Auto sprinkler placement & piping
Give it the rooms — closed polylines from the plan DXF, a selection in AutoCAD / ZWCAD through the plugin, or the storeys of a Building-model project — set the hazard, head type and riser point, and it places every head to the code spacing and coverage (aligned to the room, snapped to the ceiling grid for pendent heads, respecting beam bays and filling the corners of L-shaped rooms), runs range pipes, cross mains and corridor mains back to the riser, splits the floor into zones at the code area limit, checks the remote area of every hazard hydraulically, and draws it all back into the drawing on layers.
What it does
Checks it performs
Sample report
Inputs, results with basis, checks, worked example, drawing and the standards list. Read it before you pay.
How to use it
- Set the design basis: code regime and rule set, default hazard (coverage and spacing per head follow), head type (upright, pendent, upright + pendent up-down for false ceilings, concealed, sidewall; pendent / concealed snap to the ceiling grid), temperature rating and response, material, velocity limit, zone area limit; pipe joints (all threaded, threaded ≤ 50 mm with welded or grooved above, all grooved, all welded); supports (rigid hangers or wire-rope kits) on an RCC slab or an industrial shed; typical details on / off.
- Add floors: pull every storey of a Building-model project, upload the floor-plan DXF and pick the room-boundary layer (room names from the text inside), read the selection straight from the drawing in the CAD plugin, or add rectangles; set level and ceiling height.
- Per room set hazard, head type, beam bay, zone or exclude where needed; mark corridors (auto from names) — the mains run along them. Place the riser by clicking the plan or picking it in the drawing.
- Read the plan, the room table, the zones with their remote-area cases and the checks; export the layout DXF (or draw it straight into the plan), the schedules Excel and the report; open a zone's Calc sheet for the submittal calculation on the real pipes.
What you enter
- Rooms — polygons with names; hazard, head type, beam bay, zone, exclude
- Floors — level, ceiling height, riser point
- Basis — regime, rule set, hazard, head type, grid snap, material, C, v max, hanger spacing, zone limit
What you get
- Heads — position per room, coverage, spacing, checks
- Piping — range / cross / main with sizes by schedule, hydraulically checked, hangers
- Zones — area vs limit, remote-area flow and pressure per hazard, feed size
- DXF / Excel / report / BOQ — layers, schedules, heads, pipe, hangers, FCV sets
Also searched as
sprinkler layout design; sprinkler spacing calculator; automatic sprinkler placement AutoCAD; number of sprinklers for a room; sprinkler layout as per IS 15105; sprinkler piping layout generator. The same calculation, the same clauses — one tool for fire fighting design under the Indian codes (NBC, IS, CPWD) or the international ones (IEC, NFPA, ASHRAE, EN).
Standards applied
| Reference | Title | Used for |
|---|---|---|
| IS 15105:2002 | Design and installation of fixed automatic sprinkler fire extinguishing systems | Sprinkler hazard classes, density / area, K factors, durations |
| NBCS 2026 (SP 7:2026) Part F | National Building Construction Standards — Fire and life safety | Means of egress (Tables 2–4, cl. 4.4.2), staircase / lobby / lift-well pressurisation (cl. 4.4.2.5, Table 5), emergency lighting (cl. 3.5.6), fire-fighting installations by occupancy (Tables 7A–7J), demand, pumps and duration (Tables 7K / 7M), mains (Table 8), hydrant pressure 3.5–7 bar (cl. 5.1.1 f), sprinklers (cl. 5.1.3), gaseous suppression (cl. 5.1.6 / 5.1.9) |
| NBC 2016 Part 4 | National Building Code — Fire and life safety | Occupant load (Table 5), exit width (Table 22), travel distance (Table 21), stair widths |
| NFPA 13:2022 | Standard for the Installation of Sprinkler Systems | Design densities, hydraulic calculation method, equivalent lengths |
| FM Global Data Sheets 2-0 / 3-26 / 3-2 / 3-7 / 3-10 | FM Global property loss prevention data sheets | Hazard categories, sprinkler demand, pumps, tanks, mains |
| UAE Fire & Life Safety Code 2018 | UAE Fire and Life Safety Code of Practice, ch. 9 | Gulf fire protection systems (NFPA basis) |
| SBC 801:2018 | Saudi Fire Code | Gulf fire protection (NFPA basis) |
| BS EN 12845:2015+A1:2019 | Fixed firefighting systems — automatic sprinkler systems — design, installation and maintenance | Hazard classes, design density and area of operation, head spacing and coverage, pipe sizing, water supplies |
| LPC Rules | LPC Rules for Automatic Sprinkler Installations (BS EN 12845 + technical bulletins) | UK sprinkler design practice |
Frequently asked
How do I use the Auto sprinkler placement & piping calculator?
Set the design basis: code regime and rule set, default hazard (coverage and spacing per head follow), head type (upright, pendent, upright + pendent up-down for false ceilings, concealed, sidewall; pendent / concealed snap to the ceiling grid), temperature rating and response, material, velocity limit, zone area limit; pipe joints (all threaded, threaded ≤ 50 mm with welded or grooved above, all grooved, all welded); supports (rigid hangers or wire-rope kits) on an RCC slab or an industrial shed; typical details on / off. Add floors: pull every storey of a Building-model project, upload the floor-plan DXF and pick the room-boundary layer (room names from the text inside), read the selection straight from the drawing in the CAD plugin, or add rectangles; set level and ceiling height. Per room set hazard, head type, beam bay, zone or exclude where needed; mark corridors (auto from names) — the mains run along them. Place the riser by clicking the plan or picking it in the drawing.
Which codes and standards does the auto sprinkler placement & piping follow?
It applies IS 15105:2002, NBCS 2026 (SP 7:2026) Part F, NBC 2016 Part 4, NFPA 13:2022, FM Global Data Sheets 2-0 / 3-26 / 3-2 / 3-7 / 3-10, UAE Fire & Life Safety Code 2018 and others. Every result line shows the formula and the clause it comes from, and the report lists the standards applied.
Is the calculator free to use?
Yes — running the calculation, reading the results, checks and clauses is free. One design credit unlocks the report, Excel and DXF exports for 30 days; the first design is free on sign-in.
Can I see a sample report before I use it?
Yes, a complete sample report for this tool is published at https://calc.designlink.in/samples/sprlayout/ — inputs, results with basis, checks, worked example, drawing and the standards list.
Is this the same as a sprinkler layout design?
Yes. People also call it a sprinkler spacing calculator, a automatic sprinkler placement AutoCAD, a number of sprinklers for a room. It covers the same calculation under fire fighting design, with the Indian and international code regimes selectable.
Does it work with AutoCAD or ZWCAD?
Yes — with the free DesignLink CAD plugin the tool reads rooms, layers and selections from the open drawing and places its DXF output straight back into the plan; without the plugin you upload a DXF and download the result.