USER GUIDE

Neutral earthing resistor

NER ohms, energy and time rating for the earth-fault limit; zig-zag earthing transformer short-time kVA.

IEEE 142 · IEEE 32

How to use it

  1. Enter the inputs on the left — defaults are a typical case; every field has a note.
  2. Results, checks (PASS / CHECK) and worked steps appear on the right as you type; Drawing and 3D tabs where the calculation has a layout.
  3. Save the project, then export the Report, Excel with formulas.

Inputs

FieldType / defaultMeaning
System
System line voltagenumber (kV) default 11
Earth-fault current limitnumber (A) default 300low-resistance earthing 100–1000 A; high-resistance ≤ 10 A (typical)
Time ratingchoice default 10
10 s, 30 s, 60 s, 10 min, extended / continuous
System charging current 3·Ic0 (0 = not known)number (A) default 0
Neutral sourcechoice default star
Star neutral of a transformer / generator, Zig-zag earthing transformer (delta system)
Allowed resistor temperature risenumber (K) default 760short-time rated stainless-steel grids (IEEE 32 practice, typical)

What you get

OutputContent
Results, checks, worked steps, schedules; report, Excel and DXF exports.