Number, size and speed of passenger lifts from the round trip time, interval and 5-minute handling capacity — with zoning and the lift load for the SLD.
CIBSE Guide D
| Field | Type / default | Meaning |
|---|---|---|
| Building | ||
| Building type | choice default office | Office (single tenant), Office (multi tenant), Hotel, Residential, Hospital (passenger lifts) |
| Floors served above the main lobby | number default 12 | |
| Interfloor height | number (m) default 3.6 | |
| Population from | choice default area | Net area per floor ÷ density, Persons per floor |
| Net usable area per floor | number (m²) default 1200 | |
| Occupancy density (0 = typical for the type) | number (m²/person) default 0 | |
| Persons per floor | number default 100 | |
| Occupancy at the peak (0 = typical) | number (%) default 0 | office ≈ 80 % (absenteeism), typical |
| Express travel to the first served floor (high zone) | number (m) default 0 | |
| Lifts | ||
| Rated load (0 = select) | choice default 0 | Select automatically, 630 kg (8 persons), 800 kg (10 persons), 1000 kg (13 persons), 1275 kg (17 persons), 1600 kg (21 persons), 1800 kg (24 persons), 2000 kg (26 persons) … |
| Rated speed (0 = by travel) | choice default 0 | By travel height (typical), 1 m/s, 1.6 m/s, 2 m/s, 2.5 m/s, 3.5 m/s, 5 m/s, 6 m/s |
| Number of lifts (0 = select) | number default 0 | |
| Average car load at up-peak | number (%) default 80 | 80 % of the rated persons (CIBSE practice) |
| Acceleration | number (m/s²) default 1.0 | typical 0.8–1.2 |
| Door opening time | number (s) default 2.0 | centre opening 1100 mm ≈ 2 s (typical) |
| Door closing time | number (s) default 3.0 | typical |
| Start delay | number (s) default 0.5 | typical |
| Passenger transfer time (each way) | number (s) default 1.2 | typical 1.0–1.2 |
| Targets and load | ||
| Target 5-minute handling capacity (0 = typical for the type) | number (%) default 0 | |
| Target interval (0 = typical for the type) | number (s) default 0 | |
| Counterweight balance | number (%) default 50 | 45–50 % typical |
| Drive + machine efficiency | number (%) default 80 | gearless VVVF ≈ 80–85 % (typical) |
| Supply power factor | number default 0.9 | |
| Patterns, sizes and code checks | ||
| Code regime | choice default nbcs | India — NBCS 2026, International — CIBSE Guide D / ISO 8100 / EN 81 |
| Traffic pattern to check | choice default auto | By building type, Morning up-peak, Down-peak, Mid-day (lunch) two-way, Inter-floor |
| Lunch split in / out / inter-floor | text default 45,45,10 | percent |
| Lift class (sizes) | choice default auto | By building type, Passenger, Residential, Hospital bed / stretcher, Goods, Fire lift, Accessibility lift |
| Drive | choice default auto | By speed (MRL up to 2 m/s), Traction with machine room, Machine-room-less, Hydraulic |
| Output | Content |
|---|---|
| Results, checks, worked steps, schedules; report, Excel and DXF exports. | |