USER GUIDE

Voltage dip on motor starting

Bus and motor terminal voltage while a large motor starts — DOL, star-delta, auto-transformer, soft starter, VFD.

IEEE 3002.7

How to use it

  1. Enter the inputs on the left — defaults are a typical case; every field has a note.
  2. Results, checks (PASS / CHECK) and worked steps appear on the right as you type; Drawing and 3D tabs where the calculation has a layout.
  3. Save the project, then export the Report, Excel with formulas.

Inputs

FieldType / defaultMeaning
Supply
Transformernumber (kVA) default 1000
Transformer impedancenumber (%) default 5.0
Transformer X/Rnumber default 6
Source fault level at the HV sidenumber (MVA) default 250
LV voltagenumber (V) default 415
Motor
Motornumber (kW) default 160
Full-load pfnumber default 0.87
Efficiencynumber default 0.95
Locked-rotor currentnumber (× FLC) default 6.5
Starting power factornumber default 0.3
Starterchoice default dol
Direct-on-line, Star-delta, Auto-transformer 65 % tap, Auto-transformer 80 % tap, Soft starter (current limit), VFD
Soft-starter current limitnumber (× FLC) default 3.0
Cable resistance transformer → motor (0 = none)number (mΩ) default 8
Cable reactancenumber (mΩ) default 4
Allowed dip at the LV busnumber (%) default 10other loads on the bus: 10 % (typical)
Allowed dip at the motornumber (%) default 15≥ 80–85 % voltage at the terminals for a reliable start (typical)