Electrical · Live

Earthing & earth mat

Rod, plate and strip electrode resistance, the number of pits for the target ohms with the R-vs-N table, earth strip with corrosion allowance, PE conductor, and the IEEE 80 substation grid: Rg, GPR, mesh and step voltages against the tolerable limits.

NBCS 2026 (SP 7:2026) Part D Sec 2IS 3043:2018IEEE Std 80-2013IEC 60364-5-54:2011CEA (Measures relating to Safety and Electric Supply) Regulations, 2023

What it does

ElectrodesRod, plate, strip and pipe resistance from soil resistivity; parallel pits with spacing factor.
Pits for the target ΩR-vs-N table so you can see when adding pits stops helping.
Strip and PE conductorSizes for the fault current with corrosion allowance; IS 3043 minimums.
IEEE 80 gridRg, GPR, mesh and step voltages for the grid with rods.
Tolerable limitsStep and touch limits for the body weight, surface layer and clearing time.
ReportWith the standards list and a drawing of the grid.

Checks it performs

PASS / CHECKEarth resistance ≤ target (1 Ω substation / 5 Ω general)
PASS / CHECKMesh voltage ≤ tolerable touch voltage
PASS / CHECKStep voltage ≤ tolerable step voltage
PASS / CHECKConductor section ≥ fault-current minimum
PASS / CHECKGPR flagged when it exceeds 5 kV

Sample report

Also searched as

earthing calculation IS 3043; earth pit calculation; earth mat design IEEE 80; number of earth pits for target resistance; earthing strip size calculation; step and touch voltage calculation. The same calculation, the same clauses — one tool for electrical design under the Indian codes (NBC, IS, CPWD) or the international ones (IEC, NFPA, ASHRAE, EN).

Standards applied

ReferenceTitleUsed for
NBCS 2026 (SP 7:2026) Part D Sec 2National Building Construction Standards — Electrical and allied installationsLoad assessment and diversity, circuits, cables (4-core), earthing, lightning protection, standby supply for fire & life-safety loads
IS 3043:2018Code of practice for earthingEarth bus, strip sizing, earthing of panels (future earthing tool)
IEEE Std 80-2013Guide for Safety in AC Substation GroundingEarth grid resistance, touch and step voltages
IEC 60364-5-54:2011Low-voltage electrical installations — Earthing arrangements and protective conductorsEarth electrode, protective conductor sizing (adiabatic k), main equipotential bonding
CEA (Measures relating to Safety and Electric Supply) Regulations, 2023Central Electricity Authority safety regulationsStatutory safety requirements for installations

Frequently asked

How do I use the Earthing & earth mat calculator?

Open the tool, change the pre-filled example to your project, read the results, checks and worked steps as you type, then export the report, Excel and DXF.

Which codes and standards does the earthing & earth mat follow?

It applies NBCS 2026 (SP 7:2026) Part D Sec 2, IS 3043:2018, IEEE Std 80-2013, IEC 60364-5-54:2011, CEA (Measures relating to Safety and Electric Supply) Regulations, 2023. Every result line shows the formula and the clause it comes from, and the report lists the standards applied.

What does it check?

Every run is marked PASS or CHECK against: Earth resistance ≤ target (1 Ω substation / 5 Ω general); Mesh voltage ≤ tolerable touch voltage; Step voltage ≤ tolerable step voltage; Conductor section ≥ fault-current minimum; GPR flagged when it exceeds 5 kV.

Is the calculator free to use?

Yes — running the calculation, reading the results, checks and clauses is free. One design credit unlocks the report, Excel and DXF exports for 30 days; the first design is free on sign-in.

Can I see a sample report before I use it?

Yes, a complete sample report for this tool is published at https://calc.designlink.in/samples/earthing/ — inputs, results with basis, checks, worked example, drawing and the standards list.

Is this the same as a earthing calculation IS 3043?

Yes. People also call it a earth pit calculation, a earth mat design IEEE 80, a number of earth pits for target resistance. It covers the same calculation under electrical design, with the Indian and international code regimes selectable.

Does it work with AutoCAD or ZWCAD?

Yes — with the free DesignLink CAD plugin the tool reads rooms, layers and selections from the open drawing and places its DXF output straight back into the plan; without the plugin you upload a DXF and download the result.