Voltage drop & cable sizing

Impedance-method voltage drop through the whole cascade, source to sub-panel to load. The tool picks the cable and the run, checks the cascade limit, coordinates breakers, links bus-bar trunking, fixes every failing feeder in one click and imports or exports the schedule as Excel.

IS 732:2019IEC 60364-5-52:2009IEC 60364-4-43:2008IS 1554 (Part 1):1988IS 3961 (Part 2):1967 (reaffirmed)IEC 60287-1-1 / 60287-2-1

What it does

Full cascadeSource to sub-panel to load. Voltage drop adds up along the path and is checked against the cascade limit.
Auto cable and runSmallest cable that carries the current and keeps ΔU under the limit, with parallel runs when needed.
Derating and groupingAmbient, grouping and installation-method factors per IS 732 / IEC 60364.
Breaker coordinationBreaker rating against Iz and the cable short-circuit withstand at every node.
Fix allEvery failing feeder upsized in one click, with the change list beside it.
Excel in and outImport your feeder schedule, export the sized schedule and BOQ with live formulas.

Checks it performs

PASS / CHECKVoltage drop per feeder ≤ 3 % (limit editable)
PASS / CHECKCumulative cascade drop ≤ 5 % from source
PASS / CHECKCable current-carrying capacity Iz ≥ Ib after derating
PASS / CHECKBreaker In between Ib and Iz
PASS / CHECKCable short-circuit withstand ≥ fault energy

Sample report

How to use it

  1. Choose the Design: Indian (IS 732 / CPWD) or International (IEC 60364). International loads the IEC preset (400 V, IEC breaker ratings, Annex G voltage-drop limits) and keeps every Indian code out of the results, report and Excel. Then pick a preset if needed — it sets the catalogue, derating and voltage-drop limits.
  2. Add feeders: From → To, kW (or A), length, phase, laying method; mark panels with 'is panel' so the tree builds.
  3. Press Autosize — cables, breakers and links are chosen; edit any cell to override, results recompute.
  4. Check the cumulative voltage drop column and the flags; fix the red rows.
  5. Save, then Report / Excel / DXF. Hand over to SLD, Short-circuit and Panel GA from the buttons.

What you enter

  • Preset — CPWD or IEC catalogue, ambient, grouping and VD limits
  • Feeder rows — from, to, load kW / A, PF, length m, phase, laying (air / duct / buried), runs, cable (auto)
  • Panels — sections, incomers, fire / essential flags

What you get

  • Cable schedule — size, runs, current, derated capacity, VD %, cumulative VD, breaker
  • Load tree — connected / demand load per panel with diversity
  • Report / Excel / DXF — calculation sheet with a worked example of the largest feeder, editable workbook, cable schedule drawing

Also searched as

voltage drop calculator; cable sizing calculator; cable size calculation as per IS 732; voltage drop calculation formula and online tool; LT cable sizing calculator India; cable selection chart with derating factor. The same calculation, the same clauses — one tool for electrical design under the Indian codes (NBC, IS, CPWD) or the international ones (IEC, NFPA, ASHRAE, EN).

Standards applied

ReferenceTitleUsed for
IS 732:2019Code of practice for electrical wiring installationsVoltage-drop limits, cable selection, protection coordination (adopts IEC 60364)
IEC 60364-5-52:2009Low-voltage electrical installations — Selection and erection of wiring systemsCurrent-carrying capacity, derating (temperature, grouping, installation method), voltage drop ≤ 3–5 %
IEC 60364-4-43:2008Protection against overcurrentIb ≤ In ≤ Iz, adiabatic cable withstand I²t ≤ k²S² with k = 143 (Cu XLPE), 115 (Cu PVC), 94 (Al XLPE), 76 (Al PVC)
IS 1554 (Part 1):1988PVC insulated (heavy duty) electric cables up to 1100 VCable ratings, resistance and reactance data
IS 3961 (Part 2):1967 (reaffirmed)Recommended current ratings for cables — PVC insulated and PVC sheathed heavy duty cablesRating factors for ambient / ground temperature, soil thermal resistivity, depth of laying and grouping; installation categories (in air, in ground, in ducts)
IEC 60287-1-1 / 60287-2-1Electric cables — Calculation of the current ratingTemperature correction √((θmax−θamb)/(θmax−θref)) and depth-of-laying correction
IS 7098 (Part 1):1988Cross-linked polyethylene insulated PVC sheathed cables up to 1100 VXLPE cable ratings (90 °C), resistance and reactance data
IS 694:2010PVC insulated cables for working voltages up to 1100 VFRLS wiring conductors
CPWD General Specifications for Electrical Works (Part I Internal, Part IV Substation)CPWD specificationsVoltage-drop cascade limits, cable/wiring practice, panel and metering requirements
IEC 60947-2:2016 / IS/IEC 60947-2Low-voltage switchgear — Circuit-breakersACB/MCCB ratings Icu, Ics, Icw; release characteristics (L-S-I-G); selectivity definitions
IEC 60898-1:2015 / IS/IEC 60898-1Circuit-breakers for overcurrent protection for household and similar installations (MCB)B/C/D tripping bands (C: 5–10 × In), thermal tripping 1.13/1.45 × In
IS 13703 / IEC 60269-1Low-voltage fusesI2 = 1.6 In for gG fuses in the overload rule
IEEE 141-1993 (Red Book)Recommended practice for electric power distribution for industrial plantsMotor starting voltage dip (≥ 80–85 % at terminals), phase unbalance practice
IEC 60909-0:2016Short-circuit currents in three-phase a.c. systems — Calculation of currentsImpedance method, voltage factor c (1.05 / 1.10 max, 0.95 min), peak factor κ = 1.02 + 0.98·e^(−3R/X), Ik" = c·Un/(√3·Zk)
NBCS 2026 (SP 7:2026) Part D Sec 2National Building Construction Standards — Electrical and allied installationsLoad assessment and diversity, circuits, cables (4-core), earthing, lightning protection, standby supply for fire & life-safety loads

Frequently asked

How do I use the Voltage drop & cable sizing calculator?

Choose the Design: Indian (IS 732 / CPWD) or International (IEC 60364). International loads the IEC preset (400 V, IEC breaker ratings, Annex G voltage-drop limits) and keeps every Indian code out of the results, report and Excel. Then pick a preset if needed — it sets the catalogue, derating and voltage-drop limits. Add feeders: From → To, kW (or A), length, phase, laying method; mark panels with 'is panel' so the tree builds. Press Autosize — cables, breakers and links are chosen; edit any cell to override, results recompute.

Which codes and standards does the voltage drop & cable sizing follow?

It applies IS 732:2019, IEC 60364-5-52:2009, IEC 60364-4-43:2008, IS 1554 (Part 1):1988, IS 3961 (Part 2):1967 (reaffirmed), IEC 60287-1-1 / 60287-2-1 and others. Every result line shows the formula and the clause it comes from, and the report lists the standards applied.

What does it check?

Every run is marked PASS or CHECK against: Voltage drop per feeder ≤ 3 % (limit editable); Cumulative cascade drop ≤ 5 % from source; Cable current-carrying capacity Iz ≥ Ib after derating; Breaker In between Ib and Iz; Cable short-circuit withstand ≥ fault energy.

Is the calculator free to use?

Yes — running the calculation, reading the results, checks and clauses is free. One design credit unlocks the report, Excel and DXF exports for 30 days; the first design is free on sign-in.

Can I see a sample report before I use it?

Yes, a complete sample report for this tool is published at https://calc.designlink.in/samples/vd/ — inputs, results with basis, checks, worked example, drawing and the standards list.

Is this the same as a voltage drop calculator?

Yes. People also call it a cable sizing calculator, a cable size calculation as per IS 732, a voltage drop calculation formula and online tool. It covers the same calculation under electrical design, with the Indian and international code regimes selectable.

Does it work with AutoCAD or ZWCAD?

Yes — with the free DesignLink CAD plugin the tool reads rooms, layers and selections from the open drawing and places its DXF output straight back into the plan; without the plugin you upload a DXF and download the result.

Related electrical calculators