USER GUIDE

Septic tank & soak pit

Tank L × B × D by IS 2470, soak pit from percolation rate, grease trap.

IS 2470

How to use it

  1. Enter the inputs on the left — defaults are a typical case; every field has a note.
  2. Results, checks (PASS / CHECK) and worked steps appear on the right as you type; Drawing and 3D tabs where the calculation has a layout.
  3. Save the project, then export the Report, Excel with formulas.

Inputs

FieldType / defaultMeaning
Septic tank
Number of users (contributory population)number default 50NBCS E2 4.5.14.5.2: septic tanks only up to 300 — above that a PSTP (IS 18797) / STP
Sewage flow per user (WC only 40 L; all wastes 90–120 L)number (L/day) default 90
Detention timenumber (h) default 24
Desludging intervalnumber (years) default 2
Liquid depthnumber (m) default 1.5
Operating (coldest-month sewage) temperaturenumber (°C) default 20NBCS E2 4.5.14.5.2: capacity + 100 % at 10 °C vs 20 °C (activity halves per 10 °C)
Soak pit / trench
Percolation rate (time for 25 mm drop)number (min) default 15IS 2470-2: < 5 min sandy; 5–15 loam; 15–30 silty; > 30 unsuitable for soak pits
Disposalchoice default pit
Soak pit, Dispersion trench
Soak pit diameternumber (m) default 1.5
Grease trap
Meals per peak hour (0 = use fixtures)number default 150
Kitchen sinks / dishwashers connectednumber default 4
Retention timenumber (min) default 30

What you get

OutputContent
Results, checks, worked steps, schedules; report, Excel and DXF exports.

Standards applied

Good to know