USER GUIDE
Power distribution design
Sources (grid, transformers, DG / gas gensets, PV, battery) → fault levels for every scenario → cable schedule sized in one loop for ampacity, VD, breaker and short circuit → HT cables → SLD DXF.
IEC 60909 · IS 732 / IEC 60364 · IEC 60502
- IEC 60909-0:2016 — Short-circuit currents in three-phase a.c. systems — Calculation of currents
Impedance method, voltage factor c (1.05 / 1.10 max, 0.95 min), peak factor κ = 1.02 + 0.98·e^(−3R/X), Ik" = c·Un/(√3·Zk)
- IEC 60909-0:2016 — Short-circuit currents in three-phase AC systems — calculation of currents
Inverter-based sources as current sources; motor contribution; scenarios
- IEC 60364-4-43:2008 — Protection against overcurrent
Ib ≤ In ≤ Iz, adiabatic cable withstand I²t ≤ k²S² with k = 143 (Cu XLPE), 115 (Cu PVC), 94 (Al XLPE), 76 (Al PVC)
- IEC 60364-5-52:2009 — Low-voltage electrical installations — Selection and erection of wiring systems
Current-carrying capacity, derating (temperature, grouping, installation method), voltage drop ≤ 3–5 %
- IEC 60287-1-1 / 60287-2-1 — Electric cables — Calculation of the current rating
Temperature correction √((θmax−θamb)/(θmax−θref)) and depth-of-laying correction
- IEC 60949 — Calculation of thermally permissible short-circuit currents
Adiabatic and non-adiabatic cable withstand
- IEC 60947-2:2016 / IS/IEC 60947-2 — Low-voltage switchgear — Circuit-breakers
ACB/MCCB ratings Icu, Ics, Icw; release characteristics (L-S-I-G); selectivity definitions
- IEC 60898-1:2015 / IS/IEC 60898-1 — Circuit-breakers for overcurrent protection for household and similar installations (MCB)
B/C/D tripping bands (C: 5–10 × In), thermal tripping 1.13/1.45 × In
- IEC 61439-1/2:2020 / IS/IEC 61439 — Low-voltage switchgear and controlgear assemblies
Panel construction (TTA/PTTA), busbar short-time withstand (Icw 1 s), temperature rise, IP rating
- IEC 60076 (series) — Power transformers
Impedance, ratings and losses used for the fault study source model
- IEC 60502-2 — Power cables with extruded insulation — 6 kV to 30 kV
HT cable construction and current ratings (international regime)
- IEEE 141-1993 (Red Book) — Recommended practice for electric power distribution for industrial plants
Motor starting voltage dip (≥ 80–85 % at terminals), phase unbalance practice
- IS 732:2019 — Code of practice for electrical wiring installations
Voltage-drop limits, cable selection, protection coordination (adopts IEC 60364)
- IS 1554 (Part 1):1988 — PVC insulated (heavy duty) electric cables up to 1100 V
Cable ratings, resistance and reactance data
- IS 7098 (Part 1):1988 — Cross-linked polyethylene insulated PVC sheathed cables up to 1100 V
XLPE cable ratings (90 °C), resistance and reactance data
- IS 3961 (Part 2):1967 (reaffirmed) — Recommended current ratings for cables — PVC insulated and PVC sheathed heavy duty cables
Rating factors for ambient / ground temperature, soil thermal resistivity, depth of laying and grouping; installation categories (in air, in ground, in ducts)
- IS 13234 (Part 1):2022 / IEC 60909-0 — Short-circuit currents in three-phase a.c. systems
Indian adoption of IEC 60909
- IS 2026 (Part 1):2011 / IEC 60076-1 — Power transformers
Impedance voltage, ratings, Dyn11 vector group
- CPWD General Specifications for Electrical Works (Part I Internal, Part IV Substation) — CPWD specifications
Voltage-drop cascade limits, cable/wiring practice, panel and metering requirements
- NBCS 2026 (SP 7:2026) Part D Sec 2 — National Building Construction Standards — Electrical and allied installations
Load assessment and diversity, circuits, cables (4-core), earthing, lightning protection, standby supply for fire & life-safety loads