Power distribution design

One project from the point of supply to the last DB. Describe the sources — utility, HT cables, transformers with library %Z and X/R, main LT panel sections and couplers, DG or gas gensets with a synchronising panel, solar PV and battery storage as inverter sources — and the tool computes IEC 60909 fault levels at every bus for every supply scenario, sizes the whole cable schedule in one loop for ampacity, voltage drop, breaker coordination and short-circuit withstand, verifies the HT cables and draws the single-line diagram.

IEC 60909-0:2016IEC 60909-0:2016IEC 60364-4-43:2008IEC 60364-5-52:2009IEC 60287-1-1 / 60287-2-1IEC 60949

What it does

Source of supply wizardUtility kV and MVA, HT panel, transformers (library %Z / X/R by rating and type), DG / gas gensets (xd″ by rating), PV and battery inverters.
Main panel logicTransformers on the same panel become sections with a bus coupler; sync panel feeds the backed-up sections; NO / NC coupler changes the fault level.
Upstream and downstream fault levelsHT buses, LT main bus and every downstream panel for grid, DG and inverter scenarios — worst case governs breaker Icu and cable withstand.
One sizing loopAmpacity, VD cascade, breaker coordination and short-circuit withstand together; fault levels recomputed with the sized cables until stable; a reason on every cable.
HT cable verificationAmpacity with derating, withstand for the HV clearing time, screen withstand for the earth-fault current, voltage drop.
SLD DXFHT side, transformers, sections, couplers, DG sync panel, PV incomer and every feeder on one drawing.

Checks it performs

PASS / CHECKBreaker Icu ≥ Ik″ at its bus (worst scenario)
PASS / CHECKCable k²S² ≥ I²t (class-3 MCB let-through or adiabatic)
PASS / CHECKVoltage drop per hop and cumulative within limits
PASS / CHECKIz after derating ≥ Ib and ≥ breaker In
PASS / CHECKHT cable: Iz ≥ Ib, S ≥ Ik·√t/k, screen ≥ Ief·√t/k

Sample report

How to use it

  1. Open Source of supply: utility kV and MVA, HT side, transformers (blank %Z / X/R = library by rating), DG or gas gensets, PV and battery storage, links; transformers on the same main panel become bus sections with a coupler.
  2. Enter the feeder schedule exactly as in the voltage-drop tool (or import Excel); choose the Design (Indian / International — International cites IEC only, no Indian code anywhere), the conductor policy and the short-circuit mode (auto-fix / check / off).
  3. Run integrated design: fault levels for every scenario → cable sizing loop → HT cables. Read the governing reason of every cable and the breaker Icu per bus.
  4. Export the report (with worked examples from this project: main-bus fault level, breaker Icu per scenario, feeder withstand, discrimination, governing LV feeder, HT cable), the Excel (schedule with reasons, fault levels, sources, HT cables) and the SLD DXF.

What you enter

  • Sources — utility, HT panel, transformers, gensets, PV / BESS, couplers
  • Feeders — from, to, kW / A, length, laying, phase, runs
  • Policies — regime, Cu up to, SC mode, HT laying and clearing times

What you get

  • Fault levels — every bus × scenario, breaker Icu
  • Cable schedule — size, runs, VD, withstand, governing reason
  • HT cables, report, Excel, SLD DXF —

Also searched as

power distribution design; cable schedule and fault level calculation; single line diagram generator; LT distribution design for building; fault level calculation IEC 60909 online; cable sizing with short circuit check. The same calculation, the same clauses — one tool for electrical design under the Indian codes (NBC, IS, CPWD) or the international ones (IEC, NFPA, ASHRAE, EN).

Standards applied

ReferenceTitleUsed for
IEC 60909-0:2016Short-circuit currents in three-phase a.c. systems — Calculation of currentsImpedance method, voltage factor c (1.05 / 1.10 max, 0.95 min), peak factor κ = 1.02 + 0.98·e^(−3R/X), Ik" = c·Un/(√3·Zk)
IEC 60909-0:2016Short-circuit currents in three-phase AC systems — calculation of currentsInverter-based sources as current sources; motor contribution; scenarios
IEC 60364-4-43:2008Protection against overcurrentIb ≤ In ≤ Iz, adiabatic cable withstand I²t ≤ k²S² with k = 143 (Cu XLPE), 115 (Cu PVC), 94 (Al XLPE), 76 (Al PVC)
IEC 60364-5-52:2009Low-voltage electrical installations — Selection and erection of wiring systemsCurrent-carrying capacity, derating (temperature, grouping, installation method), voltage drop ≤ 3–5 %
IEC 60287-1-1 / 60287-2-1Electric cables — Calculation of the current ratingTemperature correction √((θmax−θamb)/(θmax−θref)) and depth-of-laying correction
IEC 60949Calculation of thermally permissible short-circuit currentsAdiabatic and non-adiabatic cable withstand
IEC 60947-2:2016 / IS/IEC 60947-2Low-voltage switchgear — Circuit-breakersACB/MCCB ratings Icu, Ics, Icw; release characteristics (L-S-I-G); selectivity definitions
IEC 60898-1:2015 / IS/IEC 60898-1Circuit-breakers for overcurrent protection for household and similar installations (MCB)B/C/D tripping bands (C: 5–10 × In), thermal tripping 1.13/1.45 × In
IEC 61439-1/2:2020 / IS/IEC 61439Low-voltage switchgear and controlgear assembliesPanel construction (TTA/PTTA), busbar short-time withstand (Icw 1 s), temperature rise, IP rating
IEC 60076 (series)Power transformersImpedance, ratings and losses used for the fault study source model
IEC 60502-2Power cables with extruded insulation — 6 kV to 30 kVHT cable construction and current ratings (international regime)
IEEE 141-1993 (Red Book)Recommended practice for electric power distribution for industrial plantsMotor starting voltage dip (≥ 80–85 % at terminals), phase unbalance practice
IS 732:2019Code of practice for electrical wiring installationsVoltage-drop limits, cable selection, protection coordination (adopts IEC 60364)
IS 1554 (Part 1):1988PVC insulated (heavy duty) electric cables up to 1100 VCable ratings, resistance and reactance data
IS 7098 (Part 1):1988Cross-linked polyethylene insulated PVC sheathed cables up to 1100 VXLPE cable ratings (90 °C), resistance and reactance data
IS 3961 (Part 2):1967 (reaffirmed)Recommended current ratings for cables — PVC insulated and PVC sheathed heavy duty cablesRating factors for ambient / ground temperature, soil thermal resistivity, depth of laying and grouping; installation categories (in air, in ground, in ducts)
IS 13234 (Part 1):2022 / IEC 60909-0Short-circuit currents in three-phase a.c. systemsIndian adoption of IEC 60909
IS 2026 (Part 1):2011 / IEC 60076-1Power transformersImpedance voltage, ratings, Dyn11 vector group
CPWD General Specifications for Electrical Works (Part I Internal, Part IV Substation)CPWD specificationsVoltage-drop cascade limits, cable/wiring practice, panel and metering requirements
NBCS 2026 (SP 7:2026) Part D Sec 2National Building Construction Standards — Electrical and allied installationsLoad assessment and diversity, circuits, cables (4-core), earthing, lightning protection, standby supply for fire & life-safety loads

Frequently asked

How do I use the Power distribution design calculator?

Open Source of supply: utility kV and MVA, HT side, transformers (blank %Z / X/R = library by rating), DG or gas gensets, PV and battery storage, links; transformers on the same main panel become bus sections with a coupler. Enter the feeder schedule exactly as in the voltage-drop tool (or import Excel); choose the Design (Indian / International — International cites IEC only, no Indian code anywhere), the conductor policy and the short-circuit mode (auto-fix / check / off). Run integrated design: fault levels for every scenario → cable sizing loop → HT cables. Read the governing reason of every cable and the breaker Icu per bus.

Which codes and standards does the power distribution design follow?

It applies IEC 60909-0:2016, IEC 60909-0:2016, IEC 60364-4-43:2008, IEC 60364-5-52:2009, IEC 60287-1-1 / 60287-2-1, IEC 60949 and others. Every result line shows the formula and the clause it comes from, and the report lists the standards applied.

What does it check?

Every run is marked PASS or CHECK against: Breaker Icu ≥ Ik″ at its bus (worst scenario); Cable k²S² ≥ I²t (class-3 MCB let-through or adiabatic); Voltage drop per hop and cumulative within limits; Iz after derating ≥ Ib and ≥ breaker In; HT cable: Iz ≥ Ib, S ≥ Ik·√t/k, screen ≥ Ief·√t/k.

Is the calculator free to use?

Yes — running the calculation, reading the results, checks and clauses is free. One design credit unlocks the report, Excel and DXF exports for 30 days; the first design is free on sign-in.

Can I see a sample report before I use it?

Yes, a complete sample report for this tool is published at https://calc.designlink.in/samples/pdd/ — inputs, results with basis, checks, worked example, drawing and the standards list.

Is this the same as a power distribution design?

Yes. People also call it a cable schedule and fault level calculation, a single line diagram generator, a LT distribution design for building. It covers the same calculation under electrical design, with the Indian and international code regimes selectable.

Does it work with AutoCAD or ZWCAD?

Yes — with the free DesignLink CAD plugin the tool reads rooms, layers and selections from the open drawing and places its DXF output straight back into the plan; without the plugin you upload a DXF and download the result.

Related electrical calculators