Pad / inertia-base size and mass ratio, spring or rubber isolator by static deflection for the target efficiency, bearing pressure on slab or soil.
ASHRAE Applications · IS 2974
| Field | Type / default | Meaning |
|---|---|---|
| Equipment | ||
| Equipment | choice default pump | Base-mounted pump, Chiller, DG set, AHU / fan, Cooling tower, Compressor / reciprocating |
| Operating weight | number (kg) default 1200 | |
| Lowest disturbing speed | number (rpm) default 1450 | |
| Base length | number (m) default 1.8 | |
| Base width | number (m) default 0.9 | |
| Location | choice default slab | On grade (soil), On a floor slab, Roof / upper floor (long span) |
| Soil bearing capacity (on grade) | number (kN/m²) default 150 | |
| Slab allowable load | number (kN/m²) default 10 | |
| Base and isolation | ||
| Base type | choice default auto | Auto by equipment / location, Plain concrete pad (housekeeping), Concrete inertia base on springs, Steel rail / frame on isolators |
| Inertia mass ratio (base : equipment) | number default 0 | 0 = ASHRAE typical: pumps 1.5–2.5, compressors 3–5, chillers 1, fans 1–2 |
| Target isolation efficiency | number (%) default 90 | |
| Isolator | choice default auto | Auto by deflection, Rubber / neoprene pad (≤ 8 mm), Open spring (25 mm), Spring (50 mm), Spring (75 mm) |
| Isolators | number default 4 | |
| Pad / base thickness | number (mm) default 150 | |
| Impact allowance (bearing check) | choice default auto | NBCS 2026 Part C Sec 1 cl. 3.6.1 / 3.6.2.1 (not less than 20 %) Auto — NBCS C1 3.6.1: 20 % motor units, 50 % DG / reciprocating, 20 % — light machinery, shaft or motor units, 50 % — reciprocating machinery or power units |
| Output | Content |
|---|---|
| Results, checks, worked steps, schedules; report, Excel and DXF exports. | |