Fp per IS 1893 Part 1 cl. 7.13 or ASCE 7-16 ch. 13, overturning, tension and shear per anchor, restrained isolators / snubbers for isolated plant.
IS 1893 · ASCE 7-16
| Field | Type / default | Meaning |
|---|---|---|
| Code and site | ||
| Code | choice default is | IS 1893 (Part 1):2016 cl. 7.13 — Indian, ASCE 7-16 ch. 13 — International |
| Seismic zone (IS 1893) | choice default IV | II — Z 0.10, III — Z 0.16, IV — Z 0.24, V — Z 0.36 |
| SDS (ASCE 7) | number default 0.5 | |
| Importance factor Ip | choice default 1.5 | 1.0 — ordinary, 1.5 — life-safety / essential (fire pumps, hospitals, DG, emergency power) |
| Building height | number (m) default 30 | |
| Height of the equipment floor above base | number (m) default 30 | |
| Equipment | ||
| Equipment | choice default chiller | Chiller / cooling tower / rigid plant (ap 1.0, Rp 2.5), Pump / DG / transformer (ap 1.0, Rp 2.5), AHU / fan on isolators (ap 2.5, Rp 2.5), Electrical panel / MCC (ap 1.0, Rp 2.5), Tank / vessel on legs (ap 2.5, Rp 2.5), Piping / duct / tray (ap 2.5, Rp 6 – 12) |
| Operating weight | number (kg) default 5000 | |
| Height of the centre of gravity | number (m) default 1.2 | |
| Anchor spacing across (short direction) | number (m) default 1.2 | |
| Anchor spacing along | number (m) default 2.4 | |
| Anchors | number default 4 | |
| On vibration isolators (restrained springs / snubbers) | yes / no default False | |
| Concrete | choice default M25 | M20, M25, M30 |
| Output | Content |
|---|---|
| Results, checks, worked steps, schedules; report, Excel and DXF exports. | |