Module count for N / N+1 / 2N, battery Ah, charger, room heat and H₂ venting.
IEEE 485 · IEC 62040
| Field | Type / default | Meaning |
|---|---|---|
| Load | ||
| Critical load | number (kW) default 80 | |
| Load power factor | number default 0.9 | |
| Future growth | number (%) default 20 | |
| UPS output rated power factor | number default 0.9 | modern double-conversion UPS: 0.9–1.0 (kW = kVA × pf) |
| Max loading of UPS | number (%) default 80 | |
| Redundancy | choice default n1 | N (single), N+1 (parallel), 2N (dual bus) |
| Modules in parallel for N (N+1 adds one) | number default 2 | |
| Battery | ||
| Backup time | number (min) default 30 | |
| Battery type | choice default vrla | VRLA (lead-acid, 12 V blocks), Li-ion (LFP) |
| DC bus nominal voltage | number (V) default 384 | typical 384 / 480 / 528 V for 3-phase UPS (32 / 40 / 44 blocks of 12 V) |
| End-of-discharge voltage per cell | number (V) default 1.75 | |
| Inverter efficiency | number default 0.95 | |
| Ageing factor | number default 1.25 | IEEE 485: 1.25 (replace at 80 % capacity) |
| Temperature factor | number default 1.0 | 1.0 at 25 °C; 1.1 at 20 °C; 1.2 at 15 °C (VRLA) |
| Design margin | number default 1.1 | |
| Peukert exponent (blank = by type) | number | VRLA at high rates ≈ 1.3; Li-ion ≈ 1.05 |
| Block capacity (0 = auto) | number (Ah) default 0 | |
| Installation | ||
| UPS overall efficiency | number default 0.94 | |
| Input power factor | number default 0.99 | |
| Input voltage (3-phase) | number (V) default 415 | |
| Recharge to 90 % within | number (h) default 10 | |
| UPS output | choice default 3 | Three-phase (4-pole CB, NBCS 10.3.2 e), Single-phase 230 V (double-pole CB) |
| NBCS 2026 D2 10.3.2 / 10.3.4 provisions | ||
| Isolation transformer on the UPS output (10.3.2 a, optional) | yes / no default False | |
| Dedicated UPS neutral earth pits, interconnected below soil (10.3.2 b) | yes / no default True | |
| UPS room ventilated / air-conditioned (10.3.2 d) | yes / no default True | |
| Battery space well ventilated (10.3.4 d) | yes / no default True | |
| Acid / alkali-resistant battery-room floor (10.3.4 e) | yes / no default True | |
| UPS-fed circuits marked at the DBs (10.3.4 a) | yes / no default True | |
| Output | Content |
|---|---|
| Results, checks, worked steps, schedules; report, Excel and DXF exports. | |