All calculators
Electrical · Live

IDMT relay setting & grading

Plug setting from the load, operating time at the fault current from the IEC 60255-151 inverse curves (SI, VI, EI, LTI), TMS chosen so each relay grades with the one below — also across a transformer — with the time-current curves on a log-log chart.

IEC 60255-151:2009IEEE Std 242-2001 (Buff Book)IEC 60909-0:2016
What goes in, what comes out

You enter

  • Relays: kV, CT ratio, plug, TMS, curve
  • Maximum fault current at each relay
  • Grading margin, TMS step

You get

  • Settings table with times and margins
  • Time-current curves
  • Worked example and report

What it does

Plug settingPick-up above full load with the overload margin, in plug steps.
Operating timet = TMS · k / ((I/Is)^α − 1) at the maximum fault.
GradingTMS for the margin against the downstream relay, voltage ratio across transformers.
CurvesLog-log time-current curves of every relay with the trip points.

Checks it performs

PASS / CHECKPick-up ≥ load × margin
PASS / CHECKEvery relay operates at its fault current
PASS / CHECKGrading margin ≥ the set margin at the downstream maximum fault

Sample report

Also searched as

IDMT relay setting calculation; relay grading calculation; IDMT curve calculator TMS PSM; overcurrent earth fault relay setting; transformer relay setting calculation. The same calculation, the same clauses — one tool for electrical design under the Indian codes (NBC, IS, CPWD) or the international ones (IEC, NFPA, ASHRAE, EN).

Standards applied

ReferenceTitleUsed for
IEC 60255-151:2009Measuring relays — Overcurrent protection functional requirementsIDMT / definite-time characteristics used in discrimination curves
IEEE Std 242-2001 (Buff Book)Recommended practice for protection and coordination of industrial and commercial power systemsRelay grading margins and coordination practice
IEC 60909-0:2016Short-circuit currents in three-phase a.c. systems — Calculation of currentsImpedance method, voltage factor c (1.05 / 1.10 max, 0.95 min), peak factor κ = 1.02 + 0.98·e^(−3R/X), Ik" = c·Un/(√3·Zk)

Frequently asked

How do I use the IDMT relay setting & grading calculator?

Open the tool, change the pre-filled example to your project, read the results, checks and worked steps as you type, then export the report, Excel and DXF.

Which codes and standards does the idmt relay setting & grading follow?

It applies IEC 60255-151:2009, IEEE Std 242-2001 (Buff Book), IEC 60909-0:2016. Every result line shows the formula and the clause it comes from, and the report lists the standards applied.

What does it check?

Every run is marked PASS or CHECK against: Pick-up ≥ load × margin; Every relay operates at its fault current; Grading margin ≥ the set margin at the downstream maximum fault.

Is the calculator free to use?

Yes — running the calculation, reading the results, checks and clauses is free. One design credit unlocks the report, Excel and DXF exports for 30 days; the first design is free on sign-in.

Can I see a sample report before I use it?

Yes, a complete sample report for this tool is published at https://calc.designlink.in/samples/idmt/ — inputs, results with basis, checks, worked example, drawing and the standards list.

Is this the same as a IDMT relay setting calculation?

Yes. People also call it a relay grading calculation, a IDMT curve calculator TMS PSM, a overcurrent earth fault relay setting. It covers the same calculation under electrical design, with the Indian and international code regimes selectable.

Does it work with AutoCAD or ZWCAD?

Yes — with the free DesignLink CAD plugin the tool reads rooms, layers and selections from the open drawing and places its DXF output straight back into the plan; without the plugin you upload a DXF and download the result.

Related electrical calculators