Load per metre of trays, ducts and pipes → cross-member (angle / strut / channel / beam) by bending and deflection, hanger rod, anchor bolt with tension–shear interaction; trapeze, bracket or goal-post.
IS 800 · IEC 61537 · SMACNA · ETAG 001
| Field | Type / default | Meaning |
|---|---|---|
| Service | ||
| Service | choice default tray | Cable tray / ladder (loaded), Sheet-metal duct, Pipe (water-filled, insulated), Custom load |
| Tray | choice default ladder_600 | ladder 300 mm — 22 kg/m, ladder 450 mm — 35 kg/m, ladder 600 mm — 48 kg/m, ladder 750 mm — 62 kg/m, ladder 900 mm — 78 kg/m, perf 150 mm — 8 kg/m, perf 300 mm — 18 kg/m, perf 450 mm — 28 kg/m … |
| Trays on the support (tiers) | number default 2 | |
| Duct width | number (mm) default 800 | |
| Duct height | number (mm) default 400 | |
| Sheet thickness | number (mm) default 0.8 | |
| Insulated + cladding | yes / no default True | |
| Pipe NB | choice default 100 | 25 NB — 3.1 + 0.6 kg/m, 32 NB — 4.1 + 1.0 kg/m, 40 NB — 4.8 + 1.3 kg/m, 50 NB — 6.2 + 2.2 kg/m, 65 NB — 8.6 + 3.6 kg/m, 80 NB — 10.3 + 5.0 kg/m, 100 NB — 14.5 + 8.7 kg/m, 125 NB — 18.0 + 13.5 kg/m … |
| Pipes on the support | number default 2 | |
| Insulated | yes / no default True | |
| Load per metre run | number (kg/m) default 60 | |
| Extra allowance (person / future) | number (kg) default 90 | IEC 61537 / SMACNA: a 90 kg point load for a person on trays, or future services |
| Support | ||
| Arrangement | choice default trapeze | Trapeze on two hanger rods, Wall / column cantilever bracket, Floor stand / goal-post |
| Support spacing (along the run) | number (m) default 1.5 | |
| Cross-member length (between rods / cantilever) | number (mm) default 900 | |
| Cross-member | choice default auto | Auto — lightest that passes, ISA 40x40x5 — 3.0 kg/m, Z 1.55 cm³, ISA 50x50x6 — 4.5 kg/m, Z 3.0 cm³, ISA 65x65x6 — 5.8 kg/m, Z 5.1 cm³, ISA 75x75x6 — 6.8 kg/m, Z 7.0 cm³, ISA 100x100x8 — 12.1 kg/m, Z 17.0 cm³, Strut 41x21x2.5 — 1.3 kg/m, Z 0.9 cm³, Strut 41x41x2.5 — 2.3 kg/m, Z 3.0 cm³ … |
| Steel design method | choice default lsm | IS 800:2007 limit state — γm0 1.10, load factor 1.5 (NBCS Part C Sec 6A), Allowable stress 0.66 fy — IS 800:1984 (withdrawn) / AISC ASD, legacy |
| Load factor γf (dead + imposed) | number default 1.5 | IS 800:2007 Table 4: 1.5 for DL + IL |
| Steel yield | number (MPa) default 250 | |
| Deflection limit L/ | number default 240 | |
| Hanger rod | choice default auto | Auto, M10 (4.6), M12, M16, M20 |
| Anchors per rod / bracket | number default 1 | |
| Concrete grade | choice default M25 | M20 (× 0.85), M25, M30 (× 1.1) |
| Safety factor on anchor loads | number default 1.5 | |
| Output | Content |
|---|---|
| Results, checks, worked steps, schedules; report, Excel and DXF exports. | |