USER GUIDE

Clean, server, DG & TX rooms

HEPA count by ISO class, server TR, DG combustion air and louvres.

ISO 14644 · IS 10028

How to use it

  1. Enter the inputs on the left — defaults are a typical case; every field has a note.
  2. Results, checks (PASS / CHECK) and worked steps appear on the right as you type; Drawing and 3D tabs where the calculation has a layout.
  3. Save the project, then export the Report, Excel with formulas.

Inputs

FieldType / defaultMeaning
Room
Room typechoice default server
Clean room (ISO 14644), Server / data room, DG set room, Transformer room
Floor areanumber (m²) default 60
Clear heightnumber (m) default 3.5
Room design temperaturenumber (°C) default 24
Ambient (for ventilation rooms)number (°C) default 43
Max room temperature (ventilated rooms)number (°C) default 50
Envelope + lighting gainnumber (W) default 3000
Clean room
ISO classchoice default 7
ISO 4 — U — 300–540 ACH (NBCS D3 Table 31), ISO 5 — U/N/M — 240–480 ACH (NBCS D3 Table 31), ISO 6 — N/M — 150–240 ACH (NBCS D3 Table 31), ISO 7 — N/M — 60–90 ACH (NBCS D3 Table 31), ISO 8 — N/M — 5–48 ACH (NBCS D3 Table 31), ISO 9 — 5–15 ACH (practice; not in NBCS Table 31)
Air changes (0 = class default)number (ACH) default 0
Occupantsnumber default 6
Process / equipment heatnumber (kW) default 5
Room pressurisationnumber (Pa) default 15
Leakage / exhaust make-up (% of supply)number (%) default 10
Fan / filter heat gain (% of sensible)number (%) default 15
Server room
IT load (UPS output)number (kW) default 40
UPS / PDU losses in roomnumber (%) default 6
Supply–return ΔTnumber (K) default 11
Cooling redundancychoice default n1
N, N+1, 2N
Unit size (0 = auto)number (TR) default 0
DG / transformer
Ratingnumber (kVA) default 1000
Heat rejected to room (DG: radiator + engine + alternator)number (%) default 12typical 8–15 % of engine rating for radiator-in-room sets; 4–6 % for remote radiators
Combustion airnumber (m³/h per kVA) default 5.1≈ 3 cfm/kVA (5.1 m³/h per kVA) typical
Transformer losses (no-load + load) at full loadnumber (%) default 1.2dry-type 1.2–1.8 %, oil-filled 0.8–1.2 % (IS 1180 level 2 ~ 1 %)
Loadingnumber (%) default 80
Air velocity through louvresnumber (m/s) default 2.5
Louvre free areanumber (%) default 50

What you get

OutputContent
Results, checks, worked steps, schedules; report, Excel and DXF exports.