Voltage drop & cable sizing
Impedance-method voltage drop through the whole cascade, source to sub-panel to load. The tool picks the cable and the run, checks the cascade limit, coordinates breakers, links bus-bar trunking, fixes every failing feeder in one click and imports or exports the schedule as Excel.
What it does
Checks it performs
Sample report
Inputs, results with basis, checks, worked example, drawing and the standards list. Read it before you pay.
How to use it
- Choose the Design: Indian (IS 732 / CPWD) or International (IEC 60364). International loads the IEC preset (400 V, IEC breaker ratings, Annex G voltage-drop limits) and keeps every Indian code out of the results, report and Excel. Then pick a preset if needed — it sets the catalogue, derating and voltage-drop limits.
- Add feeders: From → To, kW (or A), length, phase, laying method; mark panels with 'is panel' so the tree builds.
- Press Autosize — cables, breakers and links are chosen; edit any cell to override, results recompute.
- Check the cumulative voltage drop column and the flags; fix the red rows.
- Save, then Report / Excel / DXF. Hand over to SLD, Short-circuit and Panel GA from the buttons.
What you enter
- Preset — CPWD or IEC catalogue, ambient, grouping and VD limits
- Feeder rows — from, to, load kW / A, PF, length m, phase, laying (air / duct / buried), runs, cable (auto)
- Panels — sections, incomers, fire / essential flags
What you get
- Cable schedule — size, runs, current, derated capacity, VD %, cumulative VD, breaker
- Load tree — connected / demand load per panel with diversity
- Report / Excel / DXF — calculation sheet with a worked example of the largest feeder, editable workbook, cable schedule drawing
Also searched as
voltage drop calculator; cable sizing calculator; cable size calculation as per IS 732; voltage drop calculation formula and online tool; LT cable sizing calculator India; cable selection chart with derating factor. The same calculation, the same clauses — one tool for electrical design under the Indian codes (NBC, IS, CPWD) or the international ones (IEC, NFPA, ASHRAE, EN).
Standards applied
| Reference | Title | Used for |
|---|---|---|
| IS 732:2019 | Code of practice for electrical wiring installations | Voltage-drop limits, cable selection, protection coordination (adopts IEC 60364) |
| IEC 60364-5-52:2009 | Low-voltage electrical installations — Selection and erection of wiring systems | Current-carrying capacity, derating (temperature, grouping, installation method), voltage drop ≤ 3–5 % |
| IEC 60364-4-43:2008 | Protection against overcurrent | Ib ≤ In ≤ Iz, adiabatic cable withstand I²t ≤ k²S² with k = 143 (Cu XLPE), 115 (Cu PVC), 94 (Al XLPE), 76 (Al PVC) |
| IS 1554 (Part 1):1988 | PVC insulated (heavy duty) electric cables up to 1100 V | Cable ratings, resistance and reactance data |
| IS 3961 (Part 2):1967 (reaffirmed) | Recommended current ratings for cables — PVC insulated and PVC sheathed heavy duty cables | Rating factors for ambient / ground temperature, soil thermal resistivity, depth of laying and grouping; installation categories (in air, in ground, in ducts) |
| IEC 60287-1-1 / 60287-2-1 | Electric cables — Calculation of the current rating | Temperature correction √((θmax−θamb)/(θmax−θref)) and depth-of-laying correction |
| IS 7098 (Part 1):1988 | Cross-linked polyethylene insulated PVC sheathed cables up to 1100 V | XLPE cable ratings (90 °C), resistance and reactance data |
| IS 694:2010 | PVC insulated cables for working voltages up to 1100 V | FRLS wiring conductors |
| CPWD General Specifications for Electrical Works (Part I Internal, Part IV Substation) | CPWD specifications | Voltage-drop cascade limits, cable/wiring practice, panel and metering requirements |
| IEC 60947-2:2016 / IS/IEC 60947-2 | Low-voltage switchgear — Circuit-breakers | ACB/MCCB ratings Icu, Ics, Icw; release characteristics (L-S-I-G); selectivity definitions |
| IEC 60898-1:2015 / IS/IEC 60898-1 | Circuit-breakers for overcurrent protection for household and similar installations (MCB) | B/C/D tripping bands (C: 5–10 × In), thermal tripping 1.13/1.45 × In |
| IS 13703 / IEC 60269-1 | Low-voltage fuses | I2 = 1.6 In for gG fuses in the overload rule |
| IEEE 141-1993 (Red Book) | Recommended practice for electric power distribution for industrial plants | Motor starting voltage dip (≥ 80–85 % at terminals), phase unbalance practice |
| IEC 60909-0:2016 | Short-circuit currents in three-phase a.c. systems — Calculation of currents | Impedance method, voltage factor c (1.05 / 1.10 max, 0.95 min), peak factor κ = 1.02 + 0.98·e^(−3R/X), Ik" = c·Un/(√3·Zk) |
| NBCS 2026 (SP 7:2026) Part D Sec 2 | National Building Construction Standards — Electrical and allied installations | Load assessment and diversity, circuits, cables (4-core), earthing, lightning protection, standby supply for fire & life-safety loads |
Frequently asked
How do I use the Voltage drop & cable sizing calculator?
Choose the Design: Indian (IS 732 / CPWD) or International (IEC 60364). International loads the IEC preset (400 V, IEC breaker ratings, Annex G voltage-drop limits) and keeps every Indian code out of the results, report and Excel. Then pick a preset if needed — it sets the catalogue, derating and voltage-drop limits. Add feeders: From → To, kW (or A), length, phase, laying method; mark panels with 'is panel' so the tree builds. Press Autosize — cables, breakers and links are chosen; edit any cell to override, results recompute.
Which codes and standards does the voltage drop & cable sizing follow?
It applies IS 732:2019, IEC 60364-5-52:2009, IEC 60364-4-43:2008, IS 1554 (Part 1):1988, IS 3961 (Part 2):1967 (reaffirmed), IEC 60287-1-1 / 60287-2-1 and others. Every result line shows the formula and the clause it comes from, and the report lists the standards applied.
What does it check?
Every run is marked PASS or CHECK against: Voltage drop per feeder ≤ 3 % (limit editable); Cumulative cascade drop ≤ 5 % from source; Cable current-carrying capacity Iz ≥ Ib after derating; Breaker In between Ib and Iz; Cable short-circuit withstand ≥ fault energy.
Is the calculator free to use?
Yes — running the calculation, reading the results, checks and clauses is free. One design credit unlocks the report, Excel and DXF exports for 30 days; the first design is free on sign-in.
Can I see a sample report before I use it?
Yes, a complete sample report for this tool is published at https://calc.designlink.in/samples/vd/ — inputs, results with basis, checks, worked example, drawing and the standards list.
Is this the same as a voltage drop calculator?
Yes. People also call it a cable sizing calculator, a cable size calculation as per IS 732, a voltage drop calculation formula and online tool. It covers the same calculation under electrical design, with the Indian and international code regimes selectable.
Does it work with AutoCAD or ZWCAD?
Yes — with the free DesignLink CAD plugin the tool reads rooms, layers and selections from the open drawing and places its DXF output straight back into the plan; without the plugin you upload a DXF and download the result.