All calculators
Electrical · Live

HT & LT panel GA drawings

From your SLD or an Excel feeder schedule to fabrication-ready panel drawings: switchgear picked from the catalogue by make and Icu, busbars sized by heat balance and IEC 60865, tier packing into columns and shipping sections, GA views, panel SLD, control schematics, wiring list, IEC 61439 verification, BOM by kg and metre, A3 DXF sheet set and a detailed 3D model with doors off. HT 11 / 33 kV VCB cubicles too.

IEC 61439-1/2:2020 / IS/IEC 61439IS 8623 (Part 1):1993IEC TR 60890:2014IEC 60865-1:2011IS/IEC 60529IEC 60947-2:2016 / IS/IEC 60947-2
What goes in, what comes out

You enter

  • SLD / VD project code, or the Excel feeder template
  • System, busbar, switchgear, control and wiring policies
  • Per-panel type, form, front, entry, sections

You get

  • A3 DXF sheet set: GA views, SLD, schematics, terminal plan
  • BOM (kg / m), wiring list, heat check, verification matrix
  • Report, Excel and the 3D model

What it does

Switchgear from the catalogueMake, frame, In, Icu, poles and release chosen by policy; overrides per feeder.
Busbars by heat balanceAl / Cu bars, neutral %, IEC 60865 forces and IEC 60890 temperature rise.
Tier packingFeeders packed into columns and shipping sections with the form of separation you set.
GA + SLD + schematicsFront, internal, top, rear, side and section views; panel SLD; schematics with wire numbers.
IEC 61439 verificationDesign-verification matrix, RDF, incomer vs ΣIb, Icu vs fault level, heat per column.
3D with doors offMicro-detailed model per panel; click any part for its description.

Checks it performs

PASS / CHECKBusbar rating ≥ incomer In with RDF
PASS / CHECKIncomer In ≥ Σ Ib of the feeders
PASS / CHECKDevice Icu ≥ fault level at the panel
PASS / CHECKTemperature rise per column within IEC 60890
PASS / CHECKForm of separation and IP as specified

Sample report

Also searched as

LT panel GA drawing; panel general arrangement drawing generator; electrical panel BOM and SLD; switchgear panel design IEC 61439; busbar sizing in LT panel; panel drawing automation AutoCAD. The same calculation, the same clauses — one tool for electrical design under the Indian codes (NBC, IS, CPWD) or the international ones (IEC, NFPA, ASHRAE, EN).

Standards applied

ReferenceTitleUsed for
IEC 61439-1/2:2020 / IS/IEC 61439Low-voltage switchgear and controlgear assembliesPanel construction (TTA/PTTA), busbar short-time withstand (Icw 1 s), temperature rise, IP rating
IS 8623 (Part 1):1993Low-voltage switchgear and controlgear assembliesPanel construction (superseded in part by IS/IEC 61439)
IEC TR 60890:2014Method of temperature-rise verification of low-voltage switchgear assemblies by calculationEnclosure air temperature rise (ΔT0.5 / ΔT1.0) from dissipated power and effective cooling surface
IEC 60865-1:2011Short-circuit currents — calculation of effectsElectrodynamic forces and thermal effects on busbars
IS/IEC 60529Degrees of protection provided by enclosures (IP code)IP rating of the panel and IPXXB with doors open
IEC 60947-2:2016 / IS/IEC 60947-2Low-voltage switchgear — Circuit-breakersACB/MCCB ratings Icu, Ics, Icw; release characteristics (L-S-I-G); selectivity definitions
IS/IEC 60947-4-1Contactors and motor-starters — electromechanicalAC-3 utilisation, starter ratings and overload relays for motor feeders
IS 2705 (Parts 1–4):1992Current transformersRatio, burden and accuracy class for metering (1.0), protection (5P10) and PS class CTs
IS/IEC 62271-200:2021AC metal-enclosed switchgear and controlgear 1 kV to 52 kVLSC2B-PM cubicle classification, internal-arc IAC AFLR, compartments and interlocks for HT panels
IS/IEC 62271-100High-voltage alternating-current circuit-breakersVCB ratings (In, Isc, TRV), operating sequence and endurance classes
IS 3427:1997AC metal-enclosed switchgear and controlgear 1 kV to 52 kVIndian practice for clearances, cable boxes and marking of HT switchgear
IEC 81346-2:2019Reference designation — classification of objectsFunction-oriented tagging (=Q breaker, -K contactor, -F protection, -X terminal, -P meter, -B CT)
IEC 60445:2021Identification of equipment terminals, conductor terminations and conductorsTerminal marking, wire numbering and colour identification inside the panel
IEC 60204-1:2016Safety of machinery — electrical equipment of machinesControl-circuit wiring sizes, colours and marking practice
IS 5578 / IS 11353Marking and arrangement for switchgear busbars, main connections and auxiliary wiringR / Y / B / black colour code and phase sequence arrangement
IEC 60617 / IS 12032Graphical symbols for diagramsSLD symbols (breakers, CT, PT, relays, transformer, generator)
CPWD General Specifications for Electrical Works (Part I Internal, Part IV Substation)CPWD specificationsVoltage-drop cascade limits, cable/wiring practice, panel and metering requirements
CEA (Measures relating to Safety and Electric Supply) Regulations, 2023Central Electricity Authority safety regulationsStatutory safety requirements for installations
IS 3043:2018Code of practice for earthingEarth bus, strip sizing, earthing of panels (future earthing tool)
IEC 60364-5-54:2011Low-voltage electrical installations — Earthing arrangements and protective conductorsEarth electrode, protective conductor sizing (adiabatic k), main equipotential bonding
IEC 61643-11:2011Surge protective devices connected to low-voltage power systemsSPD ratings (Iimp, In, Up)
NBCS 2026 (SP 7:2026) Part D Sec 2National Building Construction Standards — Electrical and allied installationsLoad assessment and diversity, circuits, cables (4-core), earthing, lightning protection, standby supply for fire & life-safety loads

Frequently asked

How do I use the HT & LT panel GA drawings calculator?

Open the tool, change the pre-filled example to your project, read the results, checks and worked steps as you type, then export the report, Excel and DXF.

Which codes and standards does the ht & lt panel ga drawings follow?

It applies IEC 61439-1/2:2020 / IS/IEC 61439, IS 8623 (Part 1):1993, IEC TR 60890:2014, IEC 60865-1:2011, IS/IEC 60529, IEC 60947-2:2016 / IS/IEC 60947-2 and others. Every result line shows the formula and the clause it comes from, and the report lists the standards applied.

What does it check?

Every run is marked PASS or CHECK against: Busbar rating ≥ incomer In with RDF; Incomer In ≥ Σ Ib of the feeders; Device Icu ≥ fault level at the panel; Temperature rise per column within IEC 60890; Form of separation and IP as specified.

Is the calculator free to use?

Yes — running the calculation, reading the results, checks and clauses is free. One design credit unlocks the report, Excel and DXF exports for 30 days; the first design is free on sign-in.

Can I see a sample report before I use it?

Yes, a complete sample report for this tool is published at https://calc.designlink.in/samples/panel/ — inputs, results with basis, checks, worked example, drawing and the standards list.

Is this the same as a LT panel GA drawing?

Yes. People also call it a panel general arrangement drawing generator, a electrical panel BOM and SLD, a switchgear panel design IEC 61439. It covers the same calculation under electrical design, with the Indian and international code regimes selectable.

Does it work with AutoCAD or ZWCAD?

Yes — with the free DesignLink CAD plugin the tool reads rooms, layers and selections from the open drawing and places its DXF output straight back into the plan; without the plugin you upload a DXF and download the result.