USER GUIDE

Psychrometric processes

State points, mixing, coil with ADP and bypass, energy recovery.

ASHRAE Fundamentals

How to use it

  1. Enter the inputs on the left — defaults are a typical case; every field has a note.
  2. Results, checks (PASS / CHECK) and worked steps appear on the right as you type; Drawing and 3D tabs where the calculation has a layout.
  3. Save the project, then export the Report, Excel with formulas.

Inputs

FieldType / defaultMeaning
Process
Processchoice default state
State point, Mixing of two streams, Sensible heating / cooling, Cooling & dehumidifying coil, Humidification, Energy recovery (OA ↔ EA)
Altitudenumber (ft) default 0site pressure for the state points; the 1.08 / 0.68 / 4.5 load constants are scaled by p / 14.696
Code edition (room-state check)choice default nbcs2026
NBCS 2026 Part D Sec 3 cl. 3.6 — 18–26 °C, RH 30–70 %, NBC 2016 Part 8 Sec 3 cl. 6.2 — 18–26 °C (no RH band)
Room-state check — NBCS 2026 D3 cl. 3.6 (18–26 °C, RH 30–70 %)choice default auto
Return / room stream (mixing, ERV), Also the state point / leaving state as a room, No code check
Air flow (stream 1 / supply)number (cfm) default 10000
Stream 1 / entering
Dry bulbnumber (°F) default 95
Second propertychoice default wb
Wet bulb °F, Relative humidity (0–1), Dew point °F
Valuenumber default 78
Stream 2 / target
Air flow (stream 2 / return / exhaust)number (cfm) default 8000
Dry bulbnumber (°F) default 75
Second propertychoice default rh
Wet bulb °F, Relative humidity (0–1), Dew point °F
Valuenumber default 0.5
Apparatus dew pointnumber (°F) default 52
Bypass factornumber default 0.1
Humidifierchoice default steam
Steam (isothermal), Adiabatic (evaporative, constant WB)
Target RH (0–1) or effectiveness (adiabatic)number default 0.5
Sensible effectivenessnumber default 0.7
Latent effectiveness (0 = sensible wheel)number default 0.65

What you get

OutputContent
Results, checks, worked steps, schedules; report, Excel and DXF exports.