BMS architecture & panel SLDs

From the same equipment schedule as the I/O summary: every unit expanded with its tag (floor ranges such as G–3 spread the units), hardwired points packed into DDC panels by building → floor → zone up to the controller capacity less spare, I/O modules per type with spare channels, MS/TP trunks on network controllers (or BACnet/IP floor switches), third-party integrations, head-end servers and workstations. Drawings: the four-level system architecture, floor-wise panel SLD sheets with incomer, DIN-rail modules and field-cable call-outs, and the I/O card layout of every panel; Excel: panel allocation, BOM, every channel, cable schedule with lengths.

ISO 16484 (Parts 1–6)ASHRAE Standard 135 / ISO 16484-5 (BACnet)ASHRAE Guideline 36ASHRAE Guideline 13Modbus Application Protocol V1.1b3 / Serial Line V1.02IEC 61131-2 / -3
What goes in, what comes out

You enter

  • Equipment schedule with building / floor / zone
  • Controller and module sizes, trunk limits
  • Cable length rules

You get

  • System architecture DXF
  • Floor-wise panel SLD sheets + I/O card layouts (DXF)
  • Panels, BOM, I/O channels, cable schedule (Excel)

What it does

Panel allocationFloor + zone (default), per system, or fill — split when a panel is full; RTU panels for electrical SCADA assets.
Controllers and modulesPoints per controller, controllers per panel, DI / DO / AI / AO module sizes; spare per type kept in every panel.
System architectureHead-end, core switch, network controllers, MS/TP trunks or floor switches, panels per floor band, integrations — SVG and DXF.
Panel SLD sheetsOne sheet per floor: MCB, SPD, PSU, controllers and modules with used / spare channels, network in / out, field-cable bundles per equipment.
I/O card layoutEvery channel: slot, module, address, equipment tag, point, field device, signal and cable type.
Cable scheduleOne cable per point plus panel power, trunk and Ethernet links with estimated lengths.

Checks it performs

PASS / CHECKEvery hardwired point on a module channel
PASS / CHECKSpare ≥ policy % per type in every panel
PASS / CHECKChannels within the controller capacity
PASS / CHECKPanels per MS/TP trunk and trunks per NLC within limits
PASS / CHECKEvery soft-integrated system on a gateway / NLC port

Sample report

How to use it

  1. Set the scope (BMS, electrical SCADA or both), the template profile (Detailed or Generic), the spare % and the code regime.
  2. Build the equipment schedule: one row per asset type with quantity, building, floor and zone — or import the Excel schedule.
  3. Read the live I/O summary, the field-device schedule and the points requiring confirmation; adjust quantities or templates.
  4. Fill the DBR front matter (project, client, consultant, contractor, revision) and export the I/O Summary (Excel), the Design Basis Report (Word) and the report.
  5. Panels & architecture tab: choose the panel allocation (building → floor → zone, per system or fill), points per controller, controllers per panel, module sizes, panels per MS/TP trunk and trunks per NLC; floor ranges like G–3 spread the units. Read the system architecture, the floor-wise panel SLD sheets and each panel's I/O card layout, then export the Architecture & SLD (DXF) and Panels & cables (Excel: allocation, BOM, every channel, cable schedule with lengths).

What you enter

  • Equipment schedule — asset type, tag, qty, building / floor / zone, note
  • Policies — scope, profile, spare %, regime, protocols, controller sizing
  • DBR data — titles, parties, revision, background, references

What you get

  • I/O Summary (Excel) — R1 layout: sub-rows per point, Monitor / Control / Alarm, remarks, field-device columns, spare, notes
  • Design Basis Report (Word) — 17 sections with every table filled from the schedule
  • Report — HTML summary with the shared stylesheet

Also searched as

BMS architecture drawing; BMS panel SLD; BMS system architecture DXF. The same calculation, the same clauses — one tool for automation / elv design under the Indian codes (NBC, IS, CPWD) or the international ones (IEC, NFPA, ASHRAE, EN).

Standards applied

ReferenceTitleUsed for
ISO 16484 (Parts 1–6)Building automation and control systemsSystem design, hardware, functions, data communication (BACnet) for the BMS
ASHRAE Standard 135 / ISO 16484-5 (BACnet)Data communication protocol for building automation and control networksBackbone and controller network protocol
ASHRAE Guideline 36High-performance sequences of operation for HVAC systemsControl narratives for AHUs, plants and zones
ASHRAE Guideline 13Specifying building automation systemsPoint classification, spare capacity, graphics and alarm philosophy
Modbus Application Protocol V1.1b3 / Serial Line V1.02Modbus protocol specificationsThird-party integration of drives, meters, chillers, UPS and plant PLCs
IEC 61131-2 / -3Programmable controllers — equipment requirements and programming languagesPLC panels for tunnel / car-park ventilation, lighting and electrical SCADA
IEC 61439-1/2:2020 / IS/IEC 61439Low-voltage switchgear and controlgear assembliesPanel construction (TTA/PTTA), busbar short-time withstand (Icw 1 s), temperature rise, IP rating
IEC 62443 (series)Security for industrial automation and control systemsZones and conduits, user management, hardening of the automation network
IEC 61850Communication networks and systems for power utility automationSubstation SCADA — relays, IEDs, GOOSE / MMS
IEC 60870-5-104Telecontrol equipment and systems — network accessElectrical SCADA telecontrol over TCP/IP
NBCS 2026 (SP 7:2026) Part D Sec 2National Building Construction Standards — Electrical and allied installationsLoad assessment and diversity, circuits, cables (4-core), earthing, lightning protection, standby supply for fire & life-safety loads
NBCS 2026 (SP 7:2026) Part D Sec 3National Building Construction Standards — Air conditioning, heating and mechanical ventilationDesign conditions (Table 3), ventilation (Table 7), duct velocities (Table 18), clean rooms (Table 31), automation
NBCS 2026 (SP 7:2026) Part D Sec 5National Building Construction Standards — Lifts, escalators, moving walks and power-driven parkingLift traffic, fire-fighting lifts, controls
NBCS 2026 (SP 7:2026) Part D Sec 6National Building Construction Standards — Information and communication enabled installationsStructured cabling, Wi-Fi (IEEE 802.11ax/be), ICT spaces
NBCS 2026 (SP 7:2026) Part FNational Building Construction Standards — Fire and life safetyMeans of egress (Tables 2–4, cl. 4.4.2), staircase / lobby / lift-well pressurisation (cl. 4.4.2.5, Table 5), emergency lighting (cl. 3.5.6), fire-fighting installations by occupancy (Tables 7A–7J), demand, pumps and duration (Tables 7K / 7M), mains (Table 8), hydrant pressure 3.5–7 bar (cl. 5.1.1 f), sprinklers (cl. 5.1.3), gaseous suppression (cl. 5.1.6 / 5.1.9)
CEA (Measures relating to Safety and Electric Supply) Regulations, 2023Central Electricity Authority safety regulationsStatutory safety requirements for installations
IS 732:2019Code of practice for electrical wiring installationsVoltage-drop limits, cable selection, protection coordination (adopts IEC 60364)
IS 3043:2018Code of practice for earthingEarth bus, strip sizing, earthing of panels (future earthing tool)
CPWD General Specifications for Electrical Works Part VI (BMS)Building management system specificationPanels, cabling, controllers and head end for CPWD works

Frequently asked

How do I use the BMS architecture & panel SLDs calculator?

Set the scope (BMS, electrical SCADA or both), the template profile (Detailed or Generic), the spare % and the code regime. Build the equipment schedule: one row per asset type with quantity, building, floor and zone — or import the Excel schedule. Read the live I/O summary, the field-device schedule and the points requiring confirmation; adjust quantities or templates.

Which codes and standards does the bms architecture & panel slds follow?

It applies ISO 16484 (Parts 1–6), ASHRAE Standard 135 / ISO 16484-5 (BACnet), ASHRAE Guideline 36, ASHRAE Guideline 13, Modbus Application Protocol V1.1b3 / Serial Line V1.02, IEC 61131-2 / -3 and others. Every result line shows the formula and the clause it comes from, and the report lists the standards applied.

What does it check?

Every run is marked PASS or CHECK against: Every hardwired point on a module channel; Spare ≥ policy % per type in every panel; Channels within the controller capacity; Panels per MS/TP trunk and trunks per NLC within limits; Every soft-integrated system on a gateway / NLC port.

Is the calculator free to use?

Yes — running the calculation, reading the results, checks and clauses is free. One design credit unlocks the report, Excel and DXF exports for 30 days; the first design is free on sign-in.

Can I see a sample report before I use it?

Yes, a complete sample report for this tool is published at https://calc.designlink.in/samples/bms/ — inputs, results with basis, checks, worked example, drawing and the standards list.

Is this the same as a BMS architecture drawing?

Yes. People also call it a BMS panel SLD, a BMS system architecture DXF. It covers the same calculation under automation / elv design, with the Indian and international code regimes selectable.

Does it work with AutoCAD or ZWCAD?

Yes — with the free DesignLink CAD plugin the tool reads rooms, layers and selections from the open drawing and places its DXF output straight back into the plan; without the plugin you upload a DXF and download the result.