All calculators
Electrical · Live

Bus bar / bus duct sizing

Bars per phase and size by heat balance for open, enclosed or bus-duct installation, current density, the short-circuit minimum section, force between phases, support spacing and losses, with alternatives side by side.

NBCS 2026 (SP 7:2026) Part D Sec 2IEC 61439-1/2:2020 / IS/IEC 61439IS 8623 (Part 1):1993IEC 60865-1:2011IS 5082:1998IEC 60909-0:2016
What goes in, what comes out

You enter

  • Duty current, rise, material, enclosure
  • Fault level Ith / ip, duration
  • Bar arrangement or auto

You get

  • Bars per phase and size, losses, forces
  • Alternatives table
  • Report

What it does

Size by heat balanceConvection and radiation against the allowed rise; enclosed and busduct factors.
Short-circuit sectionMinimum section for Ith and 1 s; adiabatic check for the chosen bars.
Forces and supportsForce between phases at ip, support spacing from the bar stress.
LossesI²R losses per metre with the AC resistance and skin effect.
AlternativesSeveral bar arrangements that pass, ranked by copper mass.
ReportEvery step with the clause and the substituted values.

Checks it performs

PASS / CHECKTemperature rise ≤ allowed (IEC 61439-1 Table 6)
PASS / CHECKCurrent density ≤ the design limit
PASS / CHECKSection ≥ short-circuit minimum
PASS / CHECKBar stress ≤ 0.8 × yield at the support spacing
PASS / CHECKSupport spacing ≤ the mechanical limit

Sample report

Also searched as

busbar sizing calculator; bus duct sizing calculation; busbar size for current rating copper aluminium; busbar short circuit force calculation; busbar support spacing; busbar current rating chart. The same calculation, the same clauses — one tool for electrical design under the Indian codes (NBC, IS, CPWD) or the international ones (IEC, NFPA, ASHRAE, EN).

Standards applied

ReferenceTitleUsed for
NBCS 2026 (SP 7:2026) Part D Sec 2National Building Construction Standards — Electrical and allied installationsLoad assessment and diversity, circuits, cables (4-core), earthing, lightning protection, standby supply for fire & life-safety loads
IEC 61439-1/2:2020 / IS/IEC 61439Low-voltage switchgear and controlgear assembliesPanel construction (TTA/PTTA), busbar short-time withstand (Icw 1 s), temperature rise, IP rating
IS 8623 (Part 1):1993Low-voltage switchgear and controlgear assembliesPanel construction (superseded in part by IS/IEC 61439)
IEC 60865-1:2011Short-circuit currents — calculation of effectsElectrodynamic forces and thermal effects on busbars
IS 5082:1998Wrought aluminium and copper for electrical purposesBusbar material properties
IEC 60909-0:2016Short-circuit currents in three-phase a.c. systems — Calculation of currentsImpedance method, voltage factor c (1.05 / 1.10 max, 0.95 min), peak factor κ = 1.02 + 0.98·e^(−3R/X), Ik" = c·Un/(√3·Zk)

Frequently asked

How do I use the Bus bar / bus duct sizing calculator?

Open the tool, change the pre-filled example to your project, read the results, checks and worked steps as you type, then export the report, Excel and DXF.

Which codes and standards does the bus bar / bus duct sizing follow?

It applies NBCS 2026 (SP 7:2026) Part D Sec 2, IEC 61439-1/2:2020 / IS/IEC 61439, IS 8623 (Part 1):1993, IEC 60865-1:2011, IS 5082:1998, IEC 60909-0:2016. Every result line shows the formula and the clause it comes from, and the report lists the standards applied.

What does it check?

Every run is marked PASS or CHECK against: Temperature rise ≤ allowed (IEC 61439-1 Table 6); Current density ≤ the design limit; Section ≥ short-circuit minimum; Bar stress ≤ 0.8 × yield at the support spacing; Support spacing ≤ the mechanical limit.

Is the calculator free to use?

Yes — running the calculation, reading the results, checks and clauses is free. One design credit unlocks the report, Excel and DXF exports for 30 days; the first design is free on sign-in.

Can I see a sample report before I use it?

Yes, a complete sample report for this tool is published at https://calc.designlink.in/samples/busbar/ — inputs, results with basis, checks, worked example, drawing and the standards list.

Is this the same as a busbar sizing calculator?

Yes. People also call it a bus duct sizing calculation, a busbar size for current rating copper aluminium, a busbar short circuit force calculation. It covers the same calculation under electrical design, with the Indian and international code regimes selectable.

Does it work with AutoCAD or ZWCAD?

Yes — with the free DesignLink CAD plugin the tool reads rooms, layers and selections from the open drawing and places its DXF output straight back into the plan; without the plugin you upload a DXF and download the result.

Related electrical calculators