Power distribution design
One project from the point of supply to the last DB. Describe the sources — utility, HT cables, transformers with library %Z and X/R, main LT panel sections and couplers, DG or gas gensets with a synchronising panel, solar PV and battery storage as inverter sources — and the tool computes IEC 60909 fault levels at every bus for every supply scenario, sizes the whole cable schedule in one loop for ampacity, voltage drop, breaker coordination and short-circuit withstand, verifies the HT cables and draws the single-line diagram.
What it does
Checks it performs
Sample report
Inputs, results with basis, checks, worked example, drawing and the standards list. Read it before you pay.
How to use it
- Open Source of supply: utility kV and MVA, HT side, transformers (blank %Z / X/R = library by rating), DG or gas gensets, PV and battery storage, links; transformers on the same main panel become bus sections with a coupler.
- Enter the feeder schedule exactly as in the voltage-drop tool (or import Excel); choose the Design (Indian / International — International cites IEC only, no Indian code anywhere), the conductor policy and the short-circuit mode (auto-fix / check / off).
- Run integrated design: fault levels for every scenario → cable sizing loop → HT cables. Read the governing reason of every cable and the breaker Icu per bus.
- Export the report (with worked examples from this project: main-bus fault level, breaker Icu per scenario, feeder withstand, discrimination, governing LV feeder, HT cable), the Excel (schedule with reasons, fault levels, sources, HT cables) and the SLD DXF.
What you enter
- Sources — utility, HT panel, transformers, gensets, PV / BESS, couplers
- Feeders — from, to, kW / A, length, laying, phase, runs
- Policies — regime, Cu up to, SC mode, HT laying and clearing times
What you get
- Fault levels — every bus × scenario, breaker Icu
- Cable schedule — size, runs, VD, withstand, governing reason
- HT cables, report, Excel, SLD DXF —
Also searched as
power distribution design; cable schedule and fault level calculation; single line diagram generator; LT distribution design for building; fault level calculation IEC 60909 online; cable sizing with short circuit check. The same calculation, the same clauses — one tool for electrical design under the Indian codes (NBC, IS, CPWD) or the international ones (IEC, NFPA, ASHRAE, EN).
Standards applied
| Reference | Title | Used for |
|---|---|---|
| IEC 60909-0:2016 | Short-circuit currents in three-phase a.c. systems — Calculation of currents | Impedance method, voltage factor c (1.05 / 1.10 max, 0.95 min), peak factor κ = 1.02 + 0.98·e^(−3R/X), Ik" = c·Un/(√3·Zk) |
| IEC 60909-0:2016 | Short-circuit currents in three-phase AC systems — calculation of currents | Inverter-based sources as current sources; motor contribution; scenarios |
| IEC 60364-4-43:2008 | Protection against overcurrent | Ib ≤ In ≤ Iz, adiabatic cable withstand I²t ≤ k²S² with k = 143 (Cu XLPE), 115 (Cu PVC), 94 (Al XLPE), 76 (Al PVC) |
| IEC 60364-5-52:2009 | Low-voltage electrical installations — Selection and erection of wiring systems | Current-carrying capacity, derating (temperature, grouping, installation method), voltage drop ≤ 3–5 % |
| IEC 60287-1-1 / 60287-2-1 | Electric cables — Calculation of the current rating | Temperature correction √((θmax−θamb)/(θmax−θref)) and depth-of-laying correction |
| IEC 60949 | Calculation of thermally permissible short-circuit currents | Adiabatic and non-adiabatic cable withstand |
| IEC 60947-2:2016 / IS/IEC 60947-2 | Low-voltage switchgear — Circuit-breakers | ACB/MCCB ratings Icu, Ics, Icw; release characteristics (L-S-I-G); selectivity definitions |
| IEC 60898-1:2015 / IS/IEC 60898-1 | Circuit-breakers for overcurrent protection for household and similar installations (MCB) | B/C/D tripping bands (C: 5–10 × In), thermal tripping 1.13/1.45 × In |
| IEC 61439-1/2:2020 / IS/IEC 61439 | Low-voltage switchgear and controlgear assemblies | Panel construction (TTA/PTTA), busbar short-time withstand (Icw 1 s), temperature rise, IP rating |
| IEC 60076 (series) | Power transformers | Impedance, ratings and losses used for the fault study source model |
| IEC 60502-2 | Power cables with extruded insulation — 6 kV to 30 kV | HT cable construction and current ratings (international regime) |
| IEEE 141-1993 (Red Book) | Recommended practice for electric power distribution for industrial plants | Motor starting voltage dip (≥ 80–85 % at terminals), phase unbalance practice |
| IS 732:2019 | Code of practice for electrical wiring installations | Voltage-drop limits, cable selection, protection coordination (adopts IEC 60364) |
| IS 1554 (Part 1):1988 | PVC insulated (heavy duty) electric cables up to 1100 V | Cable ratings, resistance and reactance data |
| IS 7098 (Part 1):1988 | Cross-linked polyethylene insulated PVC sheathed cables up to 1100 V | XLPE cable ratings (90 °C), resistance and reactance data |
| IS 3961 (Part 2):1967 (reaffirmed) | Recommended current ratings for cables — PVC insulated and PVC sheathed heavy duty cables | Rating factors for ambient / ground temperature, soil thermal resistivity, depth of laying and grouping; installation categories (in air, in ground, in ducts) |
| IS 13234 (Part 1):2022 / IEC 60909-0 | Short-circuit currents in three-phase a.c. systems | Indian adoption of IEC 60909 |
| IS 2026 (Part 1):2011 / IEC 60076-1 | Power transformers | Impedance voltage, ratings, Dyn11 vector group |
| CPWD General Specifications for Electrical Works (Part I Internal, Part IV Substation) | CPWD specifications | Voltage-drop cascade limits, cable/wiring practice, panel and metering requirements |
| NBCS 2026 (SP 7:2026) Part D Sec 2 | National Building Construction Standards — Electrical and allied installations | Load assessment and diversity, circuits, cables (4-core), earthing, lightning protection, standby supply for fire & life-safety loads |
Frequently asked
How do I use the Power distribution design calculator?
Open Source of supply: utility kV and MVA, HT side, transformers (blank %Z / X/R = library by rating), DG or gas gensets, PV and battery storage, links; transformers on the same main panel become bus sections with a coupler. Enter the feeder schedule exactly as in the voltage-drop tool (or import Excel); choose the Design (Indian / International — International cites IEC only, no Indian code anywhere), the conductor policy and the short-circuit mode (auto-fix / check / off). Run integrated design: fault levels for every scenario → cable sizing loop → HT cables. Read the governing reason of every cable and the breaker Icu per bus.
Which codes and standards does the power distribution design follow?
It applies IEC 60909-0:2016, IEC 60909-0:2016, IEC 60364-4-43:2008, IEC 60364-5-52:2009, IEC 60287-1-1 / 60287-2-1, IEC 60949 and others. Every result line shows the formula and the clause it comes from, and the report lists the standards applied.
What does it check?
Every run is marked PASS or CHECK against: Breaker Icu ≥ Ik″ at its bus (worst scenario); Cable k²S² ≥ I²t (class-3 MCB let-through or adiabatic); Voltage drop per hop and cumulative within limits; Iz after derating ≥ Ib and ≥ breaker In; HT cable: Iz ≥ Ib, S ≥ Ik·√t/k, screen ≥ Ief·√t/k.
Is the calculator free to use?
Yes — running the calculation, reading the results, checks and clauses is free. One design credit unlocks the report, Excel and DXF exports for 30 days; the first design is free on sign-in.
Can I see a sample report before I use it?
Yes, a complete sample report for this tool is published at https://calc.designlink.in/samples/pdd/ — inputs, results with basis, checks, worked example, drawing and the standards list.
Is this the same as a power distribution design?
Yes. People also call it a cable schedule and fault level calculation, a single line diagram generator, a LT distribution design for building. It covers the same calculation under electrical design, with the Indian and international code regimes selectable.
Does it work with AutoCAD or ZWCAD?
Yes — with the free DesignLink CAD plugin the tool reads rooms, layers and selections from the open drawing and places its DXF output straight back into the plan; without the plugin you upload a DXF and download the result.