter the inputs on the left — defaults are a typical case; every field has a note.
  2. Results, checks (PASS / CHECK) and worked steps appear on the right as you type; Drawing and 3D tabs where the calculation has a layout.
  3. Save the project, then export the Report, Excel with formulas.

Inputs

FieldType / defaultMeaning
Equipment
What is testedchoice default machine
Motor / generator winding (IEEE 43), LV installation / cable circuit (IEC 60364-6)
Rated voltagenumber (kV) default 0.415
Windingchoice default random
Before ~1970 / unknown construction (kV + 1 MΩ), Form-wound, after ~1970 (100 MΩ), Random-wound and form-wound below 1 kV (5 MΩ)
Insulation classchoice default F
Class A, Class B, Class F, Class H
Circuitchoice default lv
SELV / PELV, Up to 500 V (incl. FELV), Above 500 V
Readings
IR at 30 s (0 = not read)number (MΩ) default 0
IR at 1 minnumber (MΩ) default 450
IR at 10 min (0 = not read)number (MΩ) default 1200
Winding temperature during the testnumber (°C) default 30

What you get

OutputContent
Results, checks, worked steps, schedules; report, Excel and DXF exports.

Standards applied

Good to know