Bus and motor terminal voltage while a large motor starts — DOL, star-delta, auto-transformer, soft starter, VFD.
IEEE 3002.7
| Field | Type / default | Meaning |
|---|---|---|
| Supply | ||
| Transformer | number (kVA) default 1000 | |
| Transformer impedance | number (%) default 5.0 | |
| Transformer X/R | number default 6 | |
| Source fault level at the HV side | number (MVA) default 250 | |
| LV voltage | number (V) default 415 | |
| Motor | ||
| Motor | number (kW) default 160 | |
| Full-load pf | number default 0.87 | |
| Efficiency | number default 0.95 | |
| Locked-rotor current | number (× FLC) default 6.5 | |
| Starting power factor | number default 0.3 | |
| Starter | choice default dol | Direct-on-line, Star-delta, Auto-transformer 65 % tap, Auto-transformer 80 % tap, Soft starter (current limit), VFD |
| Soft-starter current limit | number (× FLC) default 3.0 | |
| Cable resistance transformer → motor (0 = none) | number (mΩ) default 8 | |
| Cable reactance | number (mΩ) default 4 | |
| Allowed dip at the LV bus | number (%) default 10 | other loads on the bus: 10 % (typical) |
| Allowed dip at the motor | number (%) default 15 | ≥ 80–85 % voltage at the terminals for a reliable start (typical) |
| Output | Content |
|---|---|
| Results, checks, worked steps, schedules; report, Excel and DXF exports. | |