Risk R1 to LPS class, mesh / rolling sphere, down conductors, roof plan DXF.
IEC 62305 · IEC 61643
| Field | Type / default | Meaning |
|---|---|---|
| Structure | ||
| Length | number (m) default 60 | |
| Width | number (m) default 25 | |
| Height to roof / parapet | number (m) default 30 | |
| Highest protrusion (lift MR, OHT, mast) above roof | number (m) default 4 | |
| Location factor Cd | choice default 0.5 | Surrounded by taller objects (0.25), Surrounded by objects of same height or smaller (0.5), Isolated — no other objects nearby (1), Isolated on a hilltop or knoll (2) |
| Use of the structure | choice default res | Residential / apartments, Office / commercial, Hospital / nursing home (difficult evacuation), School / civic building, Hotel / hostel, Industrial / warehouse, Mall / entertainment / stadium (>1000 persons), Museum / place of worship / heritage … |
| Persons in the structure (nz) | number default 400 | |
| Construction | choice default rcc | RCC frame (rebar can serve as natural down conductor), Steel frame (natural down conductor), Load-bearing masonry / timber |
| Roof | choice default flat | Flat RCC with parapet, Metal sheet (continuous, ≥ 0.5 mm — natural air termination), Pitched tiles / sheet on purlins |
| Lightning density | ||
| Place (NBCS 2026 / NBC 2016 cl. 11.8 thunderstorm days → Ng = 0.1 Td) | choice default delhi | Agra — Td 24, Ahmadnagar — Td 10, Ahmedabad — Td 11, Ajmer — Td 26, Akola — Td 20, Alibag — Td 12, Aligarh — Td 30, Allahabad — Td 51 … |
| Ground flash density Ng | number (/km²·yr) | Leave blank to use 0.1 × Td of the city; use the IMD / lightning-detection-network value when you have it |
| Risk factors (IEC 62305-2 Annex B/C) | ||
| Fire risk rf | choice default ord | Explosion (1), High — fire load > 800 MJ/m² (0.1), Ordinary — 400–800 MJ/m² (0.01), Low — < 400 MJ/m² (0.001), None (0) |
| Fire provisions rp | choice default 0.5 | None (1), Extinguishers, hydrants, manual alarm, fire brigade < 10 min (0.5), Automatic sprinklers / detection + alarm (0.2) |
| Floor surface (touch/step) rt | choice default 1e-3 | Concrete / agricultural (10⁻²), Marble, ceramic tiles (10⁻³), Gravel, carpet (10⁻⁴), Asphalt, linoleum, wood (10⁻⁵) |
| Touch-voltage measures PTA | choice default 1 | None (1), Warning notices (0.1), Insulation of exposed down conductors / equipotential soil (0.01) |
| Environment of incoming lines CE | choice default 0.1 | Rural (1), Suburban (0.5), Urban (0.1), Urban with buildings > 20 m (0.01) |
| Power line | choice default buried | Overhead LV/HV line, Buried cable, None (own DG only) |
| Power line length (from last pole / transformer) | number (m) default 500 | |
| HV/LV transformer at the structure (CT = 0.2) | yes / no default True | |
| Telecom / data line | choice default buried | Overhead, Buried, None / fibre only |
| Telecom line length | number (m) default 500 | |
| Coordinated SPD protection on lines (PEB) | choice default auto | Auto — SPD level to match the LPS class, No SPDs, SPD for LPL III/IV (0.05), SPD for LPL II (0.02), SPD for LPL I (0.01) |
| Tolerable risk RT | number (/yr) default 1e-05 | |
| Tolerable frequency of damage FT (internal systems, IEC 62305-2 : 2024) | number (/yr) default 0.1 | indicative check of the frequency of damage F of internal systems (set by the owner; 0.1 /yr typical) |
| LPS design | ||
| Code edition | choice default nbcs2026 | NBCS 2026 (SP 7:2026) Part D Sec 2 — IEC 62305 : 2024, NBC 2016 Part 8 Sec 2 — IS/IEC 62305 : 2010 (superseded), IEC 62305 (projects outside India) |
| Class of LPS | choice default auto | Auto — lowest class that brings R1 ≤ RT, I (LPL I), II (LPL II), III (LPL III), IV (LPL IV) |
| Air-termination method | choice default mesh | Mesh on the roof + rods at corners / protrusions, Vertical rods (rolling sphere + protective angle), Mesh + rods at every node (belt and braces) |
| Air-termination rod height | number (m) default 1.0 | |
| Conductor material | choice default gi | Hot-dip galvanised steel strip / rod, Copper, Aluminium (roof only) |
| Soil resistivity ρ | number (Ω·m) default 100 | |
| Target earth resistance | number (Ω) default 10 | |
| Output | Content |
|---|---|
| Results, checks, worked steps, schedules; report, Excel and DXF exports. | |