Short-circuit analysis
Three-phase fault levels at every bus of the cascade by IEC 60909: grid, transformers, generators and motor contribution, then the breaker Icu / Ics check and the cable adiabatic check, from a voltage-drop project or entered fresh.
You enter
- VD project code or sources entered fresh
- Grid MVA, transformer %Z, generator reactances, motors
- Cable data per branch
You get
- Fault levels per bus (kA)
- Breaker and cable check tables
- Report and Excel; kA to SLD and panel GA
What it does
Checks it performs
Sample report
Inputs, results with basis, checks, worked example, drawing and the standards list. Read it before you pay.
How to use it
- Link to the VD project or enter sources (grid MVA, transformers, generators, motors).
- Buses and branches follow the feeder tree; check impedances.
- Run: Ik'' / ip / Ib / Ith per bus, breaker Icu check, cable adiabatic check.
- Export the report and Excel; the kA values feed the SLD and panel GA.
What you enter
- Sources — grid fault level, transformer kVA / %Z, DG X''d, motor contribution
- Network — cables from the VD project
What you get
- Fault levels — 3-phase, 1-phase, peak per bus
- Checks — breaker Icu, cable k²S²
Also searched as
short circuit calculation; fault level calculation IEC 60909; short circuit current calculator online; breaker Icu Ics check; fault current at LT panel calculation; short circuit analysis software free. The same calculation, the same clauses — one tool for electrical design under the Indian codes (NBC, IS, CPWD) or the international ones (IEC, NFPA, ASHRAE, EN).
Standards applied
| Reference | Title | Used for |
|---|---|---|
| IEC 60909-0:2016 | Short-circuit currents in three-phase a.c. systems — Calculation of currents | Impedance method, voltage factor c (1.05 / 1.10 max, 0.95 min), peak factor κ = 1.02 + 0.98·e^(−3R/X), Ik" = c·Un/(√3·Zk) |
| IS 13234 (Part 1):2022 / IEC 60909-0 | Short-circuit currents in three-phase a.c. systems | Indian adoption of IEC 60909 |
| IS 8130:2013 | Conductors for insulated electric cables and flexible cords | Conductor resistance at 20 °C; temperature coefficient for fault-level resistance correction |
| IEC 60364-4-43:2008 | Protection against overcurrent | Ib ≤ In ≤ Iz, adiabatic cable withstand I²t ≤ k²S² with k = 143 (Cu XLPE), 115 (Cu PVC), 94 (Al XLPE), 76 (Al PVC) |
| IEC 60947-2:2016 / IS/IEC 60947-2 | Low-voltage switchgear — Circuit-breakers | ACB/MCCB ratings Icu, Ics, Icw; release characteristics (L-S-I-G); selectivity definitions |
| IEC 61439-1/2:2020 / IS/IEC 61439 | Low-voltage switchgear and controlgear assemblies | Panel construction (TTA/PTTA), busbar short-time withstand (Icw 1 s), temperature rise, IP rating |
| IS 1180 (Part 1):2014 | Outdoor type oil-immersed distribution transformers up to 2500 kVA, 33 kV | Typical impedance (%Z) by rating |
| IS 2026 (Part 1):2011 / IEC 60076-1 | Power transformers | Impedance voltage, ratings, Dyn11 vector group |
| IEC 60076-5:2006 | Power transformers — Ability to withstand short circuit | Transformer short-circuit impedance and withstand |
Frequently asked
How do I use the Short-circuit analysis calculator?
Link to the VD project or enter sources (grid MVA, transformers, generators, motors). Buses and branches follow the feeder tree; check impedances. Run: Ik'' / ip / Ib / Ith per bus, breaker Icu check, cable adiabatic check.
Which codes and standards does the short-circuit analysis follow?
It applies IEC 60909-0:2016, IS 13234 (Part 1):2022 / IEC 60909-0, IS 8130:2013, IEC 60364-4-43:2008, IEC 60947-2:2016 / IS/IEC 60947-2, IEC 61439-1/2:2020 / IS/IEC 61439 and others. Every result line shows the formula and the clause it comes from, and the report lists the standards applied.
What does it check?
Every run is marked PASS or CHECK against: Breaker Icu ≥ Ik″ at its bus; Breaker Ics ≥ the required service breaking capacity; Cable k²S² ≥ I²t for the clearing time; Peak current ip within the panel’s Ipk rating; Fault level at the LT bus ≤ the panel design kA.
Is the calculator free to use?
Yes — running the calculation, reading the results, checks and clauses is free. One design credit unlocks the report, Excel and DXF exports for 30 days; the first design is free on sign-in.
Can I see a sample report before I use it?
Yes, a complete sample report for this tool is published at https://calc.designlink.in/samples/sc/ — inputs, results with basis, checks, worked example, drawing and the standards list.
Is this the same as a short circuit calculation?
Yes. People also call it a fault level calculation IEC 60909, a short circuit current calculator online, a breaker Icu Ics check. It covers the same calculation under electrical design, with the Indian and international code regimes selectable.
Does it work with AutoCAD or ZWCAD?
Yes — with the free DesignLink CAD plugin the tool reads rooms, layers and selections from the open drawing and places its DXF output straight back into the plan; without the plugin you upload a DXF and download the result.