Lighting design (lux)
Type or import the room schedule, pick each room's type and luminaire, press Run: the engine reads the luminaire's IES / LDT file, lays out the grid, computes the illuminance point by point with interreflections, and returns Ē, Emin, Emax, Uo and the layout for every room — then marks the emergency luminaires E and checks the emergency scene.
You enter
You get
What it does
Checks it performs
Sample report
Inputs, results with basis, checks, worked example, drawing and the standards list. Read it before you pay.
How to use it
- Set the design basis once: regime (Indian / International), project Uo, wall zone, and the category profiles — MF, reflectances, mounting height and calculation plane for utility, enclosed, parking and outdoor areas (the PMC's numbers go here).
- Add rooms (or import the schedule, or pull every room of a Building-model project with its real shape — L-shaped corridors and lobbies are calculated on the polygon): floor, name, type, L × W × ceiling. The type fills the required lux and Uo from the regime's table; every value can be typed over.
- Pick a luminaire per room from the shared library — search by make, model, watts or kind; upload the manufacturer's IES / LDT once and it stays for everyone.
- Run design: the count and grid are converged on the real point-by-point + radiosity calculation; read Ē, Emin, Emax, Uo, the false-colour plan and the checks. Fix Qty, grid or luminaire where a room fails.
- Emergency: luminaires marked E are the fewest that give the target lux (EN 1838 / NBC or % of normal); the emergency scene is reported per room.
- Open the 3D view of any room (false-colour illuminance on the plane, luminaires at mounting height) and read the calculated UGR against the regime limit.
- Export the report (room sheets like DIALux, luminaire data sheets with polar curves), the Excel (schedule, BOQ, positions, grids) and the DXF layout.
What you enter
- Rooms — floor, name, type, L, W, ceiling height, optional polygon
- Design basis — regime, Uo, wall zone, MF / ρ / mounting / plane per category, emergency policy, LPD basis
- Luminaire — library entry (IES / LDT) per room
- Overrides — lux, Uo, MF, ρ, Hm, plane, Qty, nx × ny, rotation, wall clearance, emergency kind
What you get
- Per room — Ē, Emin, Emax, Uo, g2, UF, layout, grid, checks, emergency scene
- Report — design basis, luminaire list, results table, room sheets with plans
- Excel / DXF — schedule with formulas, BOQ, positions, grid values; layout drawing on layers
Also searched as
lux calculation for room; lighting design calculator lux level; number of lights required for a room; lumen method calculation online; lighting layout DIALux alternative; emergency lighting design EN 1838. The same calculation, the same clauses — one tool for electrical design under the Indian codes (NBC, IS, CPWD) or the international ones (IEC, NFPA, ASHRAE, EN).
Standards applied
| Reference | Title | Used for |
|---|---|---|
| NBCS 2026 (SP 7:2026) Part D Sec 1 | National Building Construction Standards — Lighting and natural ventilation | Illuminance and lighting quality by room (Table 6), daylight, natural ventilation |
| NBCS 2026 (SP 7:2026) Part F | National Building Construction Standards — Fire and life safety | Means of egress (Tables 2–4, cl. 4.4.2), staircase / lobby / lift-well pressurisation (cl. 4.4.2.5, Table 5), emergency lighting (cl. 3.5.6), fire-fighting installations by occupancy (Tables 7A–7J), demand, pumps and duration (Tables 7K / 7M), mains (Table 8), hydrant pressure 3.5–7 bar (cl. 5.1.1 f), sprinklers (cl. 5.1.3), gaseous suppression (cl. 5.1.6 / 5.1.9) |
| NBC 2016 Part 8 Sec 1 | National Building Code — Lighting and natural ventilation | Recommended illuminance by activity, uniformity, emergency lighting, daylighting |
| IS 3646 (Part 1):1992 | Code of practice for interior illumination — general requirements and recommendations for working interiors | Illuminance schedule, uniformity, glare, maintenance |
| SP 72:2010 | National Lighting Code (BIS) | Lighting design practice, luminaire selection, maintenance factors |
| IS 1944 (Parts 1–6) | Code of practice for lighting of public thoroughfares | Outdoor / road lighting classes and levels |
| ECBC 2017 (BEE) | Energy Conservation Building Code — superseded by ECSBC 2024; still enforced where a State has not yet notified ECSBC 2024 | Envelope U / SHGC and lighting power density (India option) |
| EN 12464-1:2021 | Light and lighting — Lighting of work places — Part 1: Indoor work places | Required Ēm, Uo, UGR, Ra by activity; calculation grid (§4.4) |
| EN 12464-2:2014 | Light and lighting — Lighting of work places — Part 2: Outdoor work places | Outdoor areas, car parks, loading yards |
| EN 1838:2013 | Lighting applications — Emergency lighting | Escape route 1 lx, open area 0.5 lx, uniformity 40:1, duration |
| ISO 8995-1 / CIE S 008 | Lighting of work places — Part 1: Indoor | Illuminance and quality criteria (international) |
| ASHRAE 90.1-2019 | Energy Standard for Buildings | Lighting power density by space type |
| IES LM-63-2019 | Standard file format for the electronic transfer of photometric data | IES luminaire files (candela tables) used by the engine |
| EULUMDAT | European luminaire data format (.ldt) | LDT luminaire files (cd/klm tables) used by the engine |
| CIE 52 / CIE 40 | Calculations for interior lighting — applied method / basic method | Point-by-point direct illuminance and interreflection (radiosity) |
| IEC 60598-1 / IS 10322 | Luminaires — general requirements and tests | Luminaire safety and IP classification |
Frequently asked
How do I use the Lighting design (lux) calculator?
Set the design basis once: regime (Indian / International), project Uo, wall zone, and the category profiles — MF, reflectances, mounting height and calculation plane for utility, enclosed, parking and outdoor areas (the PMC's numbers go here). Add rooms (or import the schedule, or pull every room of a Building-model project with its real shape — L-shaped corridors and lobbies are calculated on the polygon): floor, name, type, L × W × ceiling. The type fills the required lux and Uo from the regime's table; every value can be typed over. Pick a luminaire per room from the shared library — search by make, model, watts or kind; upload the manufacturer's IES / LDT once and it stays for everyone.
Which codes and standards does the lighting design (lux) follow?
It applies NBCS 2026 (SP 7:2026) Part D Sec 1, NBCS 2026 (SP 7:2026) Part F, NBC 2016 Part 8 Sec 1, IS 3646 (Part 1):1992, SP 72:2010, IS 1944 (Parts 1–6) and others. Every result line shows the formula and the clause it comes from, and the report lists the standards applied.
What does it check?
Every run is marked PASS or CHECK against: Ē ≥ required illuminance; Uo = Emin / Ē ≥ project or standard value; Spacing / mounting height; Emergency Emin and Emax / Emin; LPD ≤ ECSBC / ASHRAE limit.
Is the calculator free to use?
Yes — running the calculation, reading the results, checks and clauses is free. One design credit unlocks the report, Excel and DXF exports for 30 days; the first design is free on sign-in.
Can I see a sample report before I use it?
Yes, a complete sample report for this tool is published at https://calc.designlink.in/samples/lux/ — inputs, results with basis, checks, worked example, drawing and the standards list.
Is this the same as a lux calculation for room?
Yes. People also call it a lighting design calculator lux level, a number of lights required for a room, a lumen method calculation online. It covers the same calculation under electrical design, with the Indian and international code regimes selectable.
Does it work with AutoCAD or ZWCAD?
Yes — with the free DesignLink CAD plugin the tool reads rooms, layers and selections from the open drawing and places its DXF output straight back into the plan; without the plugin you upload a DXF and download the result.