USER GUIDE

Pole transverse load & foundation

Wind on pole, luminaire and conductors plus deviation pull → ground moment, pole check and planting depth.

IS 875-3 · IS 802

How to use it

  1. Enter the inputs on the left — defaults are a typical case; every field has a note.
  2. Results, checks (PASS / CHECK) and worked steps appear on the right as you type; Drawing and 3D tabs where the calculation has a layout.
  3. Save the project, then export the Report, Excel with formulas.

Inputs

FieldType / defaultMeaning
Pole
Height above groundnumber (m) default 9
Top diameternumber (mm) default 90
Bottom diameternumber (mm) default 160
Force coefficient of the polenumber default 0.8round tubular 0.7–0.8, octagonal 1.2 (typical)
Pole working load (applied 0.6 m below top)number (kN) default 2.0from the pole maker / IS 2713 designation
Luminaire + bracket projected areanumber (m²) default 0.25
Conductors / cables
Number of overhead conductors (0 = underground feed)number default 0
Conductor diameternumber (mm) default 9.0
Wind spannumber (m) default 35
Conductor height above groundnumber (m) default 7.5
Conductor tension (each)number (kN) default 2.0
Line deviation anglenumber (°) default 0
Wind and soil
Basic wind speedchoice default 44
33 m/s, 39 m/s, 44 m/s, 47 m/s, 50 m/s, 55 m/s
Terrain / height factor k2number default 1.0IS 875 Part 3 Table 2 for the height and terrain category
Kd · Ka · Kcnumber default 0.9directionality × area averaging × combination (IS 875-3); 1.0 = conservative
Soil friction anglenumber (°) default 30
Soil unit weightnumber (kN/m³) default 18
Foundation (concrete) width / diameternumber (m) default 0.6
Factor of safety on the soilnumber default 2.0