All calculators
Electrical · Live

Short-circuit analysis

Three-phase fault levels at every bus of the cascade by IEC 60909: grid, transformers, generators and motor contribution, then the breaker Icu / Ics check and the cable adiabatic check, from a voltage-drop project or entered fresh.

IEC 60909-0:2016IS 13234 (Part 1):2022 / IEC 60909-0IS 8130:2013IEC 60364-4-43:2008IEC 60947-2:2016 / IS/IEC 60947-2IEC 61439-1/2:2020 / IS/IEC 61439
What goes in, what comes out

You enter

  • VD project code or sources entered fresh
  • Grid MVA, transformer %Z, generator reactances, motors
  • Cable data per branch

You get

  • Fault levels per bus (kA)
  • Breaker and cable check tables
  • Report and Excel; kA to SLD and panel GA

What it does

Ik″, ip, Ib, IthInitial symmetrical, peak, breaking and thermal currents per bus with the c-factor and R/X.
SourcesGrid MVA and X/R, transformers with %Z, generators with xd″, motor contribution.
Follows the cascadeBuses and branches come from the voltage-drop feeder tree; impedances from the cable data.
Breaker checkIcu and Ics against the fault level at each device, with the release settings.
Cable withstandk²S² ≥ I²t adiabatic check per cable with the clearing time.
Feeds the drawingskA values go to the SLD and the panel GA verification matrix.

Checks it performs

PASS / CHECKBreaker Icu ≥ Ik″ at its bus
PASS / CHECKBreaker Ics ≥ the required service breaking capacity
PASS / CHECKCable k²S² ≥ I²t for the clearing time
PASS / CHECKPeak current ip within the panel’s Ipk rating
PASS / CHECKFault level at the LT bus ≤ the panel design kA

Sample report

How to use it

  1. Link to the VD project or enter sources (grid MVA, transformers, generators, motors).
  2. Buses and branches follow the feeder tree; check impedances.
  3. Run: Ik'' / ip / Ib / Ith per bus, breaker Icu check, cable adiabatic check.
  4. Export the report and Excel; the kA values feed the SLD and panel GA.

What you enter

  • Sources — grid fault level, transformer kVA / %Z, DG X''d, motor contribution
  • Network — cables from the VD project

What you get

  • Fault levels — 3-phase, 1-phase, peak per bus
  • Checks — breaker Icu, cable k²S²

Also searched as

short circuit calculation; fault level calculation IEC 60909; short circuit current calculator online; breaker Icu Ics check; fault current at LT panel calculation; short circuit analysis software free. The same calculation, the same clauses — one tool for electrical design under the Indian codes (NBC, IS, CPWD) or the international ones (IEC, NFPA, ASHRAE, EN).

Standards applied

ReferenceTitleUsed for
IEC 60909-0:2016Short-circuit currents in three-phase a.c. systems — Calculation of currentsImpedance method, voltage factor c (1.05 / 1.10 max, 0.95 min), peak factor κ = 1.02 + 0.98·e^(−3R/X), Ik" = c·Un/(√3·Zk)
IS 13234 (Part 1):2022 / IEC 60909-0Short-circuit currents in three-phase a.c. systemsIndian adoption of IEC 60909
IS 8130:2013Conductors for insulated electric cables and flexible cordsConductor resistance at 20 °C; temperature coefficient for fault-level resistance correction
IEC 60364-4-43:2008Protection against overcurrentIb ≤ In ≤ Iz, adiabatic cable withstand I²t ≤ k²S² with k = 143 (Cu XLPE), 115 (Cu PVC), 94 (Al XLPE), 76 (Al PVC)
IEC 60947-2:2016 / IS/IEC 60947-2Low-voltage switchgear — Circuit-breakersACB/MCCB ratings Icu, Ics, Icw; release characteristics (L-S-I-G); selectivity definitions
IEC 61439-1/2:2020 / IS/IEC 61439Low-voltage switchgear and controlgear assembliesPanel construction (TTA/PTTA), busbar short-time withstand (Icw 1 s), temperature rise, IP rating
IS 1180 (Part 1):2014Outdoor type oil-immersed distribution transformers up to 2500 kVA, 33 kVTypical impedance (%Z) by rating
IS 2026 (Part 1):2011 / IEC 60076-1Power transformersImpedance voltage, ratings, Dyn11 vector group
IEC 60076-5:2006Power transformers — Ability to withstand short circuitTransformer short-circuit impedance and withstand

Frequently asked

How do I use the Short-circuit analysis calculator?

Link to the VD project or enter sources (grid MVA, transformers, generators, motors). Buses and branches follow the feeder tree; check impedances. Run: Ik'' / ip / Ib / Ith per bus, breaker Icu check, cable adiabatic check.

Which codes and standards does the short-circuit analysis follow?

It applies IEC 60909-0:2016, IS 13234 (Part 1):2022 / IEC 60909-0, IS 8130:2013, IEC 60364-4-43:2008, IEC 60947-2:2016 / IS/IEC 60947-2, IEC 61439-1/2:2020 / IS/IEC 61439 and others. Every result line shows the formula and the clause it comes from, and the report lists the standards applied.

What does it check?

Every run is marked PASS or CHECK against: Breaker Icu ≥ Ik″ at its bus; Breaker Ics ≥ the required service breaking capacity; Cable k²S² ≥ I²t for the clearing time; Peak current ip within the panel’s Ipk rating; Fault level at the LT bus ≤ the panel design kA.

Is the calculator free to use?

Yes — running the calculation, reading the results, checks and clauses is free. One design credit unlocks the report, Excel and DXF exports for 30 days; the first design is free on sign-in.

Can I see a sample report before I use it?

Yes, a complete sample report for this tool is published at https://calc.designlink.in/samples/sc/ — inputs, results with basis, checks, worked example, drawing and the standards list.

Is this the same as a short circuit calculation?

Yes. People also call it a fault level calculation IEC 60909, a short circuit current calculator online, a breaker Icu Ics check. It covers the same calculation under electrical design, with the Indian and international code regimes selectable.

Does it work with AutoCAD or ZWCAD?

Yes — with the free DesignLink CAD plugin the tool reads rooms, layers and selections from the open drawing and places its DXF output straight back into the plan; without the plugin you upload a DXF and download the result.

Related electrical calculators